3TX6346-3BЦена на сайте указана розничная в ЕВРО без учета НДС. Для уточнения цены и размера предоставляемой скидки - звоните или присылайте заявки | Заказной номер | Вес | PG | Описание продукта | Цена | | 3TX6346-3B | 0.25 | 41B | КРЫШКА КОНТАКТОВ, ПРОЗРАЧНАЯ ДЛЯ M12 РЕЗЬБА 1 КОМПЛЕКТ = 6 ШТУК | По запросу |
п»ї Iron output reactors for AC operating mechanisms Output reactors are used on the load side of frequency converters and motor currents flow through them. Output reactors compensate capacitive charge-reversal currents with long cables and, in the case of long motor cables, limit the dv/dt at the motor terminals. This enables the use of longer motor supply cables: - 200В m shielded motor cable
- 300В m unshielded motor cable
Use of iron-core output reactors: - Operating mechanisms with standard and trans-standard asynchronous motors and a rated motor frequency (field weakening frequency) of up to 87 Hz and a maximum frequency of 200 Hz.
- Operating mechanisms with reluctance or permanently excited synchronous motors with a maximum frequency of 120 Hz.
Note on the versions Standard (Catalog LVВ 60): The following generic parameters apply, which must not be exceeded: - Maximum motor cable length 200 m, shielded cable
- Maximum motor cable length 300 m, unshielded cable
- Maximum motor cable cross-sections for performance class:
- up to 2.2В kW/1.5В mmВІ
- > 2.2 kW ≤ 7.5 kW/2.5 mm²
- > 7.5 kW ≤ 11 kW/4 mm²
- > 11 kW ≤ 22 kW/10 mm²
- > 22 kW ≤ 30 kW/16 mm²
- > 30 kW ≤ 37 kW/25 mm²
- > 37 kW ≤ 50 kW/35 mm²
- > 50 kW ≤ 75 kW/70 mm²
- Maximum clock frequency 8В kHz
- Maximum motor frequency of output reactor 200В Hz
- Maximum motor frequency of sinewave filter 100В Hz
- UN 3В ACВ 500В V В±5В %.
If these do not meet your requirements, versions in Standard modified or customized solutions are available. For more information contact "mdexx GmbH" in Bremen. e-mail: Anfrage@mdexx.com
|