Rated input voltage | Typ. motor rated power for cabinet systems |
|---|
400 V | 15 ... 630 kW | 500 V | 15 ... 800 kW | 690 V | 45 ... 5600 kW | 950 V | 630 ... 6000 kW |
Brief overview |
|---|
Line supply voltage +10 %, -15 % | 3 ~ AC 400 ... 1140 V | Line supply cos phi (1) | Depends on the motor | Line supply frequency | 50 Hz, optional 60 Hz | Maximum output frequency | 60 Hz, higher on request | Output voltage (basic fundamental) | 3 × 0 ... line supply voltage | Motor cable length (shielded or non‑shielded) | 500 m, longer on request | Degree of protection | IP21, higher degrees of protection optionally available |
Features Explosion protection - ATEX-certified for motors located in hazardous zones with Accessory kit S, also with very long motor cable length
Emergency Off - The Emergency Off function prevents unexpected starting in compliance with EN 60204‑1, implemented according to EN 954‑1, Category 3, respectively SIL2 with Accessory kit S
Power unit - 12- and 24-pulse input optional possible. For this reason gi line supply(basic fundamental) of 99.9 % is possible
- This corresponds to the EMC Directives (EN 61800‑3 environment 2) as a result of the line filter integrated as standard
- Low harmonics as a result of the integrated line reactor
- Long motor cable lengths possible inherent to the system
- Insulation monitoring for IT line supplies for 500/690 V drive units as well as ground fault monitoring for TN and TT line supplies integrated in the 400 V drive units
- Wide supply voltage range
- Normal fuses can be used for protection (gL characteristic)
Control section - High level of personnel and plant protection through protective separation between the analog and digital control peripheral and the power unit according to VDE 0106 / EN 50178
Operator control and setting - Transparent operator control and setting using a menu-prompted 4-line plain text display with membrane keypad at the drive inverter
- or up to 1000 m away in the main control room via RS485
- Extensive functions using the Windows-based PC operator control program
Communication - Communication via conventional terminal strip with freely-programmable digital and analog inputs / outputs, with
- parameterizable limit value signals
- parameterizable timers
- parameterizable damping elements
- parameterizable drive inverter behavior when inputs/outputs respond
- Communication and parameterization via
- PC using IMS (Inverter Management Software) via RS232/RS485
- external operator panel via RS485
- bus systems such as Profibus DP or Modbus RTU
Drive behavior for LOHER DYNAVERT I - Two closed-loop control types for induction motors:
- Speed control
- Torque control
- Full 4-quadrant operation with regenerative braking as standard
The following generally apply - Automatic slip compensation
- Stall protection using current limiting control
- Flying restart circuit to connect to a rotating motor
|
|