6RX1800-4DK02Цена на сайте указана розничная в ЕВРО без учета НДС. Для уточнения цены и размера предоставляемой скидки - звоните или присылайте заявки | Заказной номер | Вес | PG | Описание продукта | Цена | | 6RX1800-4DK02 | 10.86 | 3D3 | COMMUTATING CHOKE FOR CONVERTER; PHASES:3 F(HZ):50/60; ILN=ITHMAX(A):51 UN(V):400(50HZ)/480(60HZ) UK(%):4; LN(MH):0.579 TA/ISOKL:40 DEGREES/B; IP00 TERMINALS:SCREW TERMINAL EN 61558-2-20 | По запросу |
Commutating reactors A converter must always be connected to the line supply through a commutation inductance. This must have at least 4 % uK! The commutation inductance can be in the form of a converter transformer or, for the appropriate line supply, in the form of a commutating reactor. A line supply can be considered to be "stiff" if the power ratio Ps/Sk ≤ 0.01. Even for stiff line supplies, the commutation inductance must have a uK of at least 4 %! For high-rating converters, the line reactance, i.e. the finite fault level (short-circuit power) of the line supply must be taken into account; this also results in higher uK values. Recommendation for the ratio of the line supply fault level (short-circuit power) to the apparent drive power > 33:1. The commutating reactors are dimensioned according to the rated motor current in the armature or field circuit. Operation with line frequencies of 50 Hz and 60 Hz The rated currents ILn of the reactors, specified in the table, apply for operation with a line frequency f = 50 Hz. It is permissible to operate the reactors with a line frequency f = 60 Hz. In this case, the next-higher voltage level must be selected (e.g. 480 V instead of 400 V). At the same time, the voltage drop ΔV increases by 8 %.  Arrangement of reactors and radio interference suppression filters (1) The commutating reactor in the field circuit is dimensioned for the rated motor field current. (2) The commutating reactor in the armature circuit is dimensioned for the rated motor armature current. The line current is 0.82 times the DC current. (3) The radio interference suppression filter for the armature circuit is dimensioned for the rated motor armature current. The line current is 0.82 times the DC current. (4) The radio interference suppression filter for the field circuit is dimensioned for the rated motor field current. (5) The electronics power supply itself does not require a radio interference suppression filter. Current consumption 1 A at 400 V, 2 A at 230 V. (6) If the power supply voltages for the armature circuit, field circuit and electronics power supply are the same, then the voltage for the field and electronics power supply can also be taken after the radio interference suppression filter for the armature circuit.  1)  1) All commutating reactors with rated voltages VN ≤ 600 V to UL Note: The commutating reactors are dimensioned according to the rated motor current in the armature and field circuits. When the unit is connected to a single phase, single-phase commutating reactors must also be used in the armature circuit. These are available on request. The tables below list the commutating reactors which are available as standard. Additional information can be found in the Operating Instructions "SINAMICS DCM Commutation reactors" (see http://support.automation.siemens.com/WW/view/en/85062393). General technical specifications |  | Degree of protection | IP00 | Protection class | Class 1 2) | Cooling | AN, self-ventilated | Inductance tolerance | ± 10 % | Environmental classes according to DIN IEC 60721-3, Parts 1 to 3 | - Climatic:
- Storage: 1K3
- Transport: 2K2
- Operation: 3K3
- Mechanical: 3M3
| Ambient temperature during operation |  | | 0 to +45 °C, above with derating | | 0 to +40 °C, above with derating | Ambient temperature for storage and transport | -40 to +70 °C | Installation altitude (at rated current) | ≤ 1000 m above sea level, above with derating | Operation at 50 Hz and 60 Hz with rated current is permissible |  |
2) Note about protection class 1: Despite protective conductor connection, no 'touchable conductive parts' with regard to the standard (e.g. EN 61800-5-1) are defined. In this case, the protective conductor ensures that no dangerous voltages/currents can act at the mounting surfaces. The complete reactor must be considered as being an active component. Three-phase commutating reactors, uK = 4В % |
|---|
AC rated current | Inductance | Copper losses | Total losses | Short-circuit current rating (SCCR) | Weight | Rated insulation voltage | Article No. |
|---|
A | mH | W | W | kA | kg | V | В |
|---|
Rated voltage 400В V | 13 | 2.315 | 22.8 | 33.1 | 2.0 (20 ms) | 2.9 | 600 | 6RX1800-4DK00 | 25 | 1.158 | 30.8 | 53.2 | 5.0 (20 ms) | 4.4 | 600 | 6RX1800-4DK01 | 51 | 0.579 | 43.5 | 73.2 | 6.5 (100 ms) | 10.9 | 600 | 6RX1800-4DK02 | 76 | 0.386 | 64.4 | 118.5 | 9.0 (100 ms) | 13.8 | 600 | 6RX1800-4DK03 | 106 | 0.278 | 51.3 | 119.3 | 15 (100 ms) | 23.9 | 600 | 6RX1800-4DK04 | 174 | 0.169 | 164.8 | 206.4 | 15 (100 ms) | 24.0 | 600 | 6RX1800-4DK05 | 232 | 0.127 | 197.4 | 256.2 | 20 (100 ms) | 26.8 | 600 | 6RX1800-4DK06 | 332 | 0.089 | 190.7 | 251.1 | 24 (200 ms) | 45.8 | 600 | 6RX1800-4DK07 | 374 | 0.079 | 186.7 | 251.7 | 24 (200 ms) | 56.8 | 600 | 6RX1800-4DK08 | 498 | 0.059 | 277.0 | 357.4 | 35 (200 ms) | 60.0 | 600 | 6RX1800-4DK10 | 706 | 0.042 | 329.4 | 424.8 | 55 (200 ms) | 81.6 | 1000 | 6RX1800-4DK11 | 996 | 0.030 | 390.3 | 562.8 | 75 (200 ms) | 100.1 | 1000 | 6RX1800-4DK12 | 1328 | 0.022 | 339.3 | 554.5 | 75 (200 ms) | 138.8 | 1000 | 6RX1800-4DK13 | 1660 | 0.018 | 369.3 | 591.9 | 75 (200 ms) | 210.7 | 1000 | 6RX1800-4DK14 | 2490 | 0.012 | 587.3 | 1038.3 | 75 (200 ms) | 205.6 | 1000 | 6RX1800-4DK15 |
Note: Commutating reactors with uK = 2В % are available on request. A limited tolerance range is also possible for parallel connections. Three-phase commutating reactors, uK = 4В % |
|---|
AC rated current | Inductance | Copper losses | Total losses | Short-circuit current rating (SCCR) | Weight | Rated insulation voltage | Article No. |
|---|
A | mH | W | W | kA | kg | V | В |
|---|
Rated voltage 480В V | В | 13 | 2.779 | 27.4 | 39.2 | 2.0 (20 ms) | 2.9 | 600 | 6RX1800-4FK00 | 25 | 1.389 | 34.8 | 57.8 | 5.0 (20 ms) | 6.0 | 600 | 6RX1800-4FK01 | 51 | 0.695 | 42.3 | 77.2 | 6.5 (100 ms) | 11.8 | 600 | 6RX1800-4FK02 | 76 | 0.463 | 56.3 | 118.0 | 9.0 (100 ms) | 16.3 | 600 | 6RX1800-4FK03 | 106 | 0.333 | 68.8 | 152.9 | 15 (100 ms) | 22.3 | 600 | 6RX1800-4FK04 | 174 | 0.202 | 204.6 | 255.6 | 15 (100 ms) | 26.0 | 600 | 6RX1800-4FK05 | 232 | 0.152 | 178.3 | 231.5 | 20 (100 ms) | 37.8 | 600 | 6RX1800-4FK06 | 332 | 0.106 | 193.7 | 261.5 | 24 (100 ms) | 56.1 | 600 | 6RX1800-4FK07 | 374 | 0.094 | 189.1 | 279.2 | 24 (100 ms) | 56.8 | 600 | 6RX1800-4FK08 | 498 | 0.071 | 313.8 | 396.9 | 35 (200 ms) | 78.1 | 1000 | 6RX1800-4FK10 | 664 | 0.053 | 255.6 | 360.8 | 75 (200 ms) | 96.6 | 1000 | 6RX1800-4FK11 | 706 | 0.050 | 293.9 | 404.1 | 75 (200 ms) | 96.6 | 1000 | 6RX1800-4FK12 | 913 | 0.039 | 375.6 | 558.6 | 75 (200 ms) | 114.5 | 1000 | 6RX1800-4FK13 | 996 | 0.035 | 332.7 | 532.8 | 75 (200 ms) | 127.8 | 1000 | 6RX1800-4FK14 | 1328 | 0.027 | 320.4 | 573.7 | 75 (200 ms) | 177.6 | 1000 | 6RX1800-4FK15 | 1660 | 0.021 | 436.5 | 819.0 | 75 (200 ms) | 161.0 | 1000 | 6RX1800-4FK16 | 1826 | 0.019 | 464.7 | 819.9 | 75 (200 ms) | 164.2 | 1000 | 6RX1800-4FK17 | 2324 | 0.015 | 671.8 | 1056.7 | 75 (200 ms) | 258.2 | 1000 | 6RX1800-4FK18 | Rated voltage 575В V | В | 51 | 0.832 | 56.8 | 109.7 | 6.5 (100 ms) | 13.6 | 600 | 6RX1800-4GK00 | 106 | 0.399 | 65.5 | 156.7 | 15 (100 ms) | 26.4 | 600 | 6RX1800-4GK01 | 174 | 0.243 | 150.0 | 200.5 | 15 (100 ms) | 34.5 | 600 | 6RX1800-4GK02 | 332 | 0.127 | 252.1 | 327.3 | 24 (200 ms) | 63.1 | 600 | 6RX1800-4GK03 | 498 | 0.085 | 330.3 | 427.5 | 35 (200 ms) | 86.0 | 1000 | 6RX1800-4GK04 | 598 | 0.071 | 339.6 | 455.5 | 55 (200 ms) | 89.8 | 1000 | 6RX1800-4GK05 | 631 | 0.067 | 322.8 | 441.1 | 55 (200 ms) | 95.7 | 1000 | 6RX1800-4GK06 | 664 | 0.064 | 380.7 | 547.2 | 75 (200 ms) | 108.4 | 1000 | 6RX1800-4GK07 | 706 | 0.060 | 392.7 | 564.5 | 75 (200 ms) | 120.6 | 1000 | 6RX1800-4GK08 | 830 | 0.051 | 308.1 | 498.3 | 75 (200 ms) | 134.8 | 1000 | 6RX1800-4GK10 | 913 | 0.046 | 320.7 | 515.9 | 75 (200 ms) | 143.9 | 1000 | 6RX1800-4GK11 | 1245 | 0.034 | 371.4 | 605.4 | 75 (200 ms) | 206.1 | 1000 | 6RX1800-4GK12 | 1328 | 0.032 | 503.1 | 812.4 | 75 (200 ms) | 160.9 | 1000 | 6RX1800-4GK13 | 1660 | 0.025 | 631.3 | 993.1 | 75 (200 ms) | 202.0 | 1000 | 6RX1800-4GK14 | 1826 | 0.023 | 614.7 | 1006.9 | 75 (200 ms) | 212.1 | 1000 | 6RX1800-4GK15 | 2158 | 0.020 | 534.6 | 1073.7 | 75 (200 ms) | 303.0 | 1000 | 6RX1800-4GK16 | 2324 | 0.018 | 556.2 | 1110.0 | 75 (200 ms) | 321.6 | 1000 | 6RX1800-4GK17 |
Note: Commutating reactors with uK = 2В % are available on request. A limited tolerance range is also possible for parallel connections. Three-phase commutating reactors, uK = 4В % |
|---|
AC rated current | Inductance | Copper losses | Total losses | Short-circuit current rating (SCCR) | Weight | Rated insulation voltage | Article No. |
|---|
A | mH | W | W | kA | kg | V | В |
|---|
Rated voltage 690В V | 598 | 0.085 | 388.2 | 562.1 | 55 (200 ms) | 108.9 | 1000 | 6RX1800-4KK00 | 631 | 0.080 | 402.0 | 586.4 | 75 (200 ms) | 113.3 | 1000 | 6RX1800-4KK01 | 789 | 0.064 | 362.7 | 564.6 | 75 (200 ms) | 141.9 | 1000 | 6RX1800-4KK02 | 830 | 0.061 | 350.7 | 561.4 | 75 (200 ms) | 153.4 | 1000 | 6RX1800-4KK03 | 1245 | 0.041 | 505.2 | 845.7 | 75 (200 ms) | 169.7 | 1000 | 6RX1800-4KK04 | 1577 | 0.032 | 716.8 | 1093.8 | 75 (200 ms) | 226.1 | 1000 | 6RX1800-4KK05 | 1660 | 0.031 | 596.0 | 1011.8 | 75 (200 ms) | 257.2 | 1000 | 6RX1800-4KK06 | 2158 | 0.024 | 484.8 | 1185.6 | 75 (200 ms) | 360.2 | 1000 | 6RX1800-4KK07 | Rated voltage 830В V | 789 | 0.077 | 312.0 | 532.1 | 75 (200 ms) | 205.2 | 1000 | 6RX1800-4LK00 | 1245 | 0.049 | 692.4 | 1061.9 | 75 (200 ms) | 222.4 | 1000 | 6RX1800-4LK01 | 1577 | 0.039 | 479.4 | 1059.6 | 75 (200 ms) | 308.5 | 1000 | 6RX1800-4LK02 | 1826 | 0.033 | 585.6 | 1269.0 | 75 (200 ms) | 372.5 | 1000 | 6RX1800-4LK03 | Rated voltage 950В V | 1826 | 0.038 | 534.9 | 1303.5 | 75 (200 ms) | 399.7 | 1000 | 6RX1800-4MK00 |
Note: Commutating reactors with uK = 2В % are available on request. A limited tolerance range is also possible for parallel connections. Single-phase commutating reactors, uK = 4В % |
|---|
AC rated current | Inductance | Copper losses | Total losses | Short-circuit current rating (SCCR) | Weight | Rated insulation voltage | Article No. |
|---|
A | mH | W | W | kA | kg | V | В |
|---|
Rated voltage 400В V | 3 | 16.98 | 3 | 5 | 0.8 (20 ms) | 0.7 | 600 | 6RX1800-4DE00 | 5 | 10.19 | 5 | 7 | 0.8 (20 ms) | 1.5 | 600 | 6RX1800-4DE01 | 10 | 5.090 | 7 | 12 | 2 (20 ms) | 2.0 | 600 | 6RX1800-4DE02 | 15 | 3.400 | 8 | 17 | 2 (20 ms) | 2.3 | 600 | 6RX1800-4DE03 | 25 | 2.040 | 8 | 29 | 6 (20 ms) | 3.0 | 600 | 6RX1800-4DE04 | 30 | 1.700 | 10 | 30 | 6 (20 ms) | 3.8 | 600 | 6RX1800-4DE05 | 40 | 1.270 | 9 | 49 | 10 (20 ms) | 5.2 | 600 | 6RX1800-4DE06 | 85 | 0.600 | 13 | 67 | 15 (20 ms) | 9.6 | 600 | 6RX1800-4DE07 |
|