Rated voltages | 380 ... 480 V 3 AC ±10 % (-15 % <1 min) 500 ... 690 V 3 AC ±10 % (-15 % <1 min) |
Line supply types | Grounded TN/TT systems and non-grounded IT systems |
Line frequency | 47 ... 63 Hz |
Overvoltage category | III to EN 61800-5-1 |
Electronics power supply | 24 V DC, -15 % +20 % implemented as PELV circuit in accordance with EN 61800-5-1 Ground = negative pole grounded via the electronics |
Rated short-circuit current per IEC, in conjunction with the specified fuses or circuit breakers | |
| 65 kA |
| 84 kA |
| 170 kA |
| 200 kA |
Rated short-circuit current SCCR (Short Circuit Current Rating) according to UL508C (up to 600 V), in conjunction with the specified fuses or circuit breakers | |
| 65 kA |
| 84 kA |
| 170 kA |
| 200 kA |
Control method | Vector/Servo control with and without encoder or V/f control |
Fixed speeds | 15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/PROFIBUS/PROFINET) |
Skippable speed ranges | 4, parameterizable |
Setpoint resolution | 0.001 rpm digital (14 bits + sign) 12 bits analog |
Braking operation | With Active Line Modules and Smart Line Modules, four-quadrant operation as standard (energy recovery). With Basic Line Modules, two-quadrant operation as standard, braking by means of an optional braking chopper, or alternatively by a Motor Module. |
Mechanical specifications |
Degree of protection | IP00 or IP20 depending on type |
Protection class | I acc. to EN 61800‑5‑1 |
Touch protection | EN 50274/DGUV regulation 3 when used as intended |
Cooling method | Forced air cooling AF according to EN 60146 |
Ambient conditions | Storage 1) | Transport 1) | Operation |
Ambient temperature | -25 ... +55 °C (-13 ... 131 °F) Class 1K4 acc. to EN 60721-3-1 | -25 ... +70 °C (-13 ... +158 °F) Class 2K4 acc. to EN 60721-3-2 | Line-side components, Power Modules, Line Modules and Motor Modules: 0 … 40 °C (32 ... 104 °F) without derating Up to 55 °C (131 °F), see derating data Control Units, supplementary system components, and Sensor Modules: 0 ... 55 °C (32 ... 131 °F) (for operation in a control cabinet) DC link components and motor-side components: 0 ... 55 °C (32 ... 131 °F) |
Relative humidity Condensation, splashwater, and ice formation not permitted (EN 60204, Part 1) | 5 ... 95 % Class 1K4 acc. to EN 60721‑3‑1 | 5 ... 95 % at 40 °C (104 °F) Class 2K3 acc. to EN 60721‑3‑2 | 5 ... 95 % Class 3K3 acc. to EN 60721‑3‑3 |
Environmental class/harmful chemical substances | Class 1C2 acc. to EN 60721‑3‑1 | Class 2C2 acc. to EN 60721‑3‑2 | Class 3C2 acc. to EN 60721‑3‑3 |
Organic/biological influences | Class 1B1 acc. to EN 60721‑3‑1 | Class 2B1 acc. to EN 60721‑3‑2 | Class 3B1 acc. to EN 60721‑3‑3 |
Degree of pollution | 2 acc. to EN 61800‑5‑1 |
Installation altitude | Up to 2000 m (6562 ft) above sea level without derating >2000 m (6562 ft) above sea level, see derating data |
Mechanical stability | Storage 1) | Transport 1) | Operation |
Vibratory load | – | Class 2M2 acc. to EN 60721‑3‑2 | Test values acc. to EN 60068‑2‑6 test Fc: - 10 ... 58 Hz with constant deflection 0.075 mm
- 58 ... 150 Hz with constant acceleration 9.81 m/s2 (1 Г— g)
|
Shock load | – | Class 2M2 acc. to EN 60721‑3‑2 | Test values according to EN 60068‑2‑27 test Ea: 98 m/s2 (10 Г— g)/20 ms |
Compliance with standards |
Conformances/ certificates of suitability, according to | CE (EMC Directive No. 2014/30/EU, Low Voltage Directive No. 2014/35/EU, and Machinery Directive 2006/42/EC for functional safety) RCM, RoHS II cULus (only for devices connected to line supply voltages 380 ... 480 V 3 AC and 500 ... 600 V 3 AC) |
Radio interference suppression | SINAMICS S120 chassis format units are not designed for connection to the public grid (first environment). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3, "Second environment" (industrial line supplies). EMC disturbances can occur when connected to the public grid. However, if additional measures are taken (e.g. в†’ line filter), it can also be operated in the "first environment". For further information, see section Configuring information. |