Line voltage 380 ... 480 V 3 AC | Active Interface Module |
|---|
| 6SL3305-7TE38-4AA5 | 6SL3305-7TE41-4AA5 |
|---|
Suitable for Active Line Module | | | | | | | kW | 380 | 500 | 630 | 900 | | | 6SL3335-7TE36-1AA3 | 6SL3335-7TE38-4AA3 | 6SL3335-7TE41-0AA3 | 6SL3335-7TE41-4AA3 | Rated current | A | 605 | 840 | 985 | 1405 | Bypass contactor 1) | | 3RT1476-6AP36 | 3WL1110-2BB34-4AN2-Z C22 2) | 3WL1112-2BB34-4AN2-Z C22 2) | 3WL1116-2BB34-4AN2-Z C22 2) | Current demand | | | | | | - 24 V DC auxiliary power supply
| A | 0.17 | 0.17 | 0.17 | 0.17 | | | | | | | | A | 1.0 | 1.0 | 1.0 | 1.0 | | A | 0.1 | 0.1 | 0.1 | 0.1 | DC link capacitance of the drive line-up, max. 3) | μF | 134400 | 134400 | 230400 | 230400 | Coolant volume flow | l/min (US gal./min) | 10 (2.64) | 10 (2.64) | 16 (4.23) | 16 (4.23) | Pressure drop, typ. for volume flow | Pa | 70000 | 70000 | 70000 | 70000 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 71/71 | 71/71 | 71/71 | 71/71 | Frame size | | JIL | JIL | JIL | JIL | Filter reactor | Power loss 4) | | | | | | | kW | 3.5 | 3.5 | 8.6 | 8.6 | | kW | 3.5 | 3.5 | 8.6 | 8.6 | - Dissipated to ambient air
| kW | 1.2 | 1.2 | 0.9 | 0.9 | Liquid volume | | | | | | - Of integrated reactor cooler
| dm3 | 0.6 | 0.6 | 0.6 | 0.6 | | dm3/m | 0.285 | 0.285 | 0.285 | 0.285 | Coolant volume flow | l/min (US gal./min) | 10 (2.64) | 10 (2.64) | 8 (2.11) | 8 (2.11) | Pressure drop, typ. for volume flow | Pa | 70000 | 70000 | 70000 | 70000 | Heat exchanger material | | Aluminum | Aluminum | Aluminum | Aluminum | Coolant connections Return and connection to filter module | | Pipe thread ISO 228 G 3/4 B (external thread 3/4", flat-sealing) | Line/load connection L1, L2, L3 / U2, V2, W2 | | Flat connector for M12 screws | Flat connector for M12 screws | Flat connector for M12 screws | Flat connector for M12 screws | PE/GND connection | | M10 stud | M10 stud | M10 stud | M10 stud | - Conductor cross-section, max. (IEC)
| mm2 | 1 × 240 | 1 × 240 | 1 × 240 | 1 × 240 | Degree of protection | | IP00 | IP00 | IP00 | IP00 | Dimensions | | | | | | | mm (in) | 349 (13.7) | 349 (13.7) | 382 (15.0) | 382 (15.0) | | mm (in) | 700 (27.6) | 700 (27.6) | 698 (27.5) | 698 (27.5) | | mm (in) | 575 (22.6) | 575 (22.6) | 575 (22.6) | 575 (22.6) | Weight, approx. | kg (lb) | 230 (507) | 230 (507) | 299 (659) | 299 (659) | Filter module | Power loss 4) | | | | | | | kW | 2.7 | 2.7 | 3.6 | 3.6 | | kW | 2.7 | 2.7 | 3.6 | 3.6 | - Dissipated to ambient air
| kW | 0.15 | 0.15 | 0.15 | 0.15 | Liquid volume | dm3 | 1 | 1 | 1 | 1 | Heat exchanger material | | Aluminum | Aluminum | Aluminum | Aluminum | Coolant connections Intake and connection to filter reactor | | Pipe thread ISO 228 G 3/4 B (external thread 3/4", flat-sealing) | PE/GND connection | | Flat connector for M8 screw | Flat connector for M8 screw | Flat connector for M8 screw | Flat connector for M8 screw | - Conductor cross-section, max. (IEC)
| mm2 | 2 × 120 | 2 × 120 | 2 × 120 | 2 × 120 | Degree of protection | | IP00 | IP00 | IP00 | IP00 | Dimensions | | | | | | | mm (in) | 506 (19.9) | 506 (19.9) | 506 (19.9) | 506 (19.9) | | mm (in) | 840 (33.1) | 840 (33.1) | 840 (33.1) | 840 (33.1) | | mm (in) | 574 (22.6) | 574 (22.6) | 574 (22.6) | 574 (22.6) | Weight, approx. | kg (lb) | 110 (243) | 110 (243) | 110 (243) | 110 (243) |
1) The bypass contactor is not included in the scope of supply. 2) The breakers must only be switched ON and OFF by the sequence control. An interlocking set 3WL9111‑0BA21‑0AA0 as described in Catalog LV 10 should be provided for the bypass contactor to exclude the risk of unintentional manual operation. Manual operation bypasses the pre-charging circuit and can therefore destroy the Active Line Module. 3)Information on higher capacitances is included in the SINAMICS Low Voltage Engineering Manual. 4) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual. Line voltage 500 ... 690 V 3 AC | Active Interface Modules |
|---|
| 6SL3305-7TG37-4AA5 | 6SL3305-7TG41-0AA5 | 6SL3305-7TG41-3AA5 | 6SL3305-7TG41-6AA5 |
|---|
Suitable for Active Line Module | | | | | | | kW | 800 | 900/1100 | 1400 | 1700 | | | 6SL3335-7TG37-4AA3 | 6SL3335-7TG38-1AA3 6SL3335-7TG41-0AA3 | 6SL3335-7TG41-3AA3 | 6SL3335-7TG41-6AA3 | Rated current | A | 735 | 1025 | 1270 | 1560 | Bypass contactor 1) | | 3RT1476-6AP36 (3 units) | 3WL1212-4BB34-4AN2-Z C22 2) | 3WL1216-4BB34-4AN2-Z C22 2) | 3WL1216-4BB34-4AN2-Z C22 2) | Current demand | | | | | | - 24 V DC auxiliary power supply
| A | 0.17 | 0.17 | 0.17 | 0.17 | | | | | | | | A | 1.0 | 1.0 | 1.0 | 1.0 | | A | 0.1 | 0.1 | 0.1 | 0.1 | DC link capacitance of the drive line-up, max. 3) | μF | 153600 | 153600 | 153600 | 210000 | Coolant volume flow | l/min (US gal./min) | 10 (2.64) | 16 (4.23) | 16 (4.23) | 16 (4.23) | Pressure drop, typ. for volume flow | Pa | 70000 | 70000 | 70000 | 70000 | Sound pressure level LpA (1 m) at 50/60 Hz | dB | 71/71 | 71/71 | 71/71 | 71/71 | Frame size | | JIL | JIL | JIL | JIL | Filter reactor | Power loss 4) | | | | | | | kW | 5.5 | 6.2 | 9.3 | 11.0 | | kW | 5.5 | 6.2 | 9.3 | 11.0 | - Dissipated to ambient air
| kW | 0.5 | 0.6 | 0.95 | 1.15 | Liquid volume | | | | | | - Of integrated reactor cooler
| dm3 | 0.6 | 0.6 | 0.6 | 0.6 | | dm3/m | 0.285 | 0.285 | 0.285 | 0.285 | Coolant volume flow | l/min (US gal./min) | 10 (2.64) | 10 (2.64) | 10 (2.64) | 8 (2.11) | Pressure drop, typ. for volume flow | Pa | 70000 | 70000 | 70000 | 70000 | Heat exchanger material | | Aluminum | Aluminum | Aluminum | Aluminum | Coolant connections Return and connection to filter module | | Pipe thread ISO 228 G 3/4 B (external thread 3/4", flat-sealing) | Line/load connection L1, L2, L3 / U2, V2, W2 | | Flat connector for M12 screws | Flat connector for M12 screws | Flat connector for M12 screws | Flat connector for M12 screws | PE/GND connection | | M10 stud | M10 stud | M10 stud | M10 stud | - Conductor cross-section, max. (IEC)
| mm2 | 1 × 240 | 1 × 240 | 1 × 240 | 1 × 240 | Degree of protection | | IP00 | IP00 | IP00 | IP00 | Dimensions | | | | | | | mm (in) | 358 (14.1) | 440 (17.3) | 440 (17.3) | 440 (17.3) | | mm (in) | 675 (26.6) | 705 (27.8) | 705 (27.8) | 705 (27.8) | | mm (in) | 575 (22.6) | 575 (22.6) | 575 (22.6) | 580 (22.8) | Weight, approx. | kg (lb) | 234 (516) | 365 (805) | 365 (805) | 365 (805) | Filter module | Power loss 4) | | | | | | | kW | 4.0 | 5.0 | 5.0 | 7.5 | | kW | 4.0 | 5.0 | 5.0 | 7.5 | - Dissipated to ambient air
| kW | 0.15 | 0.15 | 0.15 | 0.15 | Liquid volume | dm3 | 1 | 1 | 1 | 1 | Heat exchanger material | | Aluminum | Aluminum | Aluminum | Aluminum | Coolant connections Intake and connection to filter reactor | | Pipe thread ISO 228 G 3/4 B (external thread 3/4", flat-sealing) | PE/GND connection | | Flat connector for M8 screw | Flat connector for M8 screw | Flat connector for M8 screw | Flat connector for M8 screw | - Conductor cross-section, max. (IEC)
| mm2 | 2 × 120 | 2 × 120 | 2 × 120 | 2 × 120 | Degree of protection | | IP00 | IP00 | IP00 | IP00 | Dimensions | | | | | | | mm (in) | 506 (19.9) | 506 (19.9) | 506 (19.9) | 506 (19.9) | | mm (in) | 840 (33.1) | 840 (33.1) | 840 (33.1) | 840 (33.1) | | mm (in) | 574 (22.6) | 574 (22.6) | 574 (22.6) | 574 (22.6) | Weight, approx. | kg (lb) | 110 (243) | 110 (243) | 110 (243) | 110 (243) |
1) The bypass contactor is not included in the scope of supply. 2) The breakers must only be switched ON and OFF by the sequence control. An interlocking set 3WL9111‑0BA21‑0AA0 as described in Catalog LV 10 should be provided for the bypass contactor to exclude the risk of unintentional manual operation. Manual operation bypasses the pre-charging circuit and can therefore destroy the Active Line Module. 3)Information on higher capacitances is included in the SINAMICS Low Voltage Engineering Manual. 4) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.
|
|