General information | | | |
Product type designation | DQ 4x24VDC/2A ST | DQ 8x24VDC/0.5A ST | DQ 16x24VDC/0.5A ST |
Product function | | | |
| Yes | | Yes |
Engineering with | | | |
| V11 SP2 with HSP0024 / - | | V11 SP2 with HSP0024 / - |
| V5.5 SP2 with GSD file / - | | V5.5 SP2 with GSD file / - |
Supply voltage | | | |
Type of supply voltage | DC | | DC |
Rated value (DC) | 24 V | 24 V | 24 V |
Reverse polarity protection | Yes | | Yes |
Digital outputs | | | |
Number of digital outputs | 4; > +60 °C number of simultaneously controllable outputs max. 2 x 0.25 A or max. 4 x 0.125 A, max. total current 0.5 A | 8; > +60 °C max. total current 1.0 A | 16; > +60 °C max. total current 1.0 A |
Short-circuit protection | Yes | | Yes |
Limitation of inductive shutdown voltage to | Typ. L+ (-50 V) | Typ. L+ (-50 V) | Typ. L+ (-50 V) |
Controlling a digital input | Yes | Yes | Yes |
Switching capacity of the outputs | | | |
| 2 A | 0.5 A | 0.5 A |
| 10 W | 5 W | 5 W |
Load resistance range | | | |
| 12 ? | 48 ? | 48 ? |
| 3 400 ? | 12 k? | 12 k? |
Output current | | | |
| 2 A | 0.5 A | 0.5 A |
| 0.1 mA | | 0.1 mA |
Output delay with resistive load | | | |
| 50 µs | 50 µs | 50 µs |
| 100 µs | 100 µs | 100 µs |
Parallel switching of two outputs | | | |
| No | No | No |
| Yes | Yes | Yes |
Switching frequency | | | |
| 100 Hz | 100 Hz | 100 Hz |
| 2 Hz | 2 Hz | 2 Hz |
| 10 Hz | 10 Hz | 10 Hz |
Total current of the outputs | | | |
| 8 A | | 8 A |
Cable length | | | |
| 1 000 m | 1 000 m | 1 000 m |
| 200 m | 200 m | 200 m |
Isochronous mode | | | |
Isochronous operation (application synchronized up to terminal) | Yes | | Yes |
Interrupts/diagnostics/status information | | | |
Substitute values connectable | Yes | | Yes |
Alarms | | | |
| Yes | | Yes |
Diagnostic messages | | | |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| Yes | Yes | Yes |
| | Yes | |
Diagnostics indication LED | | | |
| Yes; green PWR LED | | Yes; green PWR LED |
| Yes; Green LED | | Yes; Green LED |
| Yes; green/red DIAG LED | | Yes; green/red DIAG LED |
Potential separation | | | |
Potential separation channels | | | |
| Yes | | Yes |
Isolation | | | |
Isolation tested with | 707 V DC | 707 V DC | 707 V DC |
Highest safety class achievable in safety mode | | | |
| d | | d |
| 2 | | 2 |
Ambient conditions | | | |
Ambient temperature during operation | | | |
| -40 °C; = Tmin; Startup @ -25 °C | -40 °C; = Tmin; Startup @ -25 °C | -40 °C; = Tmin; Startup @ -25 °C |
| 70 °C; = Tmax; > +60 °C number of simultaneously controllable outputs max. 2 x 0.25 A or max. 4 x 0.125 A, max. total current 0.5 A | 70 °C; = Tmax; > +60 °C max. total current 1.0 A | 70 °C; = Tmax; > +60 °C max. total current 1.0 A |
| -40 °C; = Tmin; Startup @ -25 °C | -40 °C; = Tmin; Startup @ -25 °C | -40 °C; = Tmin; Startup @ -25 °C |
| 50 °C; = Tmax | 50 °C; = Tmax | 50 °C; = Tmax |
Extended ambient conditions | | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Dimensions | | | |
Width | 15 mm | 15 mm | 15 mm |
Height | | 73 mm | |
Depth | | 58 mm | |
Weights | | | |
Weight, approx. | 30 g | 28 g | 28 g |