The electronics modules of the SIMATIC ET 200iSP distributed I/O?system equipped with safety functions can be used together with the safety-related automation systems (controllers) for the implementation of safety applications. The input modules record the process signals, evaluate them, and prepare them for addional processing by the automation system. The output modules convert the safety-related signals output by the automation systems so that they are suitable for controlling the connected actuators.
F digital input modules
8 F-DI Ex NAMUR Safety-related digital input module for evaluating the signals from IEC 60947?5?6/NAMUR sensors and connected/non-connected mechanical contacts in hazardous and non-hazardous areas
SIL 3/Cat. 3/PLe with 8 inputs (1-channel/1oo1 evaluation) or 4 inputs (2-channel/1oo2 evaluation)
8 short-circuit-proof sensor supplies (8 V DC) for 1 channel each
Inputs and sensor supplies electrically isolated from power bus and backplane bus
Diagnostics evaluation (deactivated for non-connected mechanical contacts)
Internal diagnostics buffer
Programmable diagnostics interrupt
Support of time stamping
Channel-selective passivation
Firmware update using HW Config possible
Exclusively for safety mode
LED displays for safety mode, group errors and channel status/fault
F digital output modules
4 F-DO Ex DC 17.4 V/40 mA Safety-related digital output module for controlling actuators in hazardous and non-hazardous areas, e.g. solenoid valves, DC current relays or indicator lamps
SIL 3/Cat. 3/PLe with 4 outputs, P/P-switching
Electrical isolation from power bus and backplane bus
Rated load voltage 17.4 V DC
Max. output current 40 mA
Performance enhancement through parallel connection of two digital outputs for one actuator
Short-circuit, overload and wire-break monitoring
Configurable diagnostics
Internal diagnostics buffer
Programmable diagnostics interrupt
Channel-selective passivation
Firmware update using HW Config possible
Exclusively for safety mode
LED displays for safety mode, group errors and channel status/fault
F analog input modules
4 F-AI Ex HART (0 ... 20 mA or 4 ... 20 mA) Safety-related digital input module for evaluating the signals from current sensors in hazardous and non-hazardous areas, e.g. 2-wire transmitters and HART field devices
SIL 3/Cat. 3/PLe with 4 inputs of one module (1-channel/1oo1 evaluation) or 4 inputs of two modules (2-channel/1oo2 evaluation)
Measuring ranges: 0 ... 20 mA or 4 ... 20 mA
Resolution 15 bit + sign
HART communication in measuring range 4 ... 20 mA
4 short-circuit-proof sensor supplies (min. 12 V DC; max. 26 V DC) for 1 channel each
Inputs and sensor supplies electrically isolated from backplane bus
Configurable diagnostics
Programmable diagnostics interrupt
Internal diagnostics buffer
Firmware update using HW Config possible
Exclusively for safety mode
LED displays for safety mode, group errors, channel faults and HART status per channel