General information | | | |
Product brand name | SIPLUS |
Product designation | Controller |
Product function | | | |
| Yes |
| Yes |
| Yes |
| No |
| Yes |
Supply voltage | | | |
Operating voltage from Power Module | 24 V |
Operating voltage from external power supply, min. | 20.4 V |
Operating voltage from external power supply, max. | 28.8 V |
Input current | | | |
Current consumption, max. | 0.5 A |
Power loss | | | |
Power loss, max. | 5.5 W |
Digital inputs | | | |
Number of digital inputs | 6; Optically isolated, free reference potential (own potential group), NPN/PNP-logic selectable via wiring |
| 1; Use of 2x DI Standard |
Digital outputs | | | |
Number of digital outputs | |
| 1 |
| 2 |
Analog inputs | | | |
Number of analog inputs | 2; The differential analog inputs can be configured as supplementary digital inputs |
Type of analog input | Differential input |
Input voltage with signal "0" to "1" | 4 V |
Input voltage with signal "1" to "0" | 1.6 V |
Analog outputs | | | |
Number of analog outputs | 2 |
Interfaces | | | |
Number of PROFINET interfaces | 0 | 2 | 0 |
Number of RS 485 interfaces | 1 | 0 | 1 |
Protocols | | | |
PROFIBUS | Yes | No |
Degree and class of protection | | | |
IP degree of protection | IP20 |
Standards, approvals, certificates | | | |
Certificate of suitability | CE / TГњV |
Verification of suitability for CE marking | Low Voltage Directive 2014/35/EU |
Ambient conditions | | | |
Ambient temperature during operation | | | |
| -20 °C |
| 55 °C |
| -4 °F |
| 131 °F |
| A derating of 3 K/1 000 m has to be applied to the Control Units from an installation altitude of 1 000 m above sea level |
Ambient temperature during storage/transportation | | | |
| -40 °C |
| 70 °C |
| -40 °F |
| 158 °F |
Relative humidity | | | |
| 100 %; RH incl. condensation/frost permitted (no commissioning in bedewed state) |
Extended ambient conditions | | | |
Resistance | | | |
| Yes; The supplied plug covers must remain in place over the unused interfaces during operation! |
| Class 3B2 acc. to EN 60721-3-3, mold and fungal spores (except fauna) | Class 3B2 according to EN 60721-3-3, mold, fungus and dry rot spores (with the exception of fauna); class 3B3 on request |
| Yes; The supplied plug covers must remain in place over the unused interfaces during operation! |
| Class 3C4 acc. to EN 60721-3-3, including salt spray acc. to EN 60068-2-52 (severity level 3) | Class 3C4 according to EN 60721-3-3,(RH <75%) incl. salt spray acc. to EN 60068-2-52 (severity degree 3). |
| No |
Connection method | | | |
Type of electrical connection for signal line | |
| 0.05 mmІ |
| 1.5 mmІ |
| 30 |
| 16 |
Dimensions | | | |
Width | 73 mm |
Height | 199 mm |
Depth | 46 mm |
Weights | | | |
Weight (without packaging) | 0.49 kg |