Electrical specifications |
Operating voltage | 24 V DC via the Power Module or by connecting to an external 20.4 ... 28.8 V DC power supply |
Current consumption, max. | 0.5 A |
Protective insulation | PELV according to EN 50178 Protective separation from the line supply using double/reinforced insulation |
Power loss, max. | 5 W |
Interfaces |
Digital inputs – Standard | 6 isolated inputs, optically isolated; free reference potential (own potential group) NPN/PNP logic can be selected using the wiring |
| 11 V |
| 5 V |
| 5.5 mA |
Digital outputs | 3 relays |
- 2 relay changeover contacts
| 250 V AC, 2 A (inductive load) 30 V DC, 5 A (ohmic load) The following applies to UL-compliant installations: A maximum of 3 A, 30 V DC or 2 A, 250 V AC may be connected via terminals 18 / 20 (DO0 NC) and 23 / 25 (DO2 NC). |
| 30 V DC, 0.5 A (ohmic load) |
Analog inputs | Analog inputs are protected against inputs in a voltage range of ± 30 V and have a common-mode voltage in the ± 15 V range |
| Switchable with DIP switch between voltage and current: -10 ... +10 V, 0/4 ... 20 mA, 12-bit resolution These differential inputs can be configured as additional digital inputs. Switching thresholds: 0 → 1: Rated voltage 4 V 1 → 0: Rated voltage 1.6 V |
| Switchable with DIP switch between 0/4 ... 20 mA current and temperature sensors, type Pt1000/LG‑Ni1000/DIN‑Ni1000, 12-bit resolution |
| Temperature sensors, type Pt1000/LG‑Ni1000/DIN‑Ni1000, 12‑bit resolution |
Analog outputs | The analog outputs have short-circuit protection |
| Switchable between voltage and current using parameter setting: 0 ... 10 V, 0/4 ... 20 mA Voltage mode: 10 V, min. burden 10 kΩ Current mode: 20 mA, max. burden 500 Ω |
PTC/KTY interface | 1 motor temperature sensor input, connectable sensors PTC, Pt1000, KTY and bimetal, accuracy ±5 °C |
Bus interface |
Fieldbus protocols | - USS
- Modbus RTU
- BACnet MS/TP
- FLN P1 (switchable using software)
| | - ODVA AC drive
- SINAMICS profile
|
Profile | – | | |
Hardware | Plug-in terminal, insulated, USS: max. 187.5 kBaud Modbus RTU: 19.2 kBaud, Bus terminating resistor that can be switched in | 9-pin SUB-D socket, insulated, max. 12 Mbit/s Slave address can be set using DIP switches | 2 × RJ45, PROFIdrive profile V4.1, device name can be stored on the device Max. 100 Mbit/s (full duplex) |