Classification
|
Class I Division 2
|
|
Enclosure dimensions (in mm)
|
444 x 438 x 275
|
|
Enclosure volume (I)
|
Approx. 50 l
|
|
Enclosure pressure (normal)
|
1 hPa
|
|
FM certificate
|
Certificate of compliance 1X8A4.AE / 0B3A3.AE
|
|
Reaction upon failure of pressure
|
Opening of switching contact, and alarm via signal indicator (red display)
|
|
System type
|
MiniPurge complete system
|
|
Operating mode
|
Continuous purging
|
|
Type of enclosure
|
Reinforced polycarbonate
|
|
Enclosure surface
|
RAL 7035 gray with transparent cover
|
|
Pressure supply
|
Dry, oil-free air or inert gas with regulated pressure of approx. 2000 hPa (30 psi) at inlet of MiniPurge
|
|
Supply connections
|
Pressure via ? BSPP connection, pressure hose at least ?" or 12 mm
|
|
Display (signal indicator)
|
Pneumatically driven color signal: green/red
|
|
Switching contact
|
Via SPCO switch approved for Class 1 Division 2
|
|
Settings
|
Lower response limit 0.5 hPa set relative to purging gas flow of 1 … 2 l/min
|
|
Prepurging time
|
Is defined by operator, and controlled manually
|
|
Enclosure pressure limitation
|
By means of stainless steel with integrated flame arrestor; opens at 10 hPa ± 10%
|