The table below lists recommended ratings for input-side switching and fuse protection elements according to IEC standards. Further information about the main contactors, switch disconnectors, fuses and circuit breakers specified in the table can be found in Catalog LV 10. Type rating (for 400V, 500V or 690V) | Rated input current | Assignment to Power Module | Line contactor | Fixed-mounted circuit breaker | Switch disconnector for cable protection fuses incl. semiconductor protection of type 3NE1 |
|---|
kW | A | Type 6SL3310‑... | Type | Type | Type |
|---|
380 ... 480 V 3 AC | 110 | 229 | 1GE32-1AA3 | 3RT1456‑….. | – | 3KL5530‑….. | 132 | 284 | 1GE32-6AA3 | 3RT1466‑….. | – | 3KL5730‑….. | 160 | 338 | 1GE33-1AA3 | 3RT1466‑….. | – | 3KL5730‑….. | 200 | 395 | 1GE33-8AA3 | 3RT1476‑….. | – | 3KL6130‑….. | 250 | 509 | 1GE35-0AA3 | 3RT1476‑….. | – | 3KL6130‑….. | 315 | 629 | 1GE36-1AA3 | 3RT1476‑….. | – | 3KL6230‑….. | 400 | 775 | 1GE37-5AA3 | 3RT1466‑….. (3 units) | – | 3KL6230‑….. | 450 | 873 | 1GE38-4AA3 | – | 3WL1110‑… *) | – | 560 | 1024 | 1GE41-0AA3 | – | 3WL1112‑… *) | – | 500 ... 600 V 3 AC | 110 | 191 | 1GF31-8AA3 | 3RT1456‑….. | – | 3KL5530‑….. | 132 | 242 | 1GF32-2AA3 | 3RT1456‑….. | – | 3KL5530‑….. | 160 | 270 | 1GF32-6AA3 | 3RT1466‑….. | – | 3KL5730‑….. | 200 | 343 | 1GF33-3AA3 | 3RT1466‑….. | – | 3KL5730‑….. | 250 | 426 | 1GF34-1AA3 | 3RT1476‑….. | – | 3KL6130‑….. | 315 | 483 | 1GF34-7AA3 | 3RT1476‑….. | – | 3KL6130‑….. | 400 | 598 | 1GF35-8AA3 | 3RT1476‑….. | – | 3KL6230‑….. | 500 | 764 | 1GF37-4AA3 | 3RT1466‑….. (3 units) | – | 3KL6230‑….. | 560 | 842 | 1GF38-1AA3 | – | 3WL1210‑… *) | – | 660 ... 690 V 3 AC | 75 | 93 | 1GH28-5AA3 | 3RT1446‑….. | – | 3KL5230‑….. | 90 | 109 | 1GH31-0AA3 | 3RT1446‑….. | – | 3KL5230‑….. | 110 | 131 | 1GH31-2AA3 | 3RT1446‑….. | – | 3KL5530‑….. | 132 | 164 | 1GH31-5AA3 | 3RT1456‑….. | – | 3KL5530‑….. | 160 | 191 | 1GH31-8AA3 | 3RT1456‑….. | – | 3KL5530‑….. | 200 | 224 | 1GH32-2AA3 | 3RT1456‑….. | – | 3KL5530‑….. | 250 | 270 | 1GH32-6AA3 | 3RT1466‑….. | – | 3KL5730‑….. | 315 | 343 | 1GH33-3AA3 | 3RT1466‑….. | – | 3KL5730‑….. | 400 | 426 | 1GH34-1AA3 | 3RT1476‑….. | – | 3KL6130‑….. | 450 | 483 | 1GH34-7AA3 | 3RT1476‑….. | – | 3KL6130‑….. | 560 | 598 | 1GH35-8AA3 | 3RT1476‑…. | – | 3KL6230‑….. | 710 | 764 | 1GH37-4AA3 | 3RT1466‑….. (3 units) | – | 3KL6230‑….. | 800 | 842 | 1GH38-1AA3 | – | 3WL1210‑… *) | – |
*) The circuit breakers must always be switched ON and OFF by the sequence control. An interlocking set 3WL9111-0BA21-0AA0 as described in Catalog LV 10 should be provided for the circuit breakers in order to exclude the risk of unintentional manual operation. Manual operation bypasses the pre-charging circuit and can therefore destroy the Power Module. Type rating (for 400V, 500V or 690V) | Rated input current | Assignment to Power Module | Cable protection fuse | Cable protection fuse incl. Semiconductor protection |
|---|
| | | | Rated current | | Rated current |
|---|
kW | A | Type 6SL3310-... | Type | A | Type | A |
|---|
380 ... 480 V 3 AC | 110 | 229 | 1GE32-1AA3 | 3NA3144 | 250 | 3NE1230-2 | 315 | 132 | 284 | 1GE32-6AA3 | 3NA3250 | 300 | 3NE1331-2 | 350 | 160 | 338 | 1GE33-1AA3 | 3NA3254 | 355 | 3NE1334-2 | 500 | 200 | 395 | 1GE33-8AA3 | 3NA3260 | 400 | 3NE1334-2 | 500 | 250 | 509 | 1GE35-0AA3 | 3NA3372 | 630 | 3NE1436-2 | 630 | 315 | 629 | 1GE36-1AA3 | 3NA3475 | 800 | 3NE1438‑2 | 800 | 400 | 775 | 1GE37-5AA3 | 3NA3475 | 800 | 3NE1448‑2 | 850 | 450 | 873 | 1GE38-4AA3 | 3NA3365 | 2 × 500 | 3NE1436‑2 | 2 × 630 | 560 | 1024 | 1GE41-0AA3 | 3NA3472 | 2 × 630 | 3NE1437‑2 | 2 × 710 | 500 ... 600 V 3 AC | 110 | 191 | 1GF31-8AA3 | 3NA3244‑6 | 250 | 3NE1227-2 | 250 | 132 | 242 | 1GF32-2AA3 | 3NA3252‑6 | 315 | 3NE1230-2 | 315 | 160 | 270 | 1GF32-6AA3 | 3NA3354‑6 | 355 | 3NE1331-2 | 350 | 200 | 343 | 1GF33-3AA3 | 3NA3365‑6 | 500 | 3NE1334-2 | 500 | 250 | 426 | 1GF34-1AA3 | 3NA3365‑6 | 500 | 3NE1334-2 | 500 | 315 | 483 | 1GF34-7AA3 | 3NA3252‑6 | 2 × 315 | 3NE1435‑2 | 560 | 400 | 598 | 1GF35-8AA3 | 3NA3354‑6 | 2 × 355 | 3NE1447‑2 | 670 | 500 | 764 | 1GF37-4AA3 | 3NA3365‑6 | 2 × 500 | 3NE1448‑2 | 850 | 560 | 842 | 1GF38-1AA3 | 3NA3365‑6 | 2 × 500 | 3NE1334‑2 | 2 × 500 | 660 ... 690 V 3 AC | 75 | 93 | 1GH28-5AA3 | 3NA3132-6 | 125 | 3NE1022-2 | 125 | 90 | 109 | 1GH31-0AA3 | 3NA3132-6 | 125 | 3NE1022-2 | 125 | 110 | 131 | 1GH31-2AA3 | 3NA3136-6 | 160 | 3NE1224-2 | 160 | 132 | 164 | 1GH31-5AA3 | 3NA3240-6 | 200 | 3NE1225-2 | 200 | 160 | 191 | 1GH31-8AA3 | 3NA3244-6 | 250 | 3NE1227-2 | 250 | 200 | 224 | 1GH32-2AA3 | 3NA3252-6 | 315 | 3NE1230-2 | 315 | 250 | 270 | 1GH32-6AA3 | 3NA3354-6 | 355 | 3NE1331-2 | 350 | 315 | 343 | 1GH33-3AA3 | 3NA3365‑6 | 500 | 3NE1334‑2 | 500 | 400 | 426 | 1GH34-1AA3 | 3NA3365‑6 | 500 | 3NE1334‑2 | 500 | 450 | 483 | 1GH34-7AA3 | 3NA3252‑6 | 2 × 315 | 3NE1435‑2 | 560 | 560 | 598 | 1GH35-8AA3 | 3NA3354‑6 | 2 × 355 | 3NE1447‑2 | 670 | 710 | 764 | 1GH37-4AA3 | 3NA3365‑6 | 2 × 500 | 3NE1448‑2 | 850 | 800 | 842 | 1GH38-1AA3 | 3NA3365‑6 | 2 × 500 | 3NE1334‑2 | 2 × 500 |
|