Dimensions and weight |
Dimensions W x H x D (mm) | 80 x 125 x 130 |
Weight | Approx. 500 g |
Technical data - General |
Degree of protection | IP20 |
Ambient temperature | - 20 °C to + 60 °C |
Standards and approvals |
| IEC 61784-1:2002 Ed1 CP 3/1 |
| 94/9/EG (ATEX 100a) |
| II 3 (2) G EEx nA[ib] IIC T4 |
| Class I, Division2, Group A, B, C, D T4 Class I Zone 2, Group IIC T4 AIS Class I, Divison 1, Group A, B, C, D [Aexib] IIC, Class I, Zone1, 2, Group IIC |
| Class I, Division2, Group A, B, C, D T4 Class I Zone 2, Group IIC T4 AIS Class I, Divison 1, Group A, B, C, D [Aexib] IIC, Class I, Zone1, 2, Group IIC |
| IEC61131-2, Part 2 |
| Conforming with 89/336/EWG Conforming with 73/23/EWG |
- Ship-building certification
| Classification companies • ABS (American Bureau of Shipping) • BV (Bureau Veritas) • DNV (Det Norske Veritas) • GL (Germanischer Lloyd) • LRD (Lloyds Register of Shipping) • Class NK (Nippon Kaiji Kyokai) |
Module-Specific Specifications |
Transfer rate on PROFIBUS DP, PROFIBUS RS 485-IS | 9.6; 19.2; 45.45; 93.75; 187.5; 500 kbit/s 1.5 Mbps |
Bus-Protocol | PROFIBUS DP |
Voltages, Currents, Potentials |
Nominal supply voltage for RS 485-IS coupler | 24 V DC (20.4 to 28.8 V) |
- Polarity reversal protection
| Yes |
| Min. 5 ms |
Potential isolation for 24 V power supply |
| Yes |
| 500 V DC |
| Yes |
| AC 500 V |
Current consumption RS 485-IS coupler (24 V DC), max. | 150 mA |
Power loss of the module, typically | 3 Watts |
Status, alarms, diagnostics |
Status display | no |
Alarms | None |
Diagnostic functions | Yes |
- Bus monitoring PROFIBUS DP (primary)
| Yellow LED "DP1" |
- Bus monitoring PROFIBUS RS 485-IS (secondary)
| Yellow LED "DP2" |
- Monitoring 24 V power supply
| Green LED "ON" |
Technical safety notice |
VDC | ±4.2 V |
ISC | ±93 mA |
P0 | 0.1 Watts |
Vmax | ±4.2 V |
LI | 0 |
Ci | 0 |
Um | AC 250 V |
Ta | –25 ... +60 °C |
RS 485-IS segment |
permitted cable length on a single line | RS 485–IS | DP Ex i |
| 1,000 m | 200 m |
| 400 m | 200 m |
| 200 m | 200 m |
Number of PROFIBUS DP nodes that can be connected, max. | 31 | 16 |
PROFIBUS RS 485-IS bus termination switch | integrated, can be added |