The Heat Exchanger Modules must be selected appropriately for the required cooling power and the required volume flow of coolant in the converter-side deionized water circuit. The values stated in the technical specifications of the Cabinet Modules for the heat loss dissipated into the coolant must be summated. The total value is then the required cooling power.

The volume flow of coolant stated in the technical data of the Cabinet Modules must also be added.

If either of the two total values exceeds the values defined in the technical specifications of the Heat Exchanger Module (cooling power and volume flow of coolant for converter-side deionized water), the next larger Heat Exchanger Module must be selected.

Line voltage 380 вЂ¦ 415 V 3 AC 50 Hz

Heat Exchanger Modules

Line voltage 440 ... 480 V 3 AC 60 Hz 1)

 

 

 

6SL3705-0RE23-2AA4

6SL3705-0RE24-8AA4

6SL3705-0RE27-2AA4

6SL3705-0RE31-1AA4

Cooling power

kW

32

48

72

120

Deionized water circuit (on the converter side)

Inlet temperature

 

 

 

 

 

  • Min.

°C

Depending on the ambient temperature and humidity of the air (see table for the dew point in section Liquid-cooled Cabinet Modules в†’ Protection against condensation)

  • Max.

 

 

 

 

 

  • Drive line-up degree of protection <IP55

°C

45

45

45

45

  • Drive line-up degree of protection IP55

°C

40

40

40

40

Intake pressure

 

 

 

 

 

  • Min.

bar

1.7

1.7

1.7

1.7

  • Max.

bar

6

6

6

6

Coolant volume flow 2)

l/min

88

132

197

267

Liquid volume

l

20.4

21.4

30.5

32.5

Intake/return connection

 

 

 

 

 

  • External diameter x wall thickness

mm

76.1 x 2

76.1 x 2

76.1 x 2

76.1 x 2

Raw water circuit (on the plant side)

Inlet temperature

 

 

 

 

 

  • Min.

°C

5 3)

5 3)

5 3)

5 3)

  • Max.

 

 

 

 

 

  • Drive line-up degree of protection <IP55

°C

38

38

38

38

  • Drive line-up degree of protection IP55

°C

33

33

33

33

Intake pressure, max.

bar

6

6

6

6

Coolant volume flow 2)

l/min

132

198

263

445

Intake/return connection

 

 

 

 

 

  • External diameter x wall thickness

mm

42 x 1.5

42 x 1.5

76.1 x 2

76.1 x 2

General data

Heat exchanger material

 

Stainless steel

Stainless steel

Stainless steel

Stainless steel

Current consumption

 

 

 

 

 

  • Operating current, total
    at 50/60 Hz 400 V

A

7.5/7.0

7.5/7.0

11.0/12.0

11.0/12.0

  • Electronics current (24 V DC)

A

1.0

1.0

1.0

1.0

Power consumption, max.

at 50/60 Hz 400 V

kW

3.5/4.7

3.5/4.7

5.5/6.4

5.5/6.4

Sound pressure level LpA

(1 m) at 50 Hz

dB

60

60

60

60

Line supply connection

L1, L2, L3

 

Terminal

Terminal

Terminal

Terminal

  • Conductor cross-section, max. (IEC)

mm2

4

4

4

4

PE/GND connection

 

Terminal

Terminal

Terminal

Terminal

  • Conductor cross-section, max. (IEC)

mm2

4

4

4

4

Degree of protection (standard version)

 

IP55

IP55

IP55

IP55

Dimensions

 

 

 

 

 

  • Width 4)

mm

600

600

600

600

  • Height

mm

2200

2200

2200

2200

  • Depth

mm

600

600

600

600

Weight, approx. 5)

(standard version)

kg

310

310

320

320



1) Heat Exchanger Modules 440 V to 480 V, 60 Hz available with option C95.

2) The value is valid for water as coolant. For other coolants, see section Cooling circuit and coolant properties.

3) 0 °C with antifreeze (see derating characteristics).

4) With option W01, the cabinet width increases to 1000 mm.

5) With option W01, the cabinet weight increases by approximately 110 kg.

 

With Heat Exchanger Modules for line voltages of 660 ... 690 V 3 AC, the voltage is adapted to the 400 V 3 AC/50 Hz or 460 V 3 AC/60 Hz supply voltage of the pump using a transformer.

Line voltage 660 вЂ¦ 690 V 3 AC 50 Hz

Heat Exchanger Modules

Line voltage 660 ... 690 V 3 AC 60 Hz1)

 

 

 

6SL3705-0RG23-2AA4

6SL3705-0RG24-8AA4

6SL3705-0RG27-2AA4

6SL3705-0RG31-1AA4

Cooling power

kW

32

48

72

120

Deionized water circuit (on the converter side)

Inlet temperature

 

 

 

 

 

  • Min.

°C

Depending on the ambient temperature and humidity of the air (see table for the dew point in section Liquid-cooled Cabinet Modules в†’ Protection against condensation)

  • Max.

 

 

 

 

 

  • Drive line-up degree of protection <IP55

°C

45

45

45

45

  • Drive line-up degree of protection IP55

°C

40

40

40

40

Intake pressure

 

 

 

 

 

  • Min.

bar

1.7

1.7

1.7

1.7

  • Max.

bar

6

6

6

6

Coolant volume flow 2)

l/min

88

132

197

267

Liquid volume

l

20.4

21.4

30.5

32.5

Intake/return connection

 

 

 

 

 

  • External diameter x wall thickness

mm

76.1 x 2

76.1 x 2

76.1 x 2

76.1 x 2

Raw water circuit (on the plant side)

Inlet temperature

 

 

 

 

 

  • Min.

°C

5 3)

5 3)

5 3)

5 3)

  • Max.

 

 

 

 

 

  • Drive line-up degree of protection <IP55

°C

38

38

38

38

  • Drive line-up degree of protection IP55

°C

33

33

33

33

Intake pressure, max.

bar

6

6

6

6

Coolant volume flow 2)

l/min

132

198

263

445

Intake/return connection

 

 

 

 

 

  • External diameter x wall thickness

mm

42 x 1.5

42 x 1.5

76.1 x 2

76.1 x 2

General data

Heat exchanger material

 

Stainless steel

Stainless steel

Stainless steel

Stainless steel

Current consumption

 

 

 

 

 

  • Operating current, total
    at 50/60 Hz 690 V

A

4.4/4.1

4.4/4.1

6.4/7.0

6.4/7.0

  • Electronics current (24 V DC)

A

1.0

1.0

1.0

1.0

Power consumption, max.

at 50/60 Hz 690 V

kW

3.5/4.7

3.5/4.7

5.5/6.4

5.5/6.4

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

60

60

60

60

Line supply connection

L1, L2, L3

 

Terminal

Terminal

Terminal

Terminal

  • Conductor cross-section, max. (IEC)

mm2

4

4

4

4

PE/GND connection

 

Terminal

Terminal

Terminal

Terminal

  • Conductor cross-section, max. (IEC)

mm2

4

4

4

4

Degree of protection (standard version)

 

IP55

IP55

IP55

IP55

Dimensions

 

 

 

 

 

  • Width 4)

mm

600

600

600

600

  • Height

mm

2200

2200

2200

2200

  • Depth

mm

600

600

600

600

Weight, approx. 5)

(standard version)

kg

350

350

360

360



1) Heat Exchanger Modules 660 V to 690 V, 60 Hz available with option C97.

2) The value is valid for water as coolant. For other coolants, see section Cooling circuit and coolant properties.

3) 0 °C with antifreeze (see derating characteristics).

4) With option W01, the cabinet width increases to 1000 mm.

5) With option W01, the cabinet weight increases by approximately 110 kg.

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Установка обезжелезивания

  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366  skenergo@mail.ru
Яндекс.Метрика