Degree of protection | IP20 |
Mounting | Wall-mounting, side-by-side mounting, push-through mounting for FSB, FSC, FSD and FSE |
Ambient temperature | |
| -10 ... 40 °C (14 ... 104 °F) without derating 40 ... 60 °C (104 ... 140 °F) with derating |
| -40 ... +70 °C (-40 ... +158 °F) |
Relative humidity | 95 % (non-condensing) |
Cooling | |
- FSAA, FSAB, FSA up to 0.75 kW
| Convection cooling |
| Power electronics cooled using heat sinks with external fan |
Installation altitude | Up to 4000 m above sea level 1000 ... 4000 m: output current derating 2000 ... 4000 m: input voltage derating |
Motor cable length | |
| |
| 50 m |
| 100 m |
| |
| 10 m for converters FSA with integrated line filter category C3; to achieve 25 m shielded motor cable length also with FSA, unfiltered converters with external line filter have to be used. |
| 25 m |
| 50 m |
- Longer motor cables with an additional output reactor
| |
| Shielded and unshielded cable: 200 m |
| Shielded and unshielded cable: 150 m for FSA to FSD Shielded cable: 200 m for FSE Unshielded cable: 300 m for FSE |
Vibratory load | |
| 5 ... 9 Hz: 3.5 mm deflection 9 ... 200 Hz: 1 g vibration Vibration class: 2M3 transportation |
| Operational area IIa 10 ... 58 Hz: 0.075 mm deflection 58 ... 200 Hz: 1 g vibration |
Shock load | |
| Operational area II Peak acceleration: 5 g Duration of shock: 30 ms |
Dimensions depending on frame size FS | FSAA without fan | FSAB without fan | FSA without fan | FSA with 1 fan | FSB with 1 fan | FSC with 1 fan | FSD with 2 fans | FSE with 2 fans |
| 68 (2.68) | 68 (2.68) | 90 (3.54) | 90 (3.54) | 140 (5.52) | 184 (7.24) | 240 (9.45) | 245 (9.65) |
| 142 (5.59) | 142 (5.59) | 150 (5.91) | 166 (6.54) | 160 (6.3) | 182 (7.17) | 206.5 (8.13) | 264.5 (10.41) |
| 107.8 (4.24) | 127.8 (5.03) | 145.5 (5.73) | 145.5 (5.73) | 164.5 (6.48) | 169 (6.65) | 172.5 (6.79) | 209 (8.23) |
Weight, approx. | FSAA without fan | FSAB without fan | FSA without fan | FSA with 1 fan | FSB with 1 fan | FSC with 1 fan | FSD with 2 fans | FSE with 2 fans |
| | | | | | | | |
- Without integrated line filter
| 0.6 kg | 0.8 kg | – | – | 1.6 kg | 2.5 kg | – | – |
- With integrated line filter category C1
| 0.7 kg | 0.9 kg | – | – | – | – | – | – |
- With integrated line filter category C2
| – | – | – | – | 1.8 kg | 2.8 kg | – | – |
| | | | | | | | |
- Without integrated line filter
| – | – | 0.9 kg | 1.0 kg | 1.6 kg | 2.4 kg | 3.9 kg | 6.4 kg |
- With integrated line filter category C3
| – | – | 1.0 kg | 1.1 kg | 1.8 kg | 2.6 kg | 4.3 kg | 7.0 kg |
Mounting clearance, minimum | |
| 100 mm (3.94 in) |
| 100 mm (3.94 in) 85 mm (3.35 in) for fan-cooled FSA |
| 0 mm (0 in) |
Compliance with standards | cULus, CE, RCM, KC |
Environmental classes | Pollution class: 3S2 Gas class: 3C2 (SO2, H2S) Climate class: 3K3 |
CE marking, according to | European Low Voltage Directive (EN 61800?5?1 /EN 60204-1) and European EMC Directive (EN 61800?3) |
UL marking, according to | UL508C |
EMC standards, radiated emissions and disturbance voltage (conducted emissions) | |
- EN 61800?3 category C1, 1st environment (residential, commercial)
| 230 V 1 AC, FSAA and FSAB with integrated line filter, or unfiltered with external line filter, shielded cables ? 5 m |
- EN 61800?3 category C2, 1st environment (residential, commercial)
| - 230 V 1 AC, FSB and FSC with integrated line filter, shielded cables ? 25 m
- 400 V 3 AC without integrated line filter with external line filter,
shielded cables FSA *) to FSE ? 25 m
|
- EN 61800?3 category C3, 2nd environment (industrial)
| - 400 V 3 AC with integrated line filter,
shielded cables FSA ? 10 m, FSB to FSD ? 25 m, FSE ? 50 m
|
Note | The EMC product standard EN 61800?3 does not directly refer to a frequency converter, but to a PDS (Power Drive System), that covers beside the converter the whole circuiting as well as the motor and cables. The converters themselves are in general not subject to marking in accordance with the EMC directive. |