Line voltages
|
380 … 480 V 3 AC, ±10 % (-15 % < 1 min)
500 … 690 V 3 AC, ±10 % (-15 % < 1 min)
|
|
Line supply types
|
Grounded TN/TT systems and non-grounded IT systems
|
|
Line frequency
|
47 … 63 Hz
|
|
Output frequency 1)
|
|
|
|
0 … 650 Hz
|
|
|
0 … 600 Hz
|
|
|
0 … 600 Hz
|
|
Line power factor Fundamental
|
|
|
|
> 0.96
|
|
|
> 0.96
|
|
|
Adjustable (factory-set to cos ? = 1)
|
|
Efficiency
|
|
|
|
> 99.0 %
|
|
|
> 98.5 %
|
|
|
> 97.5 % (including Active Interface Module)
|
|
|
> 98.5 %
|
|
Overvoltage category
|
III to EN 61800?5?1
|
|
Control method
|
Vector/servo control with and without encoder or V/f control
|
|
Fixed speeds
|
15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/PROFIBUS/PROFINET)
|
|
Skipped speed ranges
|
4, parameterizable
|
|
Setpoint resolution
|
0.001 rpm digital (14 bit + sign) 12 bit analog
|
|
Braking operation
|
With Active Line Modules and Smart Line Modules, four-quadrant operation as standard (energy recovery). With Basic Line Modules, single-quadrant operation as standard. Braking when the power fails using an optional braking module.
|
|
Mechanical specifications
|
|
Degree of protection
|
IP20 (higher degrees of protection up to IP54 optional)
|
|
Protection class
|
I acc. to EN 61800?5?1
|
|
Touch protection
|
EN 50274/BGV A3 for the intended purpose
|
|
Cabinet system
|
Rittal TS 8, doors with double-barb lock, three-section base plates for cable entry
|
|
Paint finish
|
RAL 7035 (indoor requirements)
|
|
Type of cooling
|
Forced air cooling AF to EN 60146
|
|
Ambient conditions
|
Storage 2)
|
Transport 2)
|
Operation
|
|
Ambient temperature
|
-25 ... +55 °C
|
-25 ... +70 °C from -40 °C3) for 24 hours
|
0 ... +40 °C to +50 °C, see derating data
|
|
Relative humidity
(condensation not permissible)
|
5 ... 95 %
3)
Class 1K4 acc. to IEC 60721?3?1
|
5 ... 95 % at 40 °C Class 2K3 acc. to IEC 60721?3?2
|
5 ... 95 % 3) Class 3K3 acc. to IEC 60721?3?3
|
|
Environmental class/harmful chemical substances
|
Class 1C2 acc. to EN 60721?3?1
|
Class 2C2 acc. to EN 60721?3?2
|
Class 3C2 acc. to EN 60721?3?3
|
|
Organic/biological influences
|
Class 1B1 acc. to EN 60721?3?1
|
Class 2B1 acc. to EN 60721?3?2
|
Class 3B1 acc. to EN 60721?3?3
|
|
Degree of pollution
|
2 acc. to EN 61800?5?1
|
2 acc. to EN 61800?5?1
|
2 acc. to EN 61800?5?1
|
|
Installation altitude
|
Cabinet Modules, chassis format: up to 2000 m above sea level, without derating, > 2000 m, see characteristic curves/derating data
For Motor Modules Booksize Cabinet Kit format as well as Central Braking Modules: up to 1000 m above sea level without derating, > 1000 m, see characteristic curves/derating data
|
|
Mechanical stability
|
Storage 2)
|
Transport 2)
|
Operation
|
|
Vibration load
|
Class 1M1 acc. to EN 60721?3?1
|
Class 2M1 acc. to EN 60721?3?2
|
–
|
|
|
1.5 mm at 5 ... 9 Hz
|
3.1 mm at 5 ... 9 Hz
|
0.075 mm at 10 ... 58 Hz
|
|
|
5 m/s? at > 9 ... 200 Hz
|
10 m/s? at > 9 ... 200 Hz
|
9.8 m/s? at > 58 ... 200 Hz
|
|
Shock load
|
Class 1M1 acc. to EN 60721?3?1
|
Class 2M1 acc. to EN 60721?3?2
|
Class 3M1 acc. to EN 60721?3?3
|
|
|
40 m/s? at 22 ms
|
100 m/s? at 11 ms
|
100 m/s? at 11 ms
|
|
Compliance with standards
|
|
Conformances/approvals, according to
|
CE (EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC)
|
|
Radio interference suppression
|
SINAMICS drive converter systems are not designed for connection to the public network (first environment). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3, "Second environment" (industrial line supplies). The equipment can cause electromagnetic interference when it is connected to the public network. However, if supplementary measures are taken (e.g. > line filter), it can also be operated in the "first environment".
|