4NC51 window-type current transformers, used as pin-wound transformers, Classes 1 and 3, from 5 A to 75 APin-winding increases the primary current of the current transformer. Consequently, window-type current transformers can also be used for low primary currents. | | Basic type | | 4NC51 12 | 4NC51 13 | 4NC51 15 | 4NC51 17 | 4NC51 21 | 4NC51 22 | 4NC51 23 |
|---|
| | Rated primary current | A | 50 | 60 | 75 | 100 | 150 | 200 | 250 | | | Service | VA | 2.5 | 2.5 | 2.5 | 2.5 | 2.5 | 5 | 5 | | | Primary current to be measured | | Number of required pin windings | | | | A | Class 3 | Class 1 |  4NC51 used as pin-wound transformer | | 5 | 10 | – | – | – | – | – | – | | | 10 | 5 | 6 | – | 10 | – | – | – | | | 15 | – | 4 | 5 | – | 10 | – | – | | | 20 | – | 3 | – | 5 | – | 10 | – | | | 25 | 2 | – | 3 | 4 | 6 | 8 | 10 | | | 30 | – | 2 | – | – | 5 | – | – | | | | 40 | – | – | – | – | – | 5 | – | | | | 50 | – | – | – | 2 | 3 | 4 | 5 | | | | 75 | – | – | – | – | 2 | – | – |
|
|