The Motor Modules in the chassis format have the following interfaces as standard: - 1 motor connection
- 1 connection for the 24 V DC electronics power supply
- 1 DC link connection (DCP, DCN) for connecting to the supply DC link
- 1 DC link connection (DCPA, DCNA) for connecting a Braking Module
- 1 DC link connection (DCPS, DCNS) for connecting a dv/dt filter
- 3 DRIVE‑CLiQ sockets
- 1 temperature sensor input for KTY84‑130, Pt1000, PTC or Pt100 (Pt1000 can be used from firmware V4.7 HF17 and higher)
- 1 connection for Safe Brake Adapter
- 1 connection for Safety Integrated
- 2 PE connections
The status of the Motor Modules is indicated via three LEDs. The scope of supply of the Motor Modules includes: - DRIVE‑CLiQ cable for connection to the Control Unit
- DRIVE‑CLiQ cable for connection to the next Motor Module
- 1 set of warning labels in 30 languages
(BG, CN, CZ, DE, DK, EE, ES, FI, FR, GB, GR, HU, IE, IS, IT, JP, KR, LT, LV, MT, NL, NO, PL, PT, RO, RU, SE, SI, SK, TR)
|
|