Rating for 6SE70 Compact and chassis units |
|||
---|---|---|---|
Номинальное напряжение |
|||
Напряжение питания VSupply |
3 380 V -15 % |
3 500 V -15 % |
3 660 V -15 % |
до 480 V +10 % |
до 600 V +10 % |
до 690 V +15 % |
|
напряжение постоянного тока VD |
DC 510 V -15 % |
DC 675 V -15 % |
DC 890 V -15 % |
до 650 V +10 % |
до 810 V +10 % |
до 930 V +15 % |
|
Выходное напряжение |
|||
|
3 0 V до VSupply |
3 0 V до VSupply |
3 0 V до VSupply |
|
3 AC 0 V до 0.75 x VD |
3 AC 0 V до 0.75 x VD |
3 AC 0 V до 0.75 x VD |
Rated frequency |
|||
Supply frequency |
50/60 Hz (±6 %) |
50/60 Hz (±6 %) |
50/60 Hz (±6 %) |
Output frequency |
|||
|
0 Hz to 200 Hz(500 Hz for textile) |
0 Hz to 200 Hz |
0 Hz to 200 Hz |
|
8 Hz to 300 Hz |
8 Hz to 300 Hz |
8 Hz to 300 Hz |
depending on powerup |
depending on powerup |
depending on powerup |
|
Pulse frequency |
|||
Minimum pulse frequency |
1.7 kHz |
1.7 kHz |
1.7 kHz |
Factory setting |
2.5 kHz |
2.5 kHz |
2.5 kHz |
Maximum setting |
depending on powerup to 16 kHz |
depending on powerup to 16 kHz |
depending on powerup to 7.5 kHz |
Load class II to EN 60 146-1-1 |
|||
Base load current |
0.91 x rated output current |
||
Short-time current |
1.36 x rated output current for 60 s or |
||
1.60 x rated output current for 30 s for units up to size G and a maximum supply voltage of 600 V |
|||
Cycle time |
300 s |
||
Power factor |
|||
|
0.98 |
||
|
0.93 to 0.96 |
||
Efficiency |
0.96 to 0.98 |
||
Water cooling |
|||
Cooling-water inlet temperature |
Depending on the cooling-water temperature and the ambient temperature, meausres must be taken to provide protection against condensation in accordance with the engineering information If antifreeze is added, the perfomrance of the cooling system is reduced (lower heat conductance and greater viscosity). Recommended antifreeze is „Antiforgen N“ available from Clariant (Internet address, see below1).The antifreeze agent is intended to prevent damage in the event of plant shutdown and frost. Operation at temperatures of <0°C is not permissible even when antifreeze is used! |
||
(temperature of incoming water) |
5°C to 38°C |
||
Temperature increase of cooling water during rated operation |
ca. 5 K |
||
Max. grain size of particles in water |
< 0.1 mm |
||
Ph level of cooling water |
6.0 to 8.0 |
||
Conductivity (proportion of water in the cooling water) |
< 500 S/cm |
||
Chloride |
< 40 ppm |
||
Sulphate |
< 50 ppm |
||
Total hardness |
< 170 ppm |
||
Operating pressure |
|||
Sizes B to G |
max 1 bar |
||
Size K |
max. 2.5 bar |
Каталог 2018 | Каталог 2017 | Каталог 2016 | Каталог 2015 | Каталог 2014 | Каталог 2013 | Каталог 2012 | Сертификат | Контакты | Карта сайта | Поиск |