SM 534 analog input/output modules

Article number

6ES7534-7QE00-0AB0

S7-1500, AI 4X U/I/RTD/TC/AQ 2X U/I ST

General information

 

Product type designation

AI 4xU/I/RTD/TC / AQ 2xU/I ST

Product function

 

  • ? I&M data

Yes; I&M0 to I&M3

  • ? Measuring range scalable

No

  • ? Scalable measured values

No

  • ? Adjustment of measuring range

No

  • ? Output range scalable

No

Engineering with

 

  • ? STEP 7 TIA Portal configurable/integrated as of version

V13 / V13.0.2

  • ? STEP 7 configurable/integrated as of version

V5.5 SP3 / -

  • ? PROFIBUS as of GSD version/GSD revision

V1.0 / V5.1

  • ? PROFINET as of GSD version/GSD revision

V2.3 / -

Operating mode

 

  • ? Oversampling

No

  • ? MSI

Yes

  • ? MSO

Yes

CiR – Configuration in RUN

 

Reparameterization possible in RUN

Yes

Calibration possible in RUN

Yes

Supply voltage

 

Type of supply voltage

DC

Rated value (DC)

24 V

Reverse polarity protection

Yes

Analog inputs

 

Number of analog inputs

4

  • ? For current measurement

4

  • ? For voltage measurement

4

  • ? For resistance/resistance thermometer measurement

2

  • ? For thermocouple measurement

4

permissible input voltage for voltage input (destruction limit), max.

28.8 V

permissible input current for current input (destruction limit), max.

40 mA

Technical unit for temperature measurement adjustable

Yes; °C/°F/K

Analog input with oversampling

No

Standardization of measured values

No

Input ranges (rated values), voltages

 

  • ? 0 to +5 V

No

  • ? 0 to +10 V

No

  • ? 1 V to 5 V

Yes

  • ? -1 V to +1 V

Yes

  • ? -10 V to +10 V

Yes

  • ? -2.5 V to +2.5 V

Yes

  • ? -25 mV to +25 mV

No

  • ? -250 mV to +250 mV

Yes

  • ? -5 V to +5 V

Yes

  • ? -50 mV to +50 mV

Yes

  • ? -500 mV to +500 mV

Yes

  • ? -80 mV to +80 mV

Yes

Input ranges (rated values), currents

 

  • ? 0 to 20 mA

Yes

  • ? -20 mA to +20 mA

Yes

  • ? 4 mA to 20 mA

Yes

Input ranges (rated values), thermocouples

 

  • ? Type B

Yes

  • ? Type C

No

  • ? Type E

Yes

  • ? Type J

Yes

  • ? Type K

Yes

  • ? Type L

No

  • ? Type N

Yes

  • ? Type R

Yes

  • ? Type S

Yes

  • ? Type T

Yes

  • ? Type U

No

  • ? Type TXK/TXK(L) to GOST

No

Input ranges (rated values), resistance thermometer

 

  • ? Cu 10

No

  • ? Cu 10 according to GOST

No

  • ? Cu 50

No

  • ? Cu 50 according to GOST

No

  • ? Cu 100

No

  • ? Cu 100 according to GOST

No

  • ? Ni 10

No

  • ? Ni 10 according to GOST

No

  • ? Ni 100

Yes; Standard/climate

  • ? Ni 100 according to GOST

No

  • ? Ni 1000

Yes; Standard/climate

  • ? Ni 1000 according to GOST

No

  • ? LG-Ni 1000

Yes; Standard/climate

  • ? Ni 120

No

  • ? Ni 120 according to GOST

No

  • ? Ni 200

No

  • ? Ni 200 according to GOST

No

  • ? Ni 500

No

  • ? Ni 500 according to GOST

No

  • ? Pt 10

No

  • ? Pt 10 according to GOST

No

  • ? Pt 50

No

  • ? Pt 50 according to GOST

No

  • ? Pt 100

Yes; Standard/climate

  • ? Pt 100 according to GOST

No

  • ? Pt 1000

Yes; Standard/climate

  • ? Pt 1000 according to GOST

No

  • ? Pt 200

Yes; Standard/climate

  • ? Pt 200 according to GOST

No

  • ? Pt 500

Yes; Standard/climate

  • ? Pt 500 according to GOST

No

Input ranges (rated values), resistors

 

  • ? 0 to 150 ohms

Yes

  • ? 0 to 300 ohms

Yes

  • ? 0 to 600 ohms

Yes

  • ? 0 to 3000 ohms

No

  • ? 0 to 6000 ohms

Yes

  • ? PTC

Yes

Thermocouple (TC)

 

Temperature compensation

 

  • parameterizable

Yes

Cable length

 

  • ? shielded, max.

800 m; for U/I, 200 m for R/RTD, 50 m for TC

Analog outputs

 

Number of analog outputs

2

Cycle time (all channels), min.

3.2 ms; ±0.5 ms, regardless of the number of activated channels

Output ranges, voltage

 

  • ? 0 to 10 V

Yes

  • ? 1 V to 5 V

Yes

  • ? -5 V to +5 V

No

  • ? -10 V to +10 V

Yes

Output ranges, current

 

  • ? 0 to 20 mA

Yes

  • ? -20 mA to +20 mA

Yes

  • ? 4 mA to 20 mA

Yes

Connection of actuators

 

  • ? for voltage output two-wire connection

Yes

  • ? for voltage output four-wire connection

Yes

  • ? for current output two-wire connection

Yes

Load impedance (in rated range of output)

 

  • ? with voltage outputs, min.

1 k?; 0.5 kOhm at 1 to 5 V

  • ? with voltage outputs, capacitive load, max.

1 µF

  • ? with current outputs, max.

750 ?

  • ? with current outputs, inductive load, max.

10 mH

Cable length

 

  • ? shielded, max.

800 m; for current, 200 m for voltage

Analog value generation for the inputs

 

Integration and conversion time/resolution per channel

 

  • ? Resolution with overrange (bit including sign), max.

16 bit

  • ? Integration time, parameterizable

Yes

  • ? Integration time (ms)

2,5 / 16,67 / 20 / 100 ms

  • ? Basic conversion time, including integration time (ms)

9 / 23 / 27 / 107 ms

  • additional conversion time for wire-break monitoring

9 ms

  • additional conversion time for resistance measurement

150 ohm, 300 ohm, 600 ohm, Pt100, Pt200, Ni100: 2 ms, 6000 ohm, Pt500, Pt1000, Ni1000, LG-Ni1000, PTC: 4 ms

  • ? Interference voltage suppression for interference frequency f1 in Hz

400 / 60 / 50 / 10

Smoothing of measured values

 

  • ? parameterizable

Yes

Analog value generation for the outputs

 

Integration and conversion time/resolution per channel

 

  • ? Resolution with overrange (bit including sign), max.

16 bit

  • ? Conversion time (per channel)

0.5 ms

Settling time

 

  • ? for resistive load

1.5 ms

  • ? for capacitive load

2.5 ms

  • ? for inductive load

2.5 ms

Encoder

 

Connection of signal encoders

 

  • ? for voltage measurement

Yes

  • ? for current measurement as 2-wire transducer

Yes

  • Burden of 2-wire transmitter, max.

820 ?

  • ? for current measurement as 4-wire transducer

Yes

  • ? for resistance measurement with two-wire connection

Yes; Only for PTC

  • ? for resistance measurement with three-wire connection

Yes; All measuring ranges except PTC; internal compensation of the cable resistances

  • ? for resistance measurement with four-wire connection

Yes; All measuring ranges except PTC

Errors/accuracies

 

Basic error limit (operational limit at 25 °C)

 

  • ? Voltage, relative to input range, (+/-)

0.1 %

  • ? Current, relative to input range, (+/-)

0.1 %

  • ? Resistance, relative to input range, (+/-)

0.1 %

  • ? Resistance thermometer, relative to input range, (+/-)

0.1 %; Ptxxx standard: ±0.7 K, Ptxxx climate: ±0.2 K, Nixxx standard: ±0.3 K, Nixxx climate: ±0.15 K

  • ? Thermocouple, relative to input range, (+/-)

0.1 %; Type B: > 600 °C ±1.7 K, type E: > -200 °C ±0.7 K, type J: > -210 °C ±0.8 K, type K: > -200 °C ±1.2 K, type N: > -200 °C ±1.2 K, type R: > 0 °C ±1.9 K, type S: > 0 °C ±1.9 K, type T: > -200 °C ±0.8 K

  • ? Voltage, relative to output range, (+/-)

0.2 %

  • ? Current, relative to output range, (+/-)

0.2 %

Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency

 

  • ? Series mode interference (peak value of interference < rated value of input range), min.

40 dB

  • ? Common mode voltage, max.

10 V

  • ? Common mode interference, min.

60 dB

Isochronous mode

 

Isochronous operation (application synchronized up to terminal)

No

Interrupts/diagnostics/status information

 

Diagnostics function

Yes

Substitute values connectable

Yes

Alarms

 

  • ? Diagnostic alarm

Yes

  • ? Limit value alarm

Yes; two upper and two lower limit values in each case

Diagnostic messages

 

  • ? Monitoring the supply voltage

Yes

  • ? Wire-break

Yes; only for input type 1 ... 5 V, 4 ... 20 mA, TC, R, RTD and output type current

  • ? Short-circuit

Yes; Only for output type "voltage"

  • ? Overflow/underflow

Yes

Diagnostics indication LED

 

  • ? RUN LED

Yes; Green LED

  • ? ERROR LED

Yes; Red LED

  • ? Monitoring of the supply voltage (PWR-LED)

Yes; Green LED

  • ? Channel status display

Yes; Green LED

  • ? for channel diagnostics

Yes; Red LED

  • ? for module diagnostics

Yes; Red LED

Potential separation

 

Potential separation analog inputs

 

  • ? between the channels and backplane bus

Yes

Potential separation analog outputs

 

  • ? between the channels and backplane bus

Yes

Isolation

 

Isolation tested with

707 V DC (type test)

Ambient conditions

 

Ambient temperature during operation

 

  • ? horizontal installation, min.

0 °C

  • ? horizontal installation, max.

60 °C

  • ? vertical installation, min.

0 °C

  • ? vertical installation, max.

40 °C

Decentralized operation

 

Prioritized startup

No

Dimensions

 

Width

25 mm

Height

147 mm

Depth

129 mm

Weights

 

Weight, approx.

250 g

Other

 

Note:

Supplied incl. 40-pole push-in front connectors. Additional basic error and noise for integration time = 2.5 ms: Voltage: ±250 mV (±0.02%), ±80 mV (±0.05%), ±50 mV (±0.05%); resistance: 150 Ohms (±0.02%); resistance thermometer: Pt100 climate: ±0.08 K, Ni100 climate: ±0.08 K; thermoelement: Type B, R, S: ±3 K, type E, J, K, N, T: ±1 K


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30