Input
|
|
|
Pulse input
|
NAMUR signal
|
|
Frequency
|
NAMUR: 0 ... 500 Hz
|
|
Sensor supply
|
8.2 V or 24 V DC
|
|
Output
|
|
|
Pulse output
|
Max. frequency 500 Hz, pulse width 1 ... 9999 ms adjustable.
Type: Transistor output, max. load 24 V DC/170 mA (active) and 50 V DC/300 mA (passive)
|
|
Analog output
|
Range 0/4 ... 20 mA, accuracy: < ± 0,1 %, resolution 12 bit, response time (10 ... 90 %): 100 ms, load max. 750 ?, active or passive. Function: flow 0/4 ... 20 mA freely adjustable
|
|
Functionality
|
|
|
Operator
|
The total value and flow are displayed. The total value is deleted by double-pressing the "CLEAR" key. The total value and the accumulated total are displayed by pressing the "SELECT“ key.
|
|
Total value
|
17 mm (0.67 inch) high, 7 digits, max. 3 decimal places; the total value cannot be deleted.
Units: l, m3, gal, USg, kg, lb, bbl or none
K-factor: 7-digit 0.000010 to 9 999 999
Settings independent of flow
|
|
Accumulated total
|
8 mm high, max. 11 digits, max. 3 decimal places,
the accumulated total cannot be reset
|
|
Flow
|
8 mm (0.31 inch) or 17 mm (0.65 inch) high, max. 7 digits, max. 3 decimal places
Units: ml, l, m3, mg, g, kg, ton, NI, Nm?, scf, ref, cf, lb, bbl, gal or none
Time units: seconds, minutes, hours, days
|
|
Installation conditions
|
|
|
Operating temperature
|
-40 ... +80 °C (-40 ... +176 °F)
|
|
Degree of protection
|
IP67 (NEMA 4)
|
|
Construction
|
|
|
Material
|
Housing: aluminum, UV-resistant powder coating
Window: polycarbonate
Sealing material: EPDM and PE
|
|
Dimensions
|
See Dimensional drawings
|
|
Auxiliary power supply
|
|
|
Power supply
|
24 V AC/DC ± 10 % or 115/230 V AC ± 10 %
|
|
Power consumption
|
Max. 9 W
|
|
Certificates and approvals
|
|
|
Ex protection
|
EEx ia IIB/IIC T4
|
|
For official calibration inspections
|
In preparation
|
|
|