General information | |
Product type designation | AI 4xU/I/RTD/TC / AQ 2xU/I ST |
Product function | |
| Yes; I&M0 to I&M3 |
| No |
| No |
| No |
| No |
Engineering with | |
| V13 / V13.0.2 |
| V5.5 SP3 / - |
| V1.0 / V5.1 |
| V2.3 / - |
Operating mode | |
| No |
| Yes |
| Yes |
CiR – Configuration in RUN | |
Reparameterization possible in RUN | Yes |
Calibration possible in RUN | Yes |
Supply voltage | |
Type of supply voltage | DC |
Rated value (DC) | 24 V |
Reverse polarity protection | Yes |
Analog inputs | |
Number of analog inputs | 4 |
| 4 |
| 4 |
| 2 |
| 4 |
permissible input voltage for voltage input (destruction limit), max. | 28.8 V |
permissible input current for current input (destruction limit), max. | 40 mA |
Technical unit for temperature measurement adjustable | Yes; °C/°F/K |
Analog input with oversampling | No |
Standardization of measured values | No |
Input ranges (rated values), voltages | |
| No |
| No |
| Yes |
| Yes |
| Yes |
| Yes |
| No |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
Input ranges (rated values), currents | |
| Yes |
| Yes |
| Yes |
Input ranges (rated values), thermocouples | |
| Yes |
| No |
| Yes |
| Yes |
| Yes |
| No |
| Yes |
| Yes |
| Yes |
| Yes |
| No |
| No |
Input ranges (rated values), resistance thermometer | |
| No |
| No |
| No |
| No |
| No |
| No |
| No |
| No |
| Yes; Standard/climate |
| No |
| Yes; Standard/climate |
| No |
| Yes; Standard/climate |
| No |
| No |
| No |
| No |
| No |
| No |
| No |
| No |
| No |
| No |
| Yes; Standard/climate |
| No |
| Yes; Standard/climate |
| No |
| Yes; Standard/climate |
| No |
| Yes; Standard/climate |
| No |
Input ranges (rated values), resistors | |
| Yes |
| Yes |
| Yes |
| No |
| Yes |
| Yes |
Thermocouple (TC) | |
Temperature compensation | |
| Yes |
Cable length | |
| 800 m; for U/I, 200 m for R/RTD, 50 m for TC |
Analog outputs | |
Number of analog outputs | 2 |
Cycle time (all channels), min. | 3.2 ms; ±0.5 ms, regardless of the number of activated channels |
Output ranges, voltage | |
| Yes |
| Yes |
| No |
| Yes |
Output ranges, current | |
| Yes |
| Yes |
| Yes |
Connection of actuators | |
| Yes |
| Yes |
| Yes |
Load impedance (in rated range of output) | |
| 1 k?; 0.5 kOhm at 1 to 5 V |
| 1 µF |
| 750 ? |
| 10 mH |
Cable length | |
| 800 m; for current, 200 m for voltage |
Analog value generation for the inputs | |
Integration and conversion time/resolution per channel | |
| 16 bit |
| Yes |
| 2,5 / 16,67 / 20 / 100 ms |
| 9 / 23 / 27 / 107 ms |
| 9 ms |
| 150 ohm, 300 ohm, 600 ohm, Pt100, Pt200, Ni100: 2 ms, 6000 ohm, Pt500, Pt1000, Ni1000, LG-Ni1000, PTC: 4 ms |
| 400 / 60 / 50 / 10 |
Smoothing of measured values | |
| Yes |
Analog value generation for the outputs | |
Integration and conversion time/resolution per channel | |
| 16 bit |
| 0.5 ms |
Settling time | |
| 1.5 ms |
| 2.5 ms |
| 2.5 ms |
Encoder | |
Connection of signal encoders | |
| Yes |
| Yes |
| 820 ? |
| Yes |
| Yes; Only for PTC |
| Yes; All measuring ranges except PTC; internal compensation of the cable resistances |
| Yes; All measuring ranges except PTC |
Errors/accuracies | |
Basic error limit (operational limit at 25 °C) | |
| 0.1 % |
| 0.1 % |
| 0.1 % |
| 0.1 %; Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K |
| 0.1 %; Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K |
| 0.2 % |
| 0.2 % |
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency | |
| 40 dB |
| 10 V |
| 60 dB |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | No |
Interrupts/diagnostics/status information | |
Diagnostics function | Yes |
Substitute values connectable | Yes |
Alarms | |
| Yes |
| Yes; two upper and two lower limit values in each case |
Diagnostic messages | |
| Yes |
| Yes; only for input type 1 ... 5 V, 4 ... 20 mA, TC, R, RTD and output type current |
| Yes; Only for output type "voltage" |
| Yes |
Diagnostics indication LED | |
| Yes; Green LED |
| Yes; Red LED |
| Yes; Green LED |
| Yes; Green LED |
| Yes; Red LED |
| Yes; Red LED |
Potential separation | |
Potential separation analog inputs | |
| Yes |
Potential separation analog outputs | |
| Yes |
Isolation | |
Isolation tested with | 707 V DC (type test) |
Ambient conditions | |
Ambient temperature during operation | |
| 0 °C |
| 60 °C |
| 0 °C |
| 40 °C |
Decentralized operation | |
Prioritized startup | No |
Dimensions | |
Width | 25 mm |
Height | 147 mm |
Depth | 129 mm |
Weights | |
Weight, approx. | 250 g |
Other | |
Note: | Supplied incl. 40-pole push-in front connectors. Additional basic error and noise for integration time = 2.5 ms: Voltage: ±250 mV (±0.02%), ±80 mV (±0.05%), ±50 mV (±0.05%); resistance: 150 Ohms (±0.02%); resistance thermometer: Pt100 climate: ±0.08 K, Ni100 climate: ±0.08 K; thermoelement: Type B, R, S: ±3 K, type E, J, K, N, T: ±1 K |