Input current | |
from supply voltage L+, max. | 30 mA |
Power loss | |
Power loss, typ. | 0.5 W |
Time stamping | |
Description | for each digital input, digital input module, total ET 200iS |
Accuracy | 20 ms |
Number of stampable digital inputs, max. | 64; for accuracy class 20 ms |
Time format | RFC 1119 Internet (ISP) |
Time resolution | 1 ms |
Time interval for transmitting the message buffer if a message is present | 1 000 ms |
Time stamp on signal change | rising / falling edge as signal entering or exiting |
Interfaces | |
Interface physics, RS 485 | Yes; intrinsically safe |
PROFIBUS DP | |
| 1.5 Mbit/s; 9,6 / 19,2 / 45,45 / 93,75 / 187,5 / 500 kbit/s |
| Yes |
| Yes |
| Yes; Slave to slave as publisher |
Protocols | |
PROFIBUS DP | Yes |
Protocols (Ethernet) | |
| No |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information | |
Alarms | Yes |
Diagnostic functions | Yes |
Alarms | |
| Yes |
| Yes |
Diagnostics indication LED | |
| Yes |
| Yes |
| Yes |
Potential separation | |
between supply voltage and electronics | Yes |
Standards, approvals, certificates | |
CE mark | Yes |
Use in hazardous areas | |
| II2 G Ex ib IIC T4 and I M2 Ex ib I |
| 04 ATEX 1243 |
Dimensions | |
Width | 30 mm |
Height | 129 mm |
Depth | 136.5 mm |
Weights | |
Weight, approx. | 245 g |