General information | | |
Product type designation | IM 155-6 PN ST with BA 2xRJ45 and server module | IM 155-6 PN ST with server module |
Product function | | |
| Yes; I&M0 to I&M3 | Yes; I&M0 to I&M3 |
Supply voltage | | |
Rated value (DC) | 24 V | 24 V |
Reverse polarity protection | Yes | Yes |
Mains buffering | | |
| 5 ms | 5 ms |
Hardware configuration | | |
Rack | | |
| 32; + 16 ET 200AL modules | 32; + 16 ET 200AL modules |
Submodules | | |
| 256 | 256 |
Interfaces | | |
Number of PROFINET interfaces | 1; 2 ports (switch) | 1; 2 ports (switch) |
1. Interface | | |
Interface types | | |
| 2 | 2 |
| Yes | Yes |
| Yes; Pre-assembled BusAdapter BA 2x RJ45 | |
| Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FC | Yes; Applicable BusAdapter: BA 2x RJ45, BA 2x FC |
Functionality | | |
| Yes | Yes |
| Yes | Yes |
| Yes; PROFINET MRP | Yes; PROFINET MRP |
Interface types | | |
RJ 45 (Ethernet) | | |
| PROFINET with 100 Mbit/s full duplex (100BASE-TX) | PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
| Yes; for Ethernet services | Yes; for Ethernet services |
| Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) | Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
| Yes | Yes |
| Yes | Yes |
PROFINET IO Device | | |
Services | | |
| No | No |
| Yes | Yes |
| Yes; with send cycles of between 250 µs and 4 ms in increments of 125 µs | Yes; with send cycles of between 250 µs and 4 ms in increments of 125 µs |
| Yes | Yes |
| No | No |
| No | No |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| 2 | 2 |
Open IE communication | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
Isochronous mode | | |
Isochronous operation (application synchronized up to terminal) | No | No |
Interrupts/diagnostics/status information | | |
Status indicator | Yes | Yes |
Alarms | Yes | Yes |
Diagnostic functions | Yes | Yes |
Diagnostics indication LED | | |
| Yes; Green LED | Yes; Green LED |
| Yes; Red LED | Yes; Red LED |
| Yes; yellow LED | Yes; yellow LED |
| Yes; Green LED | Yes; Green LED |
| Yes; 2x green link LEDs on BusAdapter | Yes; 2x green link LEDs on BusAdapter |
Isolation | | |
Isolation tested with | 707 V DC (type test) and according to EN 50155 (routine test) | 707 V DC (type test) and according to EN 50155 (routine test) |
Standards, approvals, certificates | | |
Network loading class | 2 | 2 |
Security level | According to Security Level 1 Test Cases V1.1.1 | According to Security Level 1 Test Cases V1.1.1 |
Railway application | | |
| Yes; EMC for rail vehicles | Yes; EMC for rail vehicles |
| Yes; EMC for signal and telecommunications systems | Yes; EMC for signal and telecommunications systems |
| Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC | Yes; Railway applications - overvoltage category OV2; pollution degree PD2; rated surge voltage UNi = 0.5 kV; UNm = 24 V DC |
| Yes; Rail vehicles - see ambient conditions | Yes; Rail vehicles - see ambient conditions |
| Yes; Stationary electrical equipment - see ambient conditions | Yes; Stationary electrical equipment - see ambient conditions |
| Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) | Yes; Signal and telecommunications systems - see ambient conditions; vibrations and shocks: Application point outside of tracks (1 m to 3 m away from track) |
| Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 | Yes; Rail vehicles - temperature class Tx, horizontal mounting position, salt spray Class ST2 |
| Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B | Yes; Rail vehicles - vibrations and shocks: Category 1 Class A/B |
| Yes; Rail vehicles - verification on request | Yes; Rail vehicles - verification on request |
Ambient conditions | | |
Ambient temperature during operation | | |
| -40 °C; = Tmin | -40 °C; = Tmin |
| 70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155) | 70 °C; = Tmax; +85 °C for 10 min (Tx acc. to EN 50155) |
Extended ambient conditions | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) |
Relative humidity | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 5B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5B2 mold and fungal spores (excluding fauna). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5C3 (RH < 75%) including salt spray according to EN 50155 (ST2). The supplied plug covers must remain in place over the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! | Yes; Class 5S3 including sand and dust. The supplied plug covers must remain in place over the unused interfaces during operation! |
Dimensions | | |
Width | 50 mm | 50 mm |
Height | 117 mm | 117 mm |
Depth | 74 mm | 74 mm |
Weights | | |
Weight, approx. | 191 g; IM155PN ST with BA 2x RJ45 (mounted) | 147 g; without BusAdapter |
Other | | |
Note: | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 | For use in railway applications, also observe the product information "SIPLUS extreme RAIL" A5E37661960A Online Support article 109736776 |