Mains voltage | 380 V to 480 V 3 AC |
Current (at 40 °C/50 °C) | For frame size A | 4.5 A/4.1 A |
For frame size B | 11.2 A/10.2 A |
For frame size C | 32.6 A/29.7 A |
Limiting of motor overvoltage | ≤ 1078 V |
dV/dt limiting | ≤ 500 V/μs |
Pulse frequency | 4 kHz |
Max. motor frequency | 150 Hz |
Max. permissible motor cable lengths | Shielded | 200 m |
Unshielded | 300 m |
Insulation strength | Overvoltage categorie III to VDE 0110 |
Electromagnetic compatibility | Up to 200 m motor cable length with emissions to Class A according to EN 55 011 in conjunction with filtered inverters and unshielded cables |
Conformity | CE according to the low-voltage directive 73/23/EEC |
Approvals | UL available soon |
Strain resistance | EN 60 068-2-31 |
Humidity | 95 % humidity, non-condensing |
Degree of protection | IP20 (to EN 60 529) |
Insulation class | H (180 °C) |
Permissible temperature | Operation | -10 °C to +40 °C (+14 °F to +104 °F) | 100 % Pn |
to +50 °C (to +122 °F) | 80 % Pn |
Storage | -25 °C to +70 °C (-13 °F to +158 °F) |
Permissible installation altitude | Up to 2000 m | 100 % Pn |
2000 to 4000 m | 62.5 % Pn |
Mounting position | Footprint or suspended |
Free space | Top | 100 mm |
Bottom | 100 mm |
Side | 100 mm |
Connection system | Input, litz wire or terminal | 1U1, 1V1, 1W1 |
Output, terminals | 1U2, 1V2, 1W2 |
Torque for power conductor connections | 1.5 Nm to 1.8 Nm |
Weight, approx. | For frame size A | 7 kg |
For frame size B | 11 kg |
For frame size C | 29 kg |