Siemens
ÑÐÅÄÑÒÂÀ ÏÐÎÌÛØËÅÍÍÎÉ ÀÂÒÎÌÀÒÈÇÀÖÈÈ
îôèöèàëüíûé ïàðòíåð Ñèìåíñ
Êàòàëîã ÑÀ01 2017
àðõèâíûé
(4872) 700-366
skenergo@mail.ru

Motor Modules
General technical specifications

Electrical specifications

Efficiency

98.5 %

DC link voltage

(up to 2000 m (6562 ft) above sea level)

510 ... 720 V DC (line supply voltage 380 ... 480 V 3 AC) or
675 ... 1035 V DC (line supply voltage 500 ... 690 V 3 AC)

Output frequency 1)

 

  • Control mode Servo

0 ... 550 Hz

  • Control mode Vector

0 ... 550 Hz

  • Control mode V/f

0 ... 550 Hz

Safety Integrated

Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to EN ISO 13849?1 and Control Category 3 acc. to EN ISO 13849?1.



1) Please note:

• The correlation between the maximum output frequency, pulse frequency and current derating. Higher output frequencies on request For further information, see https://support.industry.siemens.com/cs/document/104020669

• The correlation between the minimum output frequency and permissible output current (current derating). Information is provided in the SINAMICS Low Voltage Engineering Manual.

Line voltage 380 ... 480 V 3 AC
DC link voltage 510 ... 720 V DC

Motor Modules

 

6SL3325-1TE32-1AA3

6SL3325-1TE32-6AA3

6SL3325-1TE33-1AA3

6SL3325-1TE35-0AA3

6SL3325-1TE36-1AA3

Type rating

 

 

 

 

 

 

  • At IL (50 Hz 400 V) 1)

kW

110

132

160

250

315

  • At IH (50 Hz 400 V) 1)

kW

90

110

132

200

250

  • At IL (60 Hz 460 V) 2)

hp

150

200

250

400

500

  • At IH (60 Hz 460 V) 2)

hp

150

200

200

350

350

Output current

 

 

 

 

 

 

  • Rated current Irated O

A

210

260

310

490

605

  • Base-load current IL3)

A

205

250

302

477

590

  • Base-load current IH4)

A

178

233

277

438

460

  • Maximum current Imax O

A

307

375

453

715

885

DC link current

 

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

 

  • Basic Line Module

A

256

317

380

600

738

  • Active Line Module

A

230

287

340

538

664

  • Base-load current IL DC 3)
    when supplied via

 

 

 

 

 

 

  • Basic Line Module

A

250

305

368

581

719

  • Active Line Module

A

225

274

331

522

646

  • Base-load current IH DC 4)
    when supplied via

 

 

 

 

 

 

  • Basic Line Module

A

227

284

338

534

561

  • Active Line Module

A

195

255

303

480

504

Current demand

 

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

1.4

1.4

1.5

1.5

1.6

DC link capacitance

?F

4800

5800

8400

9600

12600

Pulse frequency 5)

 

 

 

 

 

 

  • Rated frequency

kHz

2

2

2

2

1.25

  • Pulse frequency, max.

 

 

 

 

 

 

  • Without current derating

kHz

2

2

2

2

1.25

  • With current derating

kHz

8

8

8

8

7.5

Power loss, max. 6)

 

 

 

 

 

 

  • At 50 Hz 400 V

kW

1.61

1.95

2.29

3.56

4.81

  • At 60 Hz 460 V

kW

1.68

2.06

2.38

3.74

5.25

  • Dissipated to ambient air

kW

0.06

0.07

0.09

0.14

0.16

Coolant volume flow 7)

l/min

9

9

12

12

16

Liquid volume

of the integrated heat exchanger

dm3

0.31

0.31

0.91

0.91

0.74

Pressure drop, typ. 8)

for volume flow

Pa

70000

70000

70000

70000

70000

Heat exchanger material

 

Stainless steel

Stainless steel

Stainless steel

Stainless steel

Aluminum

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

52

52

52

52

54

DC link connection

DCP, DCN

 

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

Motor connection

U2, V2, W2

 

Hole for M12

Hole for M12

Hole for M12

Hole for M12

2 ? hole for M12

  • Conductor cross section, max. (IEC)

mm2

2 ? 95

2 ? 95

2 ? 240

2 ? 240

4 ? 185

PE/GND connection

 

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

  • Conductor cross section, max. (IEC)

mm2

2 ? 95

2 ? 95

2 ? 240

2 ? 240

4 ? 185

Cable length, max. 9)

 

 

 

 

 

 

  • Shielded

m (ft)

300 (984)

300 (984)

300 (984)

300 (984)

300 (984)

  • Unshielded

m (ft)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

150 (5.91)

150 (5.91)

150 (5.91)

150 (5.91)

265 (10.4)

  • Height

mm (in)

746 (29.4)

746 (29.4)

1172 (46.1)

1172 (46.1)

1002 (39.5)

  • Depth

mm (in)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

Weight, approx.

kg (lb)

41 (90)

41 (90)

80 (176)

80 (176)

110 (243)

Frame size

 

FXL

FXL

GXL

GXL

HXL



1) Rated output of a typical 6?pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.

2) Rated output of a typical 6?pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5)Additional notes regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.

7) The value applies to coolants comprising water and a mixture of water and anti-freeze agent.

8)The value is valid for water as coolant. Additional information and notes on other coolants is provided in the SINAMICS Low Voltage Engineering Manual.

9) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

Line voltage 380 ... 480 V 3 AC
DC link voltage 510 ... 720 V DC

Motor Modules

 

6SL3325-1TE37-5AA3

6SL3325-1TE38-4AA3

6SL3325-1TE41-0AA3

6SL3325-1TE41-2AA3

6SL3325-1TE41-4AA3

6SL3325-1TE41-4AS3 1)

Type rating

 

 

 

 

 

 

 

  • At IL (50 Hz 400 V) 2)

kW

400

450

560

710

800

800

  • At IH (50 Hz 400 V) 2)

kW

315

400

450

630

710

630

  • At IL (60 Hz 460 V) 3)

hp

600

700

800

1000

1150

1000

  • At IH (60 Hz 460 V) 3)

hp

450

600

700

900

1000

900

Output current

 

 

 

 

 

 

 

  • Rated current Irated O

A

745

840

985

1260

1405

1330

  • Base-load current IL4)

A

725

820

960

1230

1370

1310

  • Base-load current I 5)

A

570

700

860

1127

1257

1150

  • Maximum current Imax O

A

1087

1230

1440

1845

2055

2055

DC link current

 

 

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

 

 

  • Basic Line Module

A

894

1025

1202

1512

1714

1550

  • Active Line Module

A

805

922

1080

1361

1544

1403

  • Base-load current IL DC 4)
    when supplied from

 

 

 

 

 

 

 

  • Basic Line Module

A

871

1000

1170

1474

1670

1525

  • Active Line Module

A

784

898

1051

1326

1500

1405

  • Base-load current IH DC 5)
    when supplied from

 

 

 

 

 

 

 

  • Basic Line Module

A

795

853

1048

1345

1532

1676

  • Active Line Module

A

716

767

942

1211

1377

1403

Current demand

 

 

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

1.6

1.6

1.46

1.46

1.46

1.46

DC link capacitance

?F

17400

17400

21000

29000

29000

21000

Pulse frequency 6)

 

 

 

 

 

 

 

  • Rated frequency

kHz

1.25

1.25

1.25

1.25

1.25

2

  • Pulse frequency, max.

 

 

 

 

 

 

 

  • Without current derating

kHz

1.25

1.25

1.25

1.25

1.25

2

  • With current derating

kHz

7.5

7.5

7.5

7.5

7.5

4

Power loss, max. 7)

 

 

 

 

 

 

 

  • At 50 Hz 400 V

kW

5.1

5.75

7.9

9.15

10.2

10.9

  • At 60 Hz 460 V

kW

5.61

6.33

8.55

10.05

11.2

12.3

  • Dissipated to ambient air

kW

0.2

0.23

0.44

0.56

0.62

0.65

Coolant volume flow 8)

l/min

16

16

27

27

27

27

Liquid volume

of the integrated heat exchanger

dm3

0.74

0.74

1.56

1.56

1.56

1.56

Pressure drop, typ. 9)

for volume flow

Pa

70000

70000

70000

70000

70000

70000

Heat exchanger material

 

Aluminum

Aluminum

Aluminum

Aluminum

Aluminum

Aluminum

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

54

54

56

56

56

56

DC link connection

DCP, DCN

 

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

Motor connection

U2, V2, W2

 

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

  • Conductor cross section, max. (IEC)

mm2

4 ? 185

4 ? 185

4 ? 240

4 ? 240

4 ? 240

4 ? 240

PE/GND connection

 

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

  • Conductor cross section, max. (IEC)

mm2

4 ? 185

4 ? 185

Busbar

Busbar

Busbar

Busbar

Cable length, max. 10)

 

 

 

 

 

 

 

  • Shielded

m (ft)

300 (984)

300 (984)

300 (984)

300 (984)

300 (984)

300 (984)

  • Unshielded

m (ft)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

Dimensions

 

 

 

 

 

 

 

  • Width

mm (in)

265 (10.4)

265 (10.4)

295 (11.6)

295 (11.6)

295 (11.6)

295 (11.6)

  • Height

mm (in)

1002 (39.5)

1002 (39.5)

1516 (59.7)

1516 (59.7)

1516 (59.7)

1516 (59.7)

  • Depth

mm (in)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

Weight, approx.

kg (lb)

110 (243)

110 (243)

220 (485)

220 (485)

220 (485)

230 (507)

Frame size

 

HXL

HXL

JXL

JXL

JXL

JXL



1) This Motor Module has been specifically designed for loads demanding a high dynamic performance. The derating factor kIGBT and the derating characteristics can be ignored (see section “Duty cycles” in the SINAMICS Low Voltage Engineering Manual).

2) Rated output of a typical 6?pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.

3) Rated output of a typical 6?pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.

4) The base-load current IL is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.

5) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

6) Additional notes regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

7) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.

8) The value applies to coolants comprising water and a mixture of water and anti-freeze agent.

9)The value is valid for water as coolant. Additional information and notes on other coolants is provided in the SINAMICS Low Voltage Engineering Manual.

10) Sum of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

Line voltage 500 ... 690 V 3 AC
DC link voltage 675 ... 1035 V DC

Motor Modules

 

6SL3325-1TG31-0AA3

6SL3325-1TG31-5AA3

6SL3325-1TG32-2AA3

6SL3325-1TG33-3AA3

6SL3325-1TG34-7AA3

6SL3325-1TG35-8AA3

Type rating

 

 

 

 

 

 

 

  • At IL (50 Hz 690 V) 1)

kW

90

132

200

315

450

560

  • At IH (50 Hz 690 V) 1)

kW

75

110

160

250

400

450

  • At IL (50 Hz 500 V) 1)

kW

55

90

132

200

315

400

  • At IH (50 Hz 500 V) 1)

kW

55

90

132

200

250

315

  • At IL (60 Hz 575 V) 2)

hp

75

150

200

300

450

600

  • At IH (60 Hz 575 V) 2)

hp

75

125

200

250

450

500

Output current

 

 

 

 

 

 

 

  • Rated current Irated O

A

100

150

215

330

465

575

  • Base-load current IL3)

A

95

142

208

320

452

560

  • Base-load current IH4)

A

89

134

192

280

416

514

  • Maximum current Imax O

A

142

213

312

480

678

840

DC link current

 

 

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

 

 

  • Basic Line Module

A

122

183

263

403

558

702

  • Active Line Module

A

110

165

237

363

502

632

  • Base-load current IL DC 3)
    when supplied via

 

 

 

 

 

 

 

  • Basic Line Module

A

116

173

253

390

544

683

  • Active Line Module

A

105

156

229

352

489

616

  • Base-load current IH DC 4)
    when supplied from

 

 

 

 

 

 

 

  • Basic Line Module

A

108

163

234

341

496

627

  • Active Line Module

A

98

147

211

308

446

565

Current demand

 

 

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

1.0

1.0

1.5

1.5

1.6

1.6

DC link capacitance

?F

2800

2800

4200

5800

9670

9670

Pulse frequency 5)

 

 

 

 

 

 

 

  • Rated frequency

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • Pulse frequency, max.

 

 

 

 

 

 

 

  • Without current derating

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

7.5

7.5

Power loss, max. 6)

 

 

 

 

 

 

 

  • At 50 Hz 690 V

kW

1.15

1.64

2.34

3.38

5.44

5.61

  • At 60 Hz 575 V

kW

1.02

1.45

2.05

2.96

5.1

5.45

  • Dissipated to ambient air

kW

0.06

0.07

0.09

0.12

0.14

0.16

Coolant volume flow 7)

l/min

9

9

12

12

16

16

Liquid volume

of the integrated heat exchanger

dm3

0.31

0.31

0.91

0.91

0.74

0.74

Pressure drop, typ. 8)

for volume flow

Pa

70000

70000

70000

70000

70000

70000

Heat exchanger material

 

Stainless steel

Stainless steel

Stainless steel

Stainless steel

Aluminum

Aluminum

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

52

52

52

52

54

54

DC link connection

DCP, DCN

 

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

Motor connection

U2, V2, W2

 

Hole for M12

Hole for M12

Hole for M12

Hole for M12

2 ? hole for M12

2 ? hole for M12

  • Conductor cross section, max. (IEC)

mm2

2 ? 95

2 ? 95

4 ? 240

4 ? 240

4 ? 185

4 ? 185

PE/GND connection

 

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

  • Conductor cross section, max. (IEC)

mm2

2 ? 95

2 ? 95

2 ? 240

2 ? 240

4 ? 185

4 ? 185

Cable length, max. 9)

 

 

 

 

 

 

 

  • Shielded

m (ft)

300 (984)

300 (984)

300 (984)

300 (984)

300 (984)

300 (984)

  • Unshielded

m (ft)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

Dimensions

 

 

 

 

 

 

 

  • Width

mm (in)

150 (5.91)

150 (5.91)

150 (5.91)

150 (5.91)

265 (10.4)

265 (10.4)

  • Height

mm (in)

728 (28.7)

728 (28.7)

1172 (46.1)

1172 (46.1)

1002 (39.5)

1002 (39.5)

  • Depth

mm (in)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

Weight, approx.

kg (lb)

41 (90)

41 (90)

80 (176)

80 (176)

110 (243)

110 (243)

Frame size

 

FXL

FXL

GXL

GXL

HXL

HXL



1) Rated output of a typical 6?pole standard induction motor based on IL or IH for 500 V or 690 V 3 AC 50 Hz.

2) Rated output of a typical 6?pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

3) The base-load current IL is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5)Additional notes regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

6) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.

7) The value applies to coolants comprising water and a mixture of water and anti-freeze agent.

8) The value is valid for water as coolant. Additional information and notes on other coolants is provided in the SINAMICS Low Voltage Engineering Manual.

9) Total of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

Line voltage 500 ... 690 V 3 AC
DC link voltage 675 ... 1035 V DC

Motor Modules

 

6SL3325-1TG37-4AA3

6SL3325-1TG38-0AA3 1)

6SL3325-1TG38-1AA3

6SL3325-1TG41-0AA3

6SL3325-1TG41-3AA3

6SL3325-1TG41-6AA3

Type rating

 

 

 

 

 

 

 

  • At IL (50 Hz 690 V) 2)

kW

710

800

800

1000

1200

1500

  • At IH (50 Hz 690 V) 2)

kW

630

710

710

900

1000

1260

  • At IL (50 Hz 500 V) 2)

kW

500

560

560

710

900

1000

  • At IH (50 Hz 500 V) 2)

kW

450

500

560

630

800

900

  • At IL (60 Hz 575 V) 3)

hp

700

800

800

1000

1250

1500

  • At IH (60 Hz 575 V) 3)

hp

700

700

700

900

1000

1250

Output current

 

 

 

 

 

 

 

  • Rated current Irated O

A

735

810

810

1025

1270

1560

  • Base-load current IL5)

A

710

790

790

1000

1230

1500

  • Base-load current I 5)

A

657

724

724

917

1136

1284

  • Maximum current Imax O

A

1065

1185

1185

1500

1845

2055

DC link current

 

 

 

 

 

 

 

  • Rated current Irated DC
    when supplied via

 

 

 

 

 

 

 

  • Basic Line Module

A

903

990

990

1250

1550

1903

  • Active Line Module

A

759

891

891

1125

1395

1605

  • Base-load current IL DC 4)
    when supplied from

 

 

 

 

 

 

 

  • Basic Line Module

A

870

948

963

1219

1500

1800

  • Active Line Module

A

781

870

869

1100

1353

1650

  • Base-load current IH DC 5)
    when supplied from

 

 

 

 

 

 

 

  • Basic Line Module

A

795

885

883

1118

1384

1680

  • Active Line Module

A

732

808

796

1009

1250

1550

Current demand

 

 

 

 

 

 

 

  • 24 V DC auxiliary power supply

A

1.6

1.6

1.46

1.46

1.46

1.46

DC link capacitance

?F

10500

10500

14000

16000

19330

21000

Pulse frequency 6)

 

 

 

 

 

 

 

  • Rated frequency

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • Pulse frequency, max.

 

 

 

 

 

 

 

  • Without current derating

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

7.5

7.5

Power loss, max. 6)

 

 

 

 

 

 

 

  • At 50 Hz 690 V

kW

7.65

8.47

9.56

10.87

13.49

17.9

  • At 60 Hz 575 V

kW

6.67

7.39

8.34

9.55

11.84

15.7

  • Dissipated to ambient air

kW

0.2

0.22

0.43

0.53

0.57

0.78

Coolant volume flow 8)

l/min

16

16

27

27

27

27

Liquid volume

of the integrated heat exchanger

dm3

0.74

0.74

1.56

1.56

1.56

1.56

Pressure drop, typ. 9)

for volume flow

Pa

70000

70000

70000

70000

70000

70000

Heat exchanger material

 

Aluminum

Aluminum

Aluminum

Aluminum

Aluminum

Aluminum

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

54

54

56

56

56

56

DC link connection

DCP, DCN

 

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

2 ? hole for M12

Busbar

Motor connection

U2, V2, W2

 

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

  • Conductor cross section, max. (IEC)

mm2

4 ? 185

4 x 185

Busbar

Busbar

Busbar

Busbar

PE/GND connection

 

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

2 ? hole for M12

  • Conductor cross section, max. (IEC)

mm2

4 ? 185

4 ? 185

Busbar

Busbar

Busbar

Busbar

Cable length, max. 10)

 

 

 

 

 

 

 

  • Shielded

m (ft)

300 (984)

300 (984)

300 (984)

300 (984)

300 (984)

300 (984)

  • Unshielded

m (ft)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

Dimensions

 

 

 

 

 

 

 

  • Width

mm (in)

265 (10.4)

265 (10.4)

295 (11.6)

295 (11.6)

295 (11.6)

295 (11.6)

  • Height

mm (in)

1002 (39.5)

1002 (39.5)

1516 (59.7)

1516 (59.7)

1516 (59.7)

1516 (59.7)

  • Depth

mm (in)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

545 (21.5)

Weight, approx.

kg (lb)

110 (243)

110 (243)

220 (485)

220 (485)

220 (485)

230 (507)

Frame size

 

HXL

HXL

JXL

JXL

JXL

JXL



1) The device is optimized for a base pulse frequency of 1.25 kHz, for an increased pulse frequency – or for certain overloads the derating factor is higher than that for the device with article number 6SL3325?1TG38?1AAx.

2) Rated output of a typical 6?pole standard induction motor based on IL or IH for 500 V or 690 V 3 AC 50 Hz.

3) Rated output of a typical 6?pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

4) The base-load current IL is based on a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.

5) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

6)Additional notes regarding the correlation between the pulse frequency and maximum output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.

7) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. To ensure safe dissipation of the minor power loss released to the ambient air, it is important to follow the instructions pertaining to control cabinet installation in the SINAMICS Low Voltage Engineering Manual.

8) The value applies to coolants comprising water and a mixture of water and anti-freeze agent.

9) The value is valid for water as coolant. Additional information and notes on other coolants is provided in the SINAMICS Low Voltage Engineering Manual.

10) Sum of all motor cables. Longer cable lengths for specific configurations are available on request. For additional information, please refer to the SINAMICS Low Voltage Engineering Manual.

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ

  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà