Device type - Top-hat rail mounted device
- Plastic case 96 mm Г— 96 mm Г— 100 mm / 3.78 in. x 3.78 in. x 3.94 in. (W Г— H Г— D)
- Degree of protection: IP20
Input and output circuits - 4 inputs for alternating voltage measurements
- 3 inputs for alternating current measurements up to 10 A continuous
- 4 optional DC analog outputs freely configurable:
- Direct currents: 0 mA to 20 mA, 4 mA to 20 mA and -20 mA to 20 mA
- Direct voltages: 0 V to 10 V and -10 V to 10 V
- Individually programmable binary outputs
Signalization LEDs Automatically monitor the functions of its hardware, software, and firmware components. Communication - Ethernet: IEC 61850 or MODBUS TCP communication protocol
- Optional serial RS485 interface that enables the device to communicate via the MODBUS RTU or the IEC 60870-5-103 communication protocol.
Measurands The following measurands can be recorded or calculated from the measured quantities: - TRMS (True RMS) for alternating voltage and current
- Active, reactive and apparent power
- Active, reactive and apparent energy
- Power frequency
- Phase angle
- Power factor and active power factor
- Voltage and current unbalance
- Mean value of the 3 phase voltages: Vavg
- Mean value of the 3 phase currents: Iavg..
Time synchronization - For a common time basis when communicating with peripheral devices and time stamping of the process data.
- External time synchronization via Ethernet NTP
- External time synchronization via field bus using the MODBUS RTU or the IEC 60870-5-103 communication protocol
- Internal time synchronization via RTC (if external time synchronization is not available).
Response time for analog and binary outputs The faster response time of the analog and binary output is a very important feature of SICAM T that enables a reliable reaction of the controlling applications. The response time of the device is 120 ms at 50 Hz and 100 ms at 60 Hz.
|