General technical specifications | PM330 Power Modules |
---|
Input data | Line voltages and power ranges | 380 ... 480 V 3 AC ±10 %, 160 ... 560 kW 500 ... 690 V 3 AC ±10 %, 315 ... 630 kW | Starting current | < rated input current (refer to power-dependent data) | Input frequency | 47 ... 63 Hz | Grid requirement Short-circuit power RSC | >33 line reactor required | Output data | Output voltage | 0 V 3 AC … ≤ (line voltage × 0.97) | Output current | (refer to power-dependent data) | Output frequency | 0 ... 150 Hz | Pulse frequency | Self-adjusting up to 4 kHz | Power factor λ | 0.75 ... 0.93 | Offset factor cos φ | 0.96 | Further technical specifications | Overvoltage category to IEC 61800‑5‑1 | - Overvoltage category III: Supply circuits
- Overvoltage category II: Non-supply circuits
| Braking methods | - DC braking
- Dynamic braking with external Braking Module with braking resistor
| Type of cooling | Forced air cooling AF to EN 60146 | Protection functions | - Undervoltage
- Overvoltage
- Overcurrent/overload
- Overtemperature
- Ground fault
- Short-circuit
- Stall protection
- Motor blocking protection
- Motor overtemperature
- Inverter overtemperature/fan failure
- Parameter locking
- Detection of single-phase motor cable break
- Line phase failure
| Standards | Compliance with standards | cULus, CE, RCM, EAC, KC, SEMI F471) | CE marking | According to EMC Directive 2014/30/EU, Low Voltage Directive 2014/35/EU | RI suppression | According to EMC product standard for variable-speed drives EN 61800‑3, "second environment". Can be operated in the "first environment" if line filters are installed. |
1) SEMI F47 for frame sizes HX (500 V to 690 V) and JX available soon PM330 Power ModulesLine voltage 380 ... 480 V 3 AC | PM330 Power Modules |
---|
| 6SL3310-1PE33-0AA0 | 6SL3310-1PE33-7AA0 | 6SL3310-1PE34-6AA0 | 6SL3310-1PE35-8AA0 | 6SL3310-1PE36-6AA0 | 6SL3310-1PE37-4AA0 |
---|
Rated power 1) | | | | | | | | - Based on the base-load current IL
| | | | | | | | | kW | 160 | 200 | 250 | 315 | 355 | 400 | | hp | 200 | 250 | 300 | 400 | 450 | 500 | - Based on the base-load current IH
| | | | | | | | | kW | 132 | 160 | 200 | 250 | 250 | 315 | | hp | 150 | 200 | 200 | 300 | 300 | 350 | Output current at 50 Hz 3 AC | | | | | | | | - Rated current Irated (400 V ±10 %)
| A | 300 | 370 | 460 | 585 | 655 | 735 | - Rated current Irated (480 V ±10 %)
| A | 245 | 308 | 369 | 487 | 526 | 602 | - Base-load current IL (400 V ±10 %) 2)
| A | 290 | 360 | 450 | 570 | 640 | 720 | - Base-load current IL (480 V ±10 %) 2)
| A | 240 | 302 | 361 | 477 | 515 | 590 | - Base-load current IH (400 V ±10 %) 3)
| A | 240 | 296 | 368 | 468 | 491 | 551 | - Base-load current IH (480 V ±10 %) 3)
| A | 196 | 247 | 295 | 390 | 394 | 452 | | A | 392 | 486 | 608 | 770 | 864 | 972 | Rated pulse frequency | kHz | 2 | 2 | 2 | 2 | 2 | 2 | Input current 4) | | | | | | | | - Rated current Irated (400 V ±10 %)
| A | 317 | 375 | 469 | 597 | 668 | 750 | - Rated current Irated (480 V ±10 %)
| A | 262 | 314 | 376 | 497 | 536 | 614 | - Base-load current IL (400 V ±10 %) 2)
| A | 307 | 365 | 459 | 585 | 654 | 735 | - Base-load current IL (480 V ±10 %) 2)
| A | 257 | 308 | 368 | 486 | 525 | 602 | - Base-load current IH (400 V ±10 %) 3)
| A | 254 | 300 | 375 | 477 | 501 | 562 | - Base-load current IH (480 V ±10 %) 3)
| A | 210 | 251 | 301 | 397 | 402 | 461 | | A | 415 | 493 | 620 | 785 | 881 | 992 | Short-circuit current rating according to IEC in conjunction with the specified fuses | kA | 100 | 100 | 100 | 100 | 100 | 100 | Rated short-circuit current SCCR (Short-Circuit Current Rating) in accordance with UL508C (up to 600 V) in conjunction with the specified fuses | kA | 100 | 100 | 100 | 100 | 100 | 100 | Minimum short-circuit current 5) | | | | | | | | | A | 3500 | 4500 | 7000 | 10000 | 11000 | 13000 | | A | 9500 | 14000 | 20000 | 20000 | 30000 | 30000 | Efficiency η At rated current Irated (400 V/45 °C (113 °F)) | % | 98 | 98 | 98.1 | 98.1 | 98 | 98.1 | Power loss At rated current Irated (400 V/45 °C (113 °F)) | kW | 3.642 | 4.414 | 5.125 | 6.791 | 7.687 | 8.385 | Coolant requirements | m3/s (ft3/s) | 0.21 (7.42) | 0.21 (7.42) | 0.21 (7.42) | 0.36 (12.7) | 0.36 (12.7) | 0.36 (12.7) | Coolant | | Air | Air | Air | Air | Air | Air | Sound pressure level LpA (1 m) | dB | 74 | 74 | 74 | 74 | 74 | 74 | Power requirement 24 V DC supply | A | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | Line supply connection U1/L1, V1/L2, W1/L3 | | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 2 × 240 | 2 × 240 | 2 × 240 | 4 × 240 | 4 × 240 | 4 × 240 | Motor connection U2, V2, W2 | | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 2 × 240 | 2 × 240 | 2 × 240 | 4 × 240 | 4 × 240 | 4 × 240 | DC link connection DCP, DCN | | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 2 × 240 | 2 × 240 | 2 × 240 | 4 × 240 | 4 × 240 | 4 × 240 | PE/GND connection | | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 3 × 240 | 3 × 240 | 3 × 240 | (4+6) × 240 | (4+6) × 240 | (4+6) × 240 | Cable length, max. between Power Module and motor | | | | | | | | - When compliant with Categories C2 and C3 according to EN 61800‑3
shielded
| m (ft) | 150 (492) | 150 (492) | 150 (492) | 150 (492) | 150 (492) | 150 (492) | - When non-compliant with the limit values for RI suppression and without output reactor or dv/dt filter
unshielded
| m (ft) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | - When non-compliant with the limit values for RI suppression with output reactor or dv/dt filter
shielded/unshielded
| m (ft) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | Degree of protection | | IP20 | IP20 | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | | | mm (in) | 452 (17.8) | 452 (17.8) | 452 (17.8) | 548 (21.6) | 548 (21.6) | 548 (21.6) | | mm (in) | 1447 (57.0) | 1447 (57.0) | 1447 (57.0) | 1696 (66.8) | 1696 (66.8) | 1696 (66.8) | | mm (in) | 327.5 (12.9) | 327.5 (12.9) | 327.5 (12.9) | 393 (15.5) | 393 (15.5) | 393 (15.5) | Frame size | | GX | GX | GX | HX | HX | HX | Weight, approx. | kg (lb) | 98 (216) | 104 (229) | 109 (240) | 151 (333) | 157 (346) | 159 (351) | Minimum size of control cabinet for installation of a Power Module | | | | | | | | | mm (in) | No specifications | No specifications | No specifications | 800 (31.5) | 800 (31.5) | 800 (31.5) | | mm (in) | No specifications | No specifications | No specifications | 2000 (78.7) | 2000 (78.7) | 2000 (78.7) | | mm (in) | No specifications | No specifications | No specifications | 600 (23.6) | 600 (23.6) | 600 (23.6) |
1) Rated power of a typical 4-pole standard induction motor based on the base-load current IL or IH at 400 V 3 AC/50 Hz (kW) or 460 V 3 AC/60 Hz (hp). 2) The base-load current IL is based on the duty cycle for low overload (LO). 3) The base-load current IH is based on the duty cycle for high overload (HO). 4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate. 5) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage. Line voltage 380 ... 480 V 3 AC | PM330 Power Modules |
---|
| 6SL3310-1PE38-4AA0 | 6SL3310-1PE38-8AA0 | 6SL3310-1PE41-0AA0 |
---|
Rated power 1) | | | | | - Based on the base-load current IL
| | | | | | kW | 450 | 500 | 560 | | hp | 500 | 600 | 700 | - Based on the base-load current IH
| | | | | | kW | 355 | 400 | 450 | | hp | 450 | 500 | 500 | Output current at 50 Hz 3 AC | | | | | - Rated current Irated (400 V ±10 %)
| A | 840 | 910 | 1021 | - Rated current Irated (480 V ±10 %)
| A | 677 | 739 | 847 | - Base-load current IL (400 V ±10 %) 2)
| A | 820 | 890 | 1000 | - Base-load current IL (480 V ±10 %) 2)
| A | 663 | 724 | 830 | - Base-load current IH (400 V ±10 %) 3)
| A | 672 | 728 | 786 | - Base-load current IH (480 V ±10 %) 3)
| A | 542 | 591 | 652 | | A | 1107 | 1202 | 1350 | Rated pulse frequency | kHz | 2 | 2 | 2 | Input current 4) | | | | | - Rated current Irated (400 V ±10 %)
| A | 870 | 945 | 1061 | - Rated current Irated (480 V ±10 %)
| A | 702 | 767 | 880 | - Base-load current IL (400 V ±10 %) 2)
| A | 850 | 924 | 1038 | - Base-load current IL (480 V ±10 %) 2)
| A | 687 | 751 | 862 | - Base-load current IH (400 V ±10 %) 3)
| A | 696 | 756 | 816 | - Base-load current IH (480 V ±10 %) 3)
| A | 561 | 614 | 677 | | A | 1147 | 1248 | 1402 | Short-circuit current rating according to IEC in conjunction with the specified fuses | kA | 100 | 100 | 100 | Rated short-circuit current SCCR (Short-Circuit Current Rating) in accordance with UL 61800‑5‑1 (up to 600 V) in conjunction with the specified fuses | kA | 100 | 100 | 100 | Minimum short-circuit current 5) | | | | | | A | 10400 | 14000 | 16000 | | A | 40000 | 40000 | 52000 | | A | 8600 | 17000 | 18000 | Efficiency η At rated current Irated (400 V/45 °C (113 °F)) | % | 98 | 98 | 98 | Power loss At rated current Irated (400 V/45 °C (113 °F)) | kW | 10.418 | 10.885 | 12.495 | Coolant requirements | m3/s (ft3/s) | 0.45 (15.9) | 0.45 (15.9) | 0.45 (15.9) | Coolant | | Air | Air | Air | Sound pressure level LpA (1 m) | dB | 74 | 74 | 74 | Power requirement 24 V DC supply | A | 0.5 | 0.5 | 0.5 | Line supply connection U1/L1, V1/L2, W1/L3 | | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 6 × 240 | 6 × 240 | 6 × 240 | Motor connection U2, V2, W2 | | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 4 × 240 | 8 × 240 | 8 × 240 | DC link connection DCP, DCN | | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 4 × 240 | 4 × 240 | 4 × 240 | PE/GND connection | | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 6 × 240 | 6 × 240 | 6 × 240 | Cable length, max. between Power Module and motor | | | | | - When compliant with Categories C2 and C3 according to EN 61800‑3
shielded
| m (ft) | 150 (492) | 150 (492) | 150 (492) | - When non-compliant with the limit values for RI suppression and without output reactor or dv/dt filter
unshielded
| m (ft) | 200 (656) | 200 (656) | 200 (656) | - When non-compliant with the limit values for RI suppression with output reactor or dv/dt filter
shielded/unshielded
| m (ft) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | Degree of protection | | IP20 | IP20 | IP20 | Dimensions | | | | | | mm (in) | 801 (31.5) | 801 (31.5) | 801 (31.5) | | mm (in) | 1621 (63.8) | 1621 (63.8) | 1621 (63.8) | | mm (in) | 393 (15.5) | 393 (15.5) | 393 (15.5) | Frame size | | JX | JX | JX | Weight, approx. | kg (lb) | 235 (518) | 250 (551) | 250 (551) | Minimum size of control cabinet for installation of a Power Module | | | | | | mm (in) | No specifications | No specifications | No specifications | | mm (in) | No specifications | No specifications | No specifications | | mm (in) | No specifications | No specifications | No specifications |
1) Rated power of a typical 4-pole standard induction motor based on the base-load current IL or IH at 400 V 3 AC/50 Hz (kW) or 460 V 3 AC/60 Hz (hp). 2) The base-load current IL is based on the duty cycle for low overload (LO). 3) The base-load current IH is based on the duty cycle for high overload (HO). 4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate. 5) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage. Line voltage 500 ... 690 V 3 AC | PM330 Power Modules |
---|
| 6SL3310-1PG33-7AA0 | 6SL3310-1PG34-0AA0 | 6SL3310-1PG34-5AA0 | 6SL3310-1PG35-2AA0 |
---|
Rated power 1) | | | | | | - Based on the base-load current IL
| | | | | | | kW | 315 | 355 | 400 | 450 | | hp | 350 | 400 | 450 | 450 | - Based on the base-load current IH
| | | | | | | kW | 250 | 315 | 355 | 400 | | hp | 250 | 300 | 350 | 450 | Output current at 50 Hz 3 AC | | | | | | - Rated current Irated (500 V ±10 %)
| A | 368 | 400 | 453 | 516 | - Rated current Irated (600 V ±10 %)
| A | 353 | 396 | 441 | 497 | - Rated current Irated (690 V ±10 %)
| A | 340 | 393 | 430 | 480 | - Base-load current IL (500 V ±10 %) 2)
| A | 361 | 392 | 443 | 505 | - Base-load current IL (690 V ±10 %) 2)
| A | 330 | 385 | 420 | 470 | - Base-load current IH (500 V ±10 %) 3)
| A | 295 | 320 | 367 | 423 | - Base-load current IH (690 V ±10 %) 3)
| A | 272 | 314 | 348 | 394 | | A | 487 | 529 | 598 | 682 | Rated pulse frequency | kHz | 2 | 2 | 2 | 2 | Input current 4) | | | | | | - Rated current Irated (500 V ±10 %)
| A | 383 | 416 | 471 | 537 | - Rated current Irated (600 V ±10 %)
| A | 367 | 412 | 459 | 517 | - Rated current Irated (690 V ±10 %)
| A | 354 | 409 | 447 | 499 | - Base-load current IL (500 V ±10 %) 2)
| A | 375 | 408 | 461 | 526 | - Base-load current IL (690 V ±10 %) 2)
| A | 343 | 401 | 437 | 489 | - Base-load current IH (500 V ±10 %) 3)
| A | 307 | 333 | 381 | 440 | - Base-load current IH (690 V ±10 %) 3)
| A | 283 | 327 | 362 | 410 | | A | 507 | 550 | 623 | 710 | Short-circuit current rating according to IEC in conjunction with the specified fuses | kA | 100 | 100 | 100 | 100 | Rated short-circuit current SCCR (Short-Circuit Current Rating) in accordance with UL 61800‑5‑1 (up to 600 V) in conjunction with the specified fuses | kA | 100 | 100 | 100 | 100 | Minimum short-circuit current 5) | | | | | | | A | 3500 | 4500 | 7000 | 8500 | Efficiency η at rated current Irated (690 V/45 °C (113 °F)) | % | 98.2 | 98.2 | 98.2 | 98.2 | Power loss at rated current Irated (690 V/45 °C (113 °F)) | kW | 5.402 | 6.191 | 6.884 | 7.716 | Coolant requirements | m3/s (ft3/s) | 0.362 (12.8) | 0.362 (12.8) | 0.362 (12.8) | 0.362 (12.8) | Coolant | | Air | Air | Air | Air | Sound pressure level LpA (1 m) | dB | 74 | 74 | 74 | 74 | Power requirement 24 V DC supply | A | 0.5 | 0.5 | 0.5 | 0.5 | Line supply connection U1/L1, V1/L2, W1/L3 | | M12 screw | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 4 × 240 | 4 × 240 | 4 × 240 | 4 × 240 | Motor connection U2, V2, W2 | | M12 screw | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 4 × 240 | 4 × 240 | 4 × 240 | 4 × 240 | DC link connection DCP, DCN | | M12 screw | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 4 × 240 | 4 × 240 | 4 × 240 | 4 × 240 | PE/GND connection | | M12 screw | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | (4+6) × 240 | (4+6) × 240 | (4+6) × 240 | (4+6) × 240 | Cable length, max. between Power Module and motor | | | | | | - When compliant with Categories C2 and C3 according to EN 61800‑3
shielded
| m (ft) | 150 (492) | 150 (492) | 150 (492) | 150 (492) | - When non-compliant with the limit values for RI suppression and without output reactor or dv/dt filter
unshielded
| m (ft) | 200 (656) | 200 (656) | 200 (656) | 200 (656) | - When non-compliant with the limit values for RI suppression with output reactor or dv/dt filter
shielded/unshielded
| m (ft) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | Degree of protection | | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | mm (in) | 548 (21.6) | 548 (21.6) | 548 (21.6) | 548 (21.6) | | mm (in) | 1695 (66.7) | 1695 (66.7) | 1695 (66.7) | 1695 (66.7) | | mm (in) | 393 (15.5) | 393 (15.5) | 393 (15.5) | 393 (15.5) | Frame size | | HX | HX | HX | HX | Weight, approx. | kg (lb) | 158 (348) | 158 (348) | 162 (357) | 162 (357) | Minimum size of control cabinet for installation of a Power Module | | | | | | | mm (in) | 800 (31.5) | 800 (31.5) | 800 (31.5) | 800 (31.5) | | mm (in) | 2000 (78.7) | 2000 (78.7) | 2000 (78.7) | 2000 (78.7) | | mm (in) | 600 (23.6) | 600 (23.6) | 600 (23.6) | 600 (23.6) |
1) Rated power of a typical 4-pole standard induction motor based on the base-load current IL or IH at 690 V 3 AC/50 Hz (kW) or 575 V 3 AC/60 Hz (hp). 2) The base-load current IL is based on the duty cycle for low overload (LO). 3) The base-load current IH is based on the duty cycle for high overload (HO). 4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate. 5) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage. Line voltage 500 ... 690 V 3 AC | PM330 Power Modules |
---|
| 6SL3310-1PG35-8AA0 | 6SL3310-1PG36-5AA0 | 6SL3310-1PG37-2AA0 |
---|
Rated power 1) | | | | | - Based on the base-load current IL
| | | | | | kW | 500 | 560 | 630 | | hp | 500 | 600 | 700 | - Based on the base-load current IH
| | | | | | kW | 450 | 500 | 560 | | hp | 450 | 500 | 500 | Output current at 50 Hz 3 AC | | | | | - Rated current Irated (500 V ±10 %)
| A | 581 | 654 | 725 | - Rated current Irated (600 V ±10 %)
| A | 557 | 623 | 693 | - Rated current Irated (690 V ±10 %)
| A | 535 | 595 | 665 | - Base-load current IL (500 V ±10 %) 2)
| A | 569 | 640 | 710 | - Base-load current IL (690 V ±10 %) 2)
| A | 520 | 580 | 650 | - Base-load current IH (500 V ±10 %) 3)
| A | 482 | 523 | 580 | - Base-load current IH (690 V ±10 %) 3)
| A | 444 | 476 | 532 | | A | 768 | 864 | 959 | Rated pulse frequency | kHz | 2 | 2 | 2 | Input current 4) | | | | | - Rated current Irated (500 V ±10 %)
| A | 596 | 679 | 753 | - Rated current Irated (600 V ±10 %)
| A | 578 | 647 | 720 | - Rated current Irated (690 V ±10 %)
| A | 555 | 618 | 690 | - Base-load current IL (500 V ±10 %) 2)
| A | 591 | 665 | 737 | - Base-load current IL (690 V ±10 %) 2)
| A | 540 | 602 | 675 | - Base-load current IH (500 V ±10 %) 3)
| A | 501 | 543 | 602 | - Base-load current IH (690 V ±10 %) 3)
| A | 461 | 494 | 552 | | A | 798 | 897 | 995 | Short-circuit current rating according to IEC in conjunction with the specified fuses | kA | 100 | 100 | 100 | Rated short-circuit current SCCR (Short-Circuit Current Rating) in accordance with UL 61800‑5‑1 (up to 600 V) in conjunction with the specified fuses | kA | 100 | 100 | 100 | Minimum short-circuit current 5) | | | | | | A | 10000 | 11000 | 13000 | Efficiency η at rated current Irated (690 V/45 °C (113 °F)) | % | 98.3 | 98.3 | 98.3 | Power loss at rated current Irated (690 V/45 °C (113 °F)) | kW | 8.134 | 8.828 | 9.937 | Coolant requirements | m3/s (ft3/s) | 0.45 (15.9) | 0.45 (15.9) | 0.45 (15.9) | Coolant | | Air | Air | Air | Sound pressure level LpA (1 m (3.28 ft)) | dB | 74 | 74 | 74 | Power requirement 24 V DC supply | A | 0.5 | 0.5 | 0.5 | Line supply connection U1/L1, V1/L2, W1/L3 | | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 6 × 240 | 6 × 240 | 6 × 240 | Motor connection U2, V2, W2 | | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 4 × 240 | 4 × 240 | 4 × 240 | DC link connection DCP, DCN | | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 4 × 240 | 4 × 240 | 4 × 240 | PE/GND connection | | M12 screw | M12 screw | M12 screw | - Conductor cross section, max. (IEC)
| mm2 | 6 × 240 | 6 × 240 | 6 × 240 | Cable length, max. between Power Module and motor | | | | | - When compliant with Categories C2 and C3 according to EN 61800‑3
shielded
| m (ft) | 150 (492) | 150 (492) | 150 (492) | - When non-compliant with the limit values for RI suppression and without output reactor or dv/dt filter
unshielded
| m (ft) | 200 (656) | 200 (656) | 200 (656) | - When non-compliant with the limit values for RI suppression with output reactor or dv/dt filter
shielded/unshielded
| m (ft) | 300/450 (984/1476) | 300/450 (984/1476) | 300/450 (984/1476) | Degree of protection | | IP20 | IP20 | IP20 | Dimensions | | | | | | mm (in) | 801 (31.5) | 801 (31.5) | 801 (31.5) | | mm (in) | 1621 (63.8) | 1621 (63.8) | 1621 (63.8) | | mm (in) | 393 (15.5) | 393 (15.5) | 393 (15.5) | Frame size | | JX | JX | JX | Weight, approx. | kg (lb) | 236 (520) | 236 (520) | 246 (542) | Minimum size of control cabinet for installation of a Power Module | | | | | | mm (in) | No specifications | No specifications | No specifications | | mm (in) | No specifications | No specifications | No specifications | | mm (in) | No specifications | No specifications | No specifications |
1) Rated power of a typical 4-pole standard induction motor based on the base-load current IL or IH at 690 V 3 AC/50 Hz (kW) or 575 V 3 AC/60 Hz (hp). 2) The base-load current IL is based on the duty cycle for low overload (LO). 3) The base-load current IH is based on the duty cycle for high overload (HO). 4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate. 5) 10 ms value from current-time characteristic for reliable tripping of installed protection devices. If the minimum short-circuit current is not reached, the tripping time of the fuses is increased, which can lead to damage.
|
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ
|