Siemens
ÑÐÅÄÑÒÂÀ ÏÐÎÌÛØËÅÍÍÎÉ ÀÂÒÎÌÀÒÈÇÀÖÈÈ
îôèöèàëüíûé ïàðòíåð Ñèìåíñ
Êàòàëîã ÑÀ01 2017
àðõèâíûé
(4872) 700-366
skenergo@mail.ru

Power Modules
General technical specifications

Power Modules

PM230

PM240?2

PM240

PM250

System operating voltage

380 ... 480 V 3 AC ±10 %

FSA to FSC:
200 … 240 V 1 AC/3 AC ±10 %
380 … 480 V 3 AC ±10 %

FSD to FSF:
200 ... 240 V 3 AC -20 % ... +10 %
380 ... 480 V 3 AC -20 % ... +10 %
500 ... 690 V 3 AC -20 % .... +10 %

380 ... 480 V 3 AC ±10 %

380 ... 480 V 3 AC ±10 %

Grid requirement
Short-circuit power RSC

>100

>25

200 V: With RSC >50 it is advisable for FSA to FSC to install a line reactor, or alternatively, to select a Power Module with the next-higher power rating.

400 V: With RSC >100 it is advisable to install a line reactor, or alternatively, to select a Power Module with the next-higher power rating.

>25

A line reactor is recommended with RSC >100

>100

Input frequency

47 ... 63 Hz

Output frequency

 

  • Control mode V/f

0 ... 550 Hz

  • Control type Vector

0 ... 240 Hz

Pulse frequency

4 kHz

For higher pulse frequencies, see derating data

200 V: 4 kHz

400 V: 2 kHz

690 V: 2 kHz

For higher pulse frequencies, see derating data

2 kHz

For higher pulse frequencies, see derating data

4 kHz

For higher pulse frequencies, see derating data

Power factor ?

0.9

0.7

FSD to FSF:
- 200 V and 400 V: 0.95
- 690 V: 0.9

0.7 ... 0.85

0.9

Offset factor cos ?

0.95

FSA to FSC: 0.95

FSD to FSF: 0.99

0.95

0.95 capacitive

Inverter efficiency

86 ... 98 %

92 ... 95 %

95 ... 98 %

95 ... 97 %

Output voltage, max.

In % of input voltage

95%

95%

95%

87%

Overload capability

 

  • Low overload
    (LO)

Note:

When the overload capability is used, the base-load current IL is not reduced.

FSA to FSC:
1.5 ? base-load current IL (i.e. 150 % overload) for 3 s plus 1.1 ? base-load current IL (i.e. 110 % overload) for 57 s within a cycle time of 300 s

FSD to FSF:
1.1 ? base-load current IL (i.e. 110 % overload) for 60 s within a cycle time of 300 s

1.5 ? base-load current IL (i.e. 150 % overload) for 3 s plus 1.1 ? base-load current IL (i.e. 110 % overload) for 57 s within a cycle time of 300 s

90 kW (LO):
1.5 ? base-load current IL (i. e. 150 % overload) for 3 s plus 1.1 ? base-load current IL (i. e. 110 % overload) for 57 s within a cycle time of 300 s

110 kW and higher (LO):
1.5 ? base-load current IL (i. e. 150 % overload) for 1 s plus 1.1 ? base-load current IL (i. e. 110 % overload) for 59 s within a cycle time of 300 s

1.5 ? base-load current IL (i.e. 150 % overload) for 3 s plus 1.1 ? base-load current IL (i.e. 110 % overload) for 57 s within a cycle time of 300 s

  • High overload
    (HO)

Note:

When the overload capability is used, the base-load current IH is not reduced.

FSA to FSC:
2 ? base-load current IH (i.e. 200 % overload) for 3 s plus 1.5 ? base-load current IH (i.e. 150 % overload) for 57 s within a cycle time of 300 s

FSD to FSF:
1.5 ? base-load current IH (i.e. 150 % overload) for 60 s within a cycle time of 300 s

2 ? base-load current IH (i.e. 200 % overload) for 3 s plus 1.5 ? base-load current IH (i.e. 150 % overload) for 57 s within a cycle time of 300 s

Up to 75 kW (HO):
2 ? base-load current IH (i. e. 200 % overload) for 3 s plus 1.5 ? base-load current IH (i. e. 150 % overload) for 57 s within a cycle time of 300 s

90 kW and higher (HO):
1.6 ? base-load current IH (i.e. 160 % overload) for 3 s plus 1.36 ? base-load current IH (i.e. 136 % overload) for 57 s within a cycle time of 300 s

2 ? base-load current IH (i.e. 200 % overload) for 3 s plus 1.5 ? base-load current IH (i.e. 150 % overload) for 57 s within a cycle time of 300 s

Possible braking methods

DC braking

Compound braking

DC braking

Compound braking

Dynamic braking with integrated braking chopper

DC braking

Compound braking

Dynamic braking with integrated braking chopper (optional for frame size FSGX)

Regenerative feedback in generator mode

Degree of protection

IP20 (standard or push-through)

IP20 (standard or push-through)

IP20

IP20

Operating temperature

 

  • Low overload
    (LO)

Frame sizes FSA to FSC:
-10 ... +40 °C (14 ... 104 °F) without derating
>40 ... 60 °C (>104 ... 140 °F) see derating characteristics

Frame sizes FSD to FSF:
0 ... 40 °C (32 … 104 °F) without derating
>40 ... 60 °C (>104 ... 140 °F) see derating characteristics

Frame sizes FSA to FSC:
-10 ... +40 °C (14 ... 104 °F) without derating
>40 ... 60 °C (>104 ... 140 °F) see derating characteristics

Frame sizes FSD to FSF:
-20 ... +40 °C (-4 ... +104 °F) without derating
>40 ... 60 °C (>104 ... 140 °F) see derating characteristics

Frame sizes FSD to FSF:
0 ... 40 °C (32 … 104 °F) without derating
>40 ... 60 °C (>104 ... 140 °F) see derating characteristics

Frame size FSGX:
0 ... 40 °C (32 ... 104 °F) without derating
>40 ... 55 °C (>104 ... 131 °F) see derating characteristics

0 ... 40 °C (32 ... 104 °F) without derating
>40 ... 60 °C (>104 ... 140 °F) see derating characteristics

  • High overload
    (HO)

Frame sizes FSA to FSC:
-10 ... +50 °C (14 ... 122 °F) without derating
>50 ... 60 °C (>122 ... 140 °F) see derating characteristics

Frame sizes FSD to FSF:
0 ... 50 °C (32 ... 122 °F) without derating
>50 ... 60 °C (>122 ... 140 °F) see derating characteristics

Frame sizes FSA to FSC:
-10 ... +50 °C (14 ... 122 °F) without derating
>50 ... 60 °C (>122 ... 140 °F) see derating characteristics

Frame sizes FSD to FSF:
-20 ... +50 °C (-4 ... +122 °F) without derating
>50 ... 60 °C (>122 ... 140 °F) see derating characteristics

Frame sizes FSD to FSF:
0 ... 50 °C (32 ... 122 °F) without derating
>50 ... 60 °C (>122 ... 140 °F) see derating characteristics

Frame size FSGX:
0 ... 40 °C (32 ... 104 °F) without derating
>40 ... 55 °C (>104 ... 131 °F) see derating characteristics

0 ... 50 °C (32 ... 122 °F) without derating
>50 ... 60 °C (>122 ... 140 °F) see derating characteristics

Storage temperature

-40 ... +70 °C (-40 ... +158 °F)

Relative humidity

<95 % RH, condensation not permissible

Cooling

Power units with increased air cooling using integrated fans

Internal air cooling, power units with increased air cooling by built-in fans

Internal air cooling, power units with increased air cooling by built-in fans

Internal air cooling, power units with increased air cooling by built-in fans

Installation altitude

Up to 1000 m (3281 ft.) above sea level without derating,
> 1000 m (3281 ft.) see derating characteristics

Protection functions

  • Undervoltage
  • Overvoltage
  • Overload
  • Ground fault
  • Short-circuit
  • Stall protection
  • Motor blocking protection
  • Motor overtemperature
  • Inverter overtemperature
  • Parameter locking

Short-Circuit Current Rating SCCR

according to UL
(Short Circuit Current Rating) 1)

IP20 degree of protection: 65 kA

200 V: 65 kA

400 V: 65 kA

690 V: 65 kA

65 kA

FSC: 40 kA

FSD to FSF: 42 kA

Compliance with standards

UL, cUL 2), CE, C-Tick (RCM), SEMI F47

FSA ... FSC: UL, cUL, CE, C-Tick (RCM), SEMI F47

FSD … FSF: UL, cUL, CE, C-Tick (RCM), SEMI F47, KCC, WEEE, RoHS, EAC

UL, cUL, CE, C-Tick (RCM), SEMI F47

UL 3), cUL 3), CE, C-Tick (RCM), SEMI F47

CE marking

According to Low-Voltage Directive 2006/95/EC, EMC Directive 2004/108/EC



1) Applies to industrial control panel installations to NEC article 409 or UL 508A.

2) Applies to PM230 Power Modules, frame sizes FSA to FSC.

3) Applies to all PM250 Power Modules with integrated line filter class A.

PM230 Power Modules degree of protection IP20 standard variant

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 standard variant

Without integrated line filter

6SL3210-1NE11-3UL1

6SL3210-1NE11-7UL1

6SL3210-1NE12-2UL1

6SL3210-1NE13-1UL1

6SL3210-1NE14-1UL1

With integrated line filter class A

6SL3210-1NE11-3AL1

6SL3210-1NE11-7AL1

6SL3210-1NE12-2AL1

6SL3210-1NE13-1AL1

6SL3210-1NE14-1AL1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated 1)

A

1.3

1.7

2.2

3.1

4.1

  • Base-load current IL1)

A

1.3

1.7

2.2

3.1

4.1

  • Base-load current IH2)

A

0.9

1.3

1.7

2.2

3.1

  • Maximum current Imax

A

2

2.6

3.4

4.7

6.2

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

0.37 (0.5)

0.55 (0.75)

0.75 (1)

1.1 (1.5)

1.5 (2)

  • Based on IH

kW (hp)

0.25 (0.34)

0.37 (0.5)

0.55 (0.75)

0.75 (1)

1.1 (1.5)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

%

89

93

93

94

95

Power loss 3)

At rated current

kW

0.031

0.034

0.041

0.049

0.06

Cooling air requirement

m3/s (ft3/s)

0.002 (0.07)

0.002 (0.07)

0.005 (0.18)

0.005 (0.18)

0.005 (0.18)

Sound pressure level

LpA (1 m)

dB

<50

<50

<50

<50

<50

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

1.3

1.8

2.3

3.2

4.2

  • Based on IH

A

0.9

1.3

1.8

2.3

3.2

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

73 (2.87)

73 (2.87)

73 (2.87)

73 (2.87)

73 (2.87)

  • Height

mm (in)

196 (7.72)

196 (7.72)

196 (7.72)

196 (7.72)

196 (7.72)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

  • With operator panel, max.

mm (in)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

Frame size

 

FSA

FSA

FSA

FSA

FSA

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

  • With integrated line filter

kg (lb)

1.6 (3.53)

1.6 (3.53)

1.6 (3.53)

1.6 (3.53)

1.6 (3.53)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800?3 Category C2. With unshielded cables, Category C2 is not achieved.

 

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 standard variant

Without integrated line filter

6SL3210-1NE15-8UL1

6SL3210-1NE17-7UL1

6SL3210-1NE21-0UL1

6SL3210-1NE21-3UL1

6SL3210-1NE21-8UL1

With integrated line filter class A

6SL3210-1NE15-8AL1

6SL3210-1NE17-7AL1

6SL3210-1NE21-0AL1

6SL3210-1NE21-3AL1

6SL3210-1NE21-8AL1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated 1)

A

5.9

7.7

10.2

13.2

18

  • Base-load current IL1)

A

5.9

7.7

10.2

13.2

18

  • Base-load current IH2)

A

4.1

5.9

7.7

10.2

13.2

  • Maximum current Imax

A

8.9

11.8

15.4

20.4

27

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

2.2 (3)

3 (4)

4 (5)

5.5 (7.5)

7.5 (10)

  • Based on IH

kW (hp)

1.5 (2)

2.2 (3)

3 (4)

4 (5)

5.5 (7.5)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

%

96

96

97

97

97

Power loss 3)

At rated current

kW

0.078

0.102

0.13

0.165

0.224

Cooling air requirement

m3/s (ft3/s)

0.005 (0.18)

0.005 (0.18)

0.009 (0.32)

0.009 (0.32)

0.009 (0.32)

Sound pressure level

LpA (1 m)

dB

<50

<50

<62

<62

<62

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

6.1

8

11

14

19

  • Based on IH

A

4.2

6.1

8

11

14

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 2.5

1.5 ... 6

1.5 ... 6

1.5 ... 6

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 2.5

1.5 ... 6

1.5 ... 6

1.5 ... 6

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

73 (2.87)

73 (2.87)

100 (3.94)

100 (3.94)

100 (3.94)

  • Height

mm (in)

196 (7.72)

196 (7.72)

292 (11.5)

292 (11.5)

292 (11.5)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

  • With operator panel, max.

mm (in)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

245 (9.65)

Frame size

 

FSA

FSA

FSB

FSB

FSB

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

1.4 (3.09)

1.4 (3.09)

2.8 (6.17)

2.8 (6.17)

2.8 (6.17)

  • With integrated line filter

kg (lb)

1.6 (3.53)

1.6 (3.53)

3 (4.02)

3 (4.02)

3 (4.02)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800?3 Category C2. With unshielded cables, Category C2 is not achieved.

 

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 standard variant

Without integrated line filter

6SL3210-
1NE22-6UL1

6SL3210-
1NE23-2UL1

6SL3210-
1NE23-8UL1

6SL3210-
1NE24-5UL0

6SL3210-
1NE26-0UL0

With integrated line filter class A

6SL3210-
1NE22-6AL1

6SL3210-
1NE23-2AL1

6SL3210-
1NE23-8AL1

6SL3210-
1NE24-5AL0

6SL3210-
1NE26-0AL0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated 1)

A

26

32

38

45

60

  • Base-load current IL1)

A

26

32

38

45

60

  • Base-load current IH2)

A

18

26

32

38

45

  • Maximum current Imax

A

39

52

64

57

67

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

11 (10)

15 (15)

18.5 (20)

22 (25)

30 (30)

  • Based on IH

kW (hp)

7.5 (10)

11 (10)

15 (15)

18.5 (20)

22 (25)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

%

97

97

98

98

97

Power loss 3)

At rated current

kW

0.291

0.355

0.423

0.539

0.726

Cooling air requirement

m3/s (ft3/s)

0.019 (0.7)

0.019 (0.7)

0.019 (0.7)

0.08 (2.8)

0.08 (2.8)

Sound pressure level

LpA (1 m)

dB

<65

<65

<65

<60

<60

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

27

33

39

42

56

  • Based on IH

A

19

27

33

36

42

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

6 ... 16

6 ... 16

6 ... 16

16 ... 35

16 ... 35

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

6 ... 16

6 ... 16

6 ... 16

16 ... 35

16 ... 35

Motor cable length, max. 5)

 

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

140 (5.51)

140 (5.51)

140 (5.51)

275 (10.83)

275 (10.83)

  • Height

 

 

 

 

 

 

  • Without integrated line filter

mm (in)

355 (13.98)

355 (13.98)

355 (13.98)

419 (16.50)

419 (16.50)

  • With integrated line filter

mm (in)

355 (13.98)

355 (13.98)

355 (13.98)

512 (20.16)

512 (20.16)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

204 (8.03)

204 (8.03)

  • With operator panel, max.

mm (in)

245 (9.65)

245 (9.65)

245 (9.65)

275 (10.83)

275 (10.83)

Frame size

 

FSC

FSC

FSC

FSD

FSD

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

4.5 (9.92)

4.5 (9.92)

4.5 (9.92)

11 (24.3)

11 (24.3)

  • With integrated line filter

kg (lb)

5.1 (11.3)

5.1 (11.3)

5.1 (11.3)

14 (30.9)

14 (30.9)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800?3 Category C2. With unshielded cables, Category C2 is not achieved.

 

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 standard variant

Without integrated line filter

6SL3210-1NE27-5UL0

6SL3210-1NE28-8UL0

6SL3210-1NE31-1UL0

6SL3210-1NE31-5UL0

With integrated line filter class A

6SL3210-1NE27-5AL0

6SL3210-1NE28-8AL0

6SL3210-1NE31-1AL0

6SL3210-1NE31-5AL0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

  • Rated current Irated 1)

A

75

90

110

145

  • Base-load current IL1)

A

75

90

110

145

  • Base-load current IH2)

A

60

75

90

110

  • Maximum current Imax

A

90

112

135

165

Rated power

 

 

 

 

 

  • Based on IL

kW (hp)

37 (40)

45 (50)

55 (60)

75 (75)

  • Based on IH

kW (hp)

30 (30)

37 (40)

45 (50)

55 (60)

Rated pulse frequency

kHz

4

4

4

4

Efficiency ?

%

97

97

97

97

Power loss 3)

At rated current

kW

0.791

0.976

1.237

1.69

Cooling air requirement

m3/s (ft3/s)

0.08 (2.8)

0.08 (2.8)

0.15 (5.3)

0.15 (5.3)

Sound pressure level

LpA (1 m)

dB

<60

<60

<60

<60

24 V DC power supply

for Control Unit

A

1

1

1

1

Input current 4)

 

 

 

 

 

  • Rated current

A

70

84

102

135

  • Based on IH

A

56

70

84

102

Line supply connection

U1/L1, V1/L2, W1/L3

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section

mm2

25 ... 50

25 ... 50

35 ... 120

35 ... 120

Motor connection

U2, V2, W2

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section

mm2

25 ... 50

25 ... 50

35 ... 120

35 ... 120

Motor cable length, max. 5)

 

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

  • Width

mm (in)

275 (10.83)

275 (10.83)

350 (13.78)

350 (13.78)

  • Height

 

 

 

 

 

  • Without integrated line filter

mm (in)

499 (19.65)

499 (19.65)

634 (24.96)

634 (24.96)

  • With integrated line filter

mm (in)

635 (25.0)

635 (25.0)

934 (36.77)

934 (36.77)

  • Depth

 

 

 

 

 

  • Without operator panel

mm (in)

204 (8.03)

204 (8.03)

316 (12.44)

316 (12.44)

  • With operator panel, max.

mm (in)

275 (10.83)

275 (10.83)

387 (15.24)

387 (15.24)

Frame size

 

FSE

FSE

FSF

FSF

Weight, approx.

 

 

 

 

 

  • Without integrated line filter

kg (lb)

15 (33.1)

15 (33.1)

34 (75)

34 (75)

  • With integrated line filter

kg (lb)

22 (48.5)

22 (48.5)

46 (101)

46 (101)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800?3 Category C2. With unshielded cables, Category C2 is not achieved.

 

PM230 Power Modules degree of protection IP20 push-through variant

Line voltage 380 ... 480 V 3 AC

PM230 Power Modules degree of protection IP20 push-through variant

Without integrated line filter

6SL3211-1NE17-7UL1

6SL3211-1NE21-8UL1

6SL3211-1NE23-8UL1

With integrated line filter class A

6SL3211-1NE17-7AL1

6SL3211-1NE21-8AL1

6SL3211-1NE23-8AL1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

  • Rated current Irated 1)

A

7.7

18

38

  • Base-load current IL1)

A

7.7

18

38

  • Base-load current IH2)

A

5.9

13.2

32

  • Maximum current Imax

A

11.8

27

64

Rated power

 

 

 

 

  • Based on IL

kW (hp)

3 (4)

7.5 (10)

18.5 (20)

  • Based on IH

kW (hp)

2.2 (3)

5.5 (7.5)

15 (15)

Rated pulse frequency

kHz

4

4

4

Efficiency ?

%

96

97

98

Power loss 3)

At rated current

kW

0.102

0.224

0.423

Cooling air requirement

m3/s (ft3/s)

0.005 (0.18)

0.009 (0.32)

0.019 (0.7)

Sound pressure level

LpA (1 m)

dB

<56

<62

<65

24 V DC power supply

for Control Unit

A

1

1

1

Input current 4)

 

 

 

 

  • Rated current

A

8

19

39

  • Based on IH

A

6.1

14

33

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

4 ... 6

6 ... 16

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1 ... 2.5

4 ... 6

10 ... 16

Motor cable length, max. 5)

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

Dimensions

 

 

 

 

  • Width

mm (in)

126 (4.96)

154 (6.06)

200 (7.87)

  • Height

mm (in)

238 (9.37)

345 (13.58)

411 (16.18)

  • Depth

 

 

 

 

  • Without operator panel

mm (in)

171 (6.73)

171 (6.73)

171 (6.73)

  • With operator panel, max.

mm (in)

251 (9.88)

251 (9.88)

251 (9.88)

Frame size

 

FSA

FSB

FSC

Weight, approx.

With integrated line filter

 

 

 

 

  • Without integrated line filter

kg (lb)

1.7 (3.75)

3.4 (7.50)

5.4 (11.9)

  • With integrated line filter

kg (lb)

1.9 (4.19)

3.6 (7.94)

6 (13.2)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82 ft) (shielded) for PM230 Power Modules with integrated line filter to maintain the limit values acc. to EN 61800?3 Category C2. With unshielded cables, Category C2 is not achieved.

 

PM240?2 Power Modules standard variant

Line voltage 200 ... 240 V 1 AC/3 AC

PM240?2 Power Modules standard variant

Without integrated line filter

6SL3210-1PB13-0UL0

6SL3210-1PB13-8UL0

6SL3210-1PB15-5UL0

6SL3210-1PB17-4UL0

6SL3210-1PB21-0UL0

With integrated line filter class A

6SL3210-1PB13-0AL0

6SL3210-1PB13-8AL0

6SL3210-1PB15-5AL0

6SL3210-1PB17-4AL0

6SL3210-1PB21-0AL0

Output current

at 50 Hz 230 V 1 AC

 

 

 

 

 

 

  • Rated current Irated 1)

A

3.2

4.2

6

7.4

10.4

  • Base-load current IL1)

A

3.2

4.2

6

7.4

10.4

  • Base-load current IH2)

A

2.3

3.2

4.2

6

7.4

  • Maximum current Imax

A

4.8

6.4

9

12

15.6

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

0.55 (0.75)

0.75 (1)

1.1 (1.5)

1.5 (2)

2.2 (3)

  • Based on IH

kW (hp)

0.37 (0.5)

0.55 (0.75)

0.75 (1)

1.1 (1.5)

1.5 (2)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

%

>96

>96

>96

>96

>96

Power loss 3)

At rated current

kW

0.04

0.04

0.05

0.07

0.12

Cooling air requirement

m3/s (ft3/s)

0.005 (0.18)

0.005 (0.18)

0.0092 (0.325)

0.0092 (0.325)

0.0092 (0.325)

Sound pressure level

LpA (1 m)

dB

<50

<50

<62

<62

<62

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current 1 AC/3 AC

A

7.5/4.3

9.6/5.5

13.5/7.8

18.1/10.5

24/13.9

  • Based on IH 1 AC/3 AC

A

6.6/3.8

8.4/4.8

11.8/6.8

15.8/9.1

20.9/12.1

Line supply connection

U1/L1, V1/L2, W1/L3

 

Terminal connector

Terminal connector

Terminal connector

Terminal connector

Terminal connector

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 2.5

1.5 ... 6

1.5 ... 6

1.5 ... 6

Motor connection

U2, V2, W2

 

Terminal connector

Terminal connector

Terminal connector

Terminal connector

Terminal connector

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 2.5

1.5 ... 6

1.5 ... 6

1.5 ... 6

PE connection

 

Included in terminal connector

Included in terminal connector

Included in terminal connector

Included in terminal connector

Included in terminal connector

Motor cable length, max.

 

 

 

 

 

 

  • Shielded

m (ft)

50 (164)

50 (164)

50 (164)

50 (164)

50 (164)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

73 (2.87)

73 (2.87)

100 (3.94)

100 (3.94)

100 (3.94)

  • Height

mm (in)

196 (7.72)

196 (7.72)

291 (11.46)

291 (11.46)

291 (11.46)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

  • With operator panel, max.

mm (in)

248 (9.76)

248 (9.76)

248 (9.76)

248 (9.76)

248 (9.76)

Frame size

 

FSA

FSA

FSB

FSB

FSB

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

1.4 (3.09)

1.4 (3.09)

2.9 (6.39)

2.9 (6.39)

2.9 (6.39)

  • With integrated line filter

kg (lb)

1.6 (3.53)

1.6 (3.53)

3.1 (6.84)

3.1 (6.84)

3.1 (6.84)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on Irated) for a line impedance corresponding to uK = 1 %. The current values are specified on the rating plate of the Power Module.

 

Line voltage 200 ... 240 V 1 AC/3 AC

PM240?2 Power Modules standard variant

Without integrated line filter

6SL3210-1PB21-4UL0

6SL3210-1PB21-8UL0

With integrated line filter class A

6SL3210-1PB21-4AL0

6SL3210-1PB21-8AL0

Output current

at 50 Hz 230 V 1 AC

 

 

 

  • Rated current Irated 1)

A

13.6

17.5

  • Base-load current IL1)

A

13.6

17.5

  • Base-load current IH2)

A

10.4

13.6

  • Maximum current Imax

A

20.8

27.2

Rated power

 

 

 

  • Based on IL

kW (hp)

3 (4)

4 (5)

  • Based on IH

kW (hp)

2.2 (3)

3 (4)

Rated pulse frequency

kHz

4

4

Efficiency ?

%

>96

>96

Power loss 3)

At rated current

kW

0.14

0.18

Cooling air requirement

m3/s (ft3/s)

0.0185 (0.65)

0.0185 (0.65)

Sound pressure level

LpA (1 m)

dB

<65

<65

24 V DC power supply

for Control Unit

A

1

1

Input current 4)

 

 

 

  • Rated current 1 AC/3 AC

A

35.9/20.7

43/24.8

  • Based on IH 1 AC/3 AC

A

31.3/18.1

37.5/21.7

Line supply connection

U1/L1, V1/L2, W1/L3

 

Terminal connector

Terminal connector

  • Conductor cross-section

mm2

6 ... 16

6 ... 16

Motor connection

U2, V2, W2

 

Terminal connector

Terminal connector

  • Conductor cross-section

mm2

6 ... 16

6 ... 16

PE connection

 

Included in terminal connector

Included in terminal connector

Motor cable length, max.

 

 

 

  • Shielded

m (ft)

50 (164)

50 (164)

  • Unshielded

m (ft)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

Dimensions

 

 

 

  • Width

mm (in)

140 (5.51)

140 (5.51)

  • Height

mm (in)

355 (13.98)

355 (13.98)

  • Depth

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

  • With operator panel, max.

mm (in)

248 (9.76)

248 (9.76)

Frame size

 

FSC

FSC

Weight, approx.

 

 

 

  • Without integrated line filter

kg (lb)

5 (11)

5 (11)

  • With integrated line filter

kg (lb)

5.2 (11.5)

5.2 (11.5)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on Irated) for a line impedance corresponding to uK = 1 %. The current values are specified on the rating plate of the Power Module.

 

Line voltage 200 ... 240 V 3 AC

PM240?2 Power Modules standard variant

Without integrated line filter

6SL3210-1PC22-2UL0

6SL3210-1PC22-8UL0

6SL3210-1PC24-2UL0

6SL3210-1PC25-4UL0

6SL3210-1PC26-8UL0

With integrated line filter class A

6SL3210-1PC22-2AL0

6SL3210-1PC22-8AL0

Output current

at 50 Hz 230 V 3 AC

 

 

 

 

 

 

  • Rated current Irated 1)

A

22

28

42

54

68

  • Base-load current IL1)

A

22

28

42

54

68

  • Base-load current IH2)

A

17.5

22

35

42

54

  • Maximum current Imax

A

35

44

70

84

108

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

5.5 (7.5)

7.5 (10)

11 (10)

15 (15)

18.5 (20)

  • Based on IH

kW (hp)

4 (5)

5.5 (7.5)

7.5 (10)

11 (10)

15 (15)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

%

>97

>97

>97

>97

>97

Power loss 3)

At rated current

kW

0.2

0.26

0.42

0.57

0.76

Cooling air requirement

m3/s (ft3/s)

0.0185 (0.65)

0.0185 (0.65)

0.055 (1.9)

0.055 (1.9)

0.055 (1.9)

Sound pressure level

LpA (1 m)

dB

<65

<65

45 ... 65 4)

45 ... 65 4)

45 ... 65 4)

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 5)

 

 

 

 

 

 

  • Rated current

A

29

37

40

51

64

  • Based on IH

A

26.2

33

36

43

56

Line supply connection

U1/L1, V1/L2, W1/L3

 

Terminal connector

Terminal connector

Screw-type terminals

Screw-type terminals

Screw-type terminals

  • Conductor cross-section

mm2

6 ... 16

6 ... 16

10 ... 35

10 ... 35

10 ... 35

Motor connection

U2, V2, W2

 

Terminal connector

Terminal connector

Screw-type terminals

Screw-type terminals

Screw-type terminals

  • Conductor cross-section

mm2

6 ... 16

6 ... 16

10 ... 35

10 ... 35

10 ... 35

PE connection

 

Included in terminal connector

Included in terminal connector

Screw-type terminals

Screw-type terminals

Screw-type terminals

Motor cable length, max.

 

 

 

 

 

 

  • Shielded

m (ft)

50 (164)

50 (164)

200 (656)

200 (656)

200 (656)

  • Unshielded

m (ft)

100 (328)

100 (328)

300 (984)

300 (984)

300 (984)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

140 (5.51)

140 (5.51)

200 (7.87)

200 (7.87)

200 (7.87)

  • Height

mm (in)

355 (13.98)

355 (13.98)

472 (18.58)

472 (18.58)

472 (18.58)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

237 (9.33)

237 (9.33)

237 (9.33)

  • With operator panel, max.

mm (in)

248 (9.76)

248 (9.76)

278 (10.94)

278 (10.94)

278 (10.94)

Frame size

 

FSC

FSC

FSD

FSD

FSD

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

5 (11)

5 (11)

17 (37.5)

17 (37.5)

17 (37.5)

  • With integrated line filter

kg (lb)

5.2 (11.5)

5.2 (11.5)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) Values dependent on ambient temperature and utilization.

5) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on Irated) for a line impedance corresponding to uK = 1%. The current values are specified on the rating plate of the Power Module.

 

Line voltage 200 ... 240 V 3 AC

PM240?2 Power Modules standard variant

Without integrated line filter

6SL3210-1PC28-0UL0

6SL3210-1PC31-1UL0

6SL3210-1PC31-3UL0

6SL3210-1PC31-6UL0

6SL3210-1PC31-8UL0

With integrated line filter class A

Output current

at 50 Hz 230 V 3 AC

 

 

 

 

 

 

  • Rated current Irated 1)

A

80

104

130

154

178

  • Base-load current IL1)

A

80

104

130

154

178

  • Base-load current IH2)

A

68

80

104

130

154

  • Maximum current Imax

A

136

160

208

260

308

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

22 (25)

30 (30)

37 (40)

45 (50)

55 (60)

  • Based on IH

kW (hp)

18.5 (20)

22 (25)

30 (30)

37 (40)

45 (50)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

%

>97

>97

>97

>97

>97

Power loss 3)

At rated current

kW

0.85

1.2

1.3

1.63

1.98

Cooling air requirement

m3/s (ft3/s)

0.083 (2.9)

0.083 (2.9)

0.153 (5.4)

0.153 (5.4)

0.153 (5.4)

Sound pressure level

LpA (1 m)

dB

44 ... 62 4)

44 ... 62 4)

56 ... 68 4)

56 ... 68 4)

56 ... 68 4)

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 5)

 

 

 

 

 

 

  • Rated current

A

76

98

126

149

172

  • Based on IH

A

71

83

110

138

164

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals

Screw-type terminals

M10 screw stud

M10 screw stud

M10 screw stud

  • Conductor cross-section

mm2

25 ... 70

25 ... 70

35 ... 2 ? 120

35 ... 2 ? 120

35 ... 2 ? 120

Motor connection

U2, V2, W2

 

Screw-type terminals

Screw-type terminals

M10 screw stud

M10 screw stud

M10 screw stud

  • Conductor cross-section

mm2

25 ... 70

25 ... 70

35 ... 2 ? 120

35 ... 2 ? 120

35 ... 2 ? 120

PE connection

 

Screw-type terminals

Screw-type terminals

M10 screw stud

M10 screw stud

M10 screw stud

Motor cable length, max.

 

 

 

 

 

 

  • Shielded

m (ft)

200 (656)

200 (656)

300 (984)

300 (984)

300 (984)

  • Unshielded

m (ft)

300 (984)

300 (984)

450 (1476)

450 (1476)

450 (1476)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

275 (10.83)

275 (10.83)

305 (12.01)

305 (12.01)

305 (12.01)

  • Height

mm (in)

551 (21.69)

551 (21.69)

708 (27.87)

708 (27.87)

708 (27.87)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

237 (9.33)

237 (9.33)

357 (14.06)

357 (14.06)

357 (14.06)

  • With operator panel, max.

mm (in)

278 (10.94)

278 (10.94)

398 (15.67)

398 (15.67)

398 (15.67)

Frame size

 

FSE

FSE

FSF

FSF

FSF

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

26 (57.3)

26 (57.3)

57 (126)

57 (126)

57 (126)

  • With integrated line filter

kg (lb)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) Values dependent on ambient temperature and utilization.

5) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on Irated) for a line impedance corresponding to uK = 1 %. The current values are specified on the rating plate of the Power Module.

 

Line voltage 380 ... 480 V 3 AC

PM240?2 Power Modules standard variant

Without integrated line filter

6SL3210-1PE11-8UL1

6SL3210-1PE12-3UL1

6SL3210-1PE13-2UL1

6SL3210-1PE14-3UL1

6SL3210-1PE16-1UL1

6SL3210-1PE18-0UL1

With integrated line filter class A

6SL3210-1PE11-8AL1

6SL3210-1PE12-3AL1

6SL3210-1PE13-2AL1

6SL3210-1PE14-3AL1

6SL3210-1PE16-1AL1

6SL3210-1PE18-0AL1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

 

  • Rated current Irated 1)

A

1.7

2.2

3.1

4.1

5.9

7.7

  • Base-load current IL1)

A

1.7

2.2

3.1

4.1

5.9

7.7

  • Base-load current IH2)

A

1.3

1.7

2.2

3.1

4.1

5.9

  • Maximum current Imax

A

2.6

3.4

4.7

6.2

8.9

11.8

Rated power

 

 

 

 

 

 

 

  • Based on IL

kW (hp)

0.55 (0.75)

0.75 (1)

1.1 (1.5)

1.5 (2)

2.2 (3)

3 (4)

  • Based on IH

kW (hp)

0.37 (0.5)

0.55 (0.75)

0.75 (1)

1.1 (1.5)

1.5 (2)

2.2 (3)

Rated pulse frequency

kHz

4

4

4

4

4

4

Efficiency ?

%

>96

>96

>96

>96

>96

>96

Power loss 3)

At rated current

kW

0.033

0.038

0.048

0.061

0.085

0.113

Cooling air requirement

m3/s (ft3/s)

0.005 (0.18)

0.005 (0.18)

0.005 (0.18)

0.005 (0.18)

0.005 (0.18)

0.005 (0.18)

Sound pressure level

LpA (1 m)

dB

<50

<50

<50

<50

<50

<50

24 V DC power supply

for Control Unit

A

1

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

 

  • Rated current

A

2.3

2.9

4.1

5.5

7.7

10.1

  • Based on IH

A

2

2.6

3.3

4.7

6.1

8.8

Line supply connection

U1/L1, V1/L2, W1/L3

 

Terminal connector

Terminal connector

Terminal connector

Terminal connector

Terminal connector

Terminal connector

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

Motor connection

U2, V2, W2

 

Terminal connector

Terminal connector

Terminal connector

Terminal connector

Terminal connector

Terminal connector

  • Conductor cross-section

mm2

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

1 ... 2.5

PE connection

 

Included in terminal connector

Included in terminal connector

Included in terminal connector

Included in terminal connector

Included in terminal connector

Included in terminal connector

Motor cable length, max.

 

 

 

 

 

 

 

  • Without filter, shielded/unshielded

m (ft)

150/150 (492/492)

150/150 (492/492)

150/150 (492/492)

150/150 (492/492)

150/150 (492/492)

150/150 (492/492)

  • With integrated filter class A, shielded/unshielded

m (ft)

50/100 (164/328)

50/100 (164/328)

50/100 (164/328)

50/100 (164/328)

50/100 (164/328)

50/100 (164/328)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

 

  • Width

mm (in)

73 (2.87)

73 (2.87)

73 (2.87)

73 (2.87)

73 (2.87)

73 (2.87)

  • Height

mm (in)

196 (7.72)

196 (7.72)

196 (7.72)

196 (7.72)

196 (7.72)

196 (7.72)

  • Depth

 

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

  • With operator panel, max.

mm (in)

248 (9.76)

248 (9.76)

248 (9.76)

248 (9.76)

248 (9.76)

248 (9.76)

Frame size

 

FSA

FSA

FSA

FSA

FSA

FSA

Weight, approx.

 

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

1.4 (3.09)

  • With integrated line filter

kg (lb)

1.5 (3.31)

1.5 (3.31)

1.5 (3.31)

1.5 (3.31)

1.5 (3.31)

1.5 (3.31)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on Irated) for a line impedance corresponding to uK = 1 %. The current values are specified on the rating plate of the Power Module.

 

Line voltage 380 ... 480 V 3 AC

PM240?2 Power Modules standard variant

Without integrated line filter

6SL3210-1PE21-1UL0

6SL3210-1PE21-4UL0

6SL3210-1PE21-8UL0

6SL3210-1PE22-7UL0

6SL3210-1PE23-3UL0

With integrated line filter class A

6SL3210-1PE21-1AL0

6SL3210-1PE21-4AL0

6SL3210-1PE21-8AL0

6SL3210-1PE22-7AL0

6SL3210-1PE23-3AL0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated 1)

A

10.2

13.2

18

26

32

  • Base-load current IL1)

A

10.2

13.2

18

26

32

  • Base-load current IH2)

A

7.7

10.2

13.2

18

26

  • Maximum current Imax

A

15.4

20.4

27

39

52

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

4 (5)

5.5 (7.5)

7.5 (10)

11 (10)

15 (15)

  • Based on IH

kW (hp)

3 (4)

4 (5)

5.5 (7.5)

7.5 (10)

11 (10)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

%

>97

>97

>97

>97

>97

Power loss 3)

At rated current

kW

0.14

0.184

0.239

0.333

0.385

Cooling air requirement

m3/s (ft3/s)

0.0092 (0.325)

0.0092 (0.325)

0.0092 (0.325)

0.0185 (0.65)

0.0185 (0.65)

Sound pressure level

LpA (1 m)

dB

<62

<62

<62

<65

<65

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

13.3

17.2

22.2

32.6

39.9

  • Based on IH

A

11.6

15.3

19.8

27

36

Line supply connection

U1/L1, V1/L2, W1/L3

 

Terminal connector

Terminal connector

Terminal connector

Terminal connector

Terminal connector

  • Conductor cross-section

mm2

1.5 ... 6

1.5 ... 6

1.5 ... 6

6 ... 16

6 ... 16

Motor connection

U2, V2, W2

 

Terminal connector

Terminal connector

Terminal connector

Terminal connector

Terminal connector

  • Conductor cross-section

mm2

1.5 ... 6

1.5 ... 6

1.5 ... 6

6 ... 16

6 ... 16

PE connection

 

Included in terminal connector

Included in terminal connector

Included in terminal connector

Included in terminal connector

Included in terminal connector

Motor cable length, max.

 

 

 

 

 

 

  • Without filter, shielded/unshielded

m (ft)

150/150 (492/492)

150/150 (492/492)

150/150 (492/492)

150/150 (492/492)

150/150 (492/492)

  • With integrated filter class A, shielded/unshielded

m (ft)

100/100 (328/328) 5)

100/100 (328/328) 5)

100/100 (328/328) 5)

150/150 (492/492) 5)

150/150 (492/492) 5)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

100 (3.94)

100 (3.94)

100 (3.94)

140 (5.51)

140 (5.51)

  • Height

mm (in)

291 (11.46)

291 (11.46)

291 (11.46)

355 (13.98)

355 (13.98)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

165 (6.50)

  • With operator panel, max.

mm (in)

248 (9.76)

248 (9.76)

248 (9.76)

248 (9.76)

248 (9.76)

Frame size

 

FSB

FSB

FSB

FSC

FSC

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

2.9 (6.39)

2.9 (6.39)

3 (6.62)

4.7 (10.4)

4.8 (10.6)

  • With integrated line filter

kg (lb)

3.1 (6.84)

3.1 (6.84)

3.2 (7.06)

5.3 (11.7)

5.4 (11.9)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on Irated) for a line impedance corresponding to uK = 1 %. The current values are specified on the rating plate of the Power Module.

5) The values apply with low-capacitance CY cables - the max. permissible motor cable length is 50 m (164 ft) (shielded) as standard.

 

Line voltage 380 ... 480 V 3 AC

PM240?2 Power Modules standard variant

Without integrated line filter

6SL3210-1PE23-8UL0

6SL3210-1PE24-5UL0

6SL3210-1PE26-0UL0

6SL3210-1PE27-5UL0

6SL3210-1PE28-8UL0

6SL3210-1PE31-1UL0

With integrated line filter class A

6SL3210-1PE23-8AL0

6SL3210-1PE24-5AL0

6SL3210-1PE26-0AL0

6SL3210-1PE27-5AL0

6SL3210-1PE28-8AL0

6SL3210-1PE31-1AL0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

 

  • Rated current Irated 1)

A

38

45

60

75

90

110

  • Base-load current IL1)

A

38

45

60

75

90

110

  • Base-load current IH2)

A

32

38

45

60

75

90

  • Maximum current Imax

A

64

76

90

120

150

180

Rated power

 

 

 

 

 

 

 

  • Based on IL

kW (hp)

18.5 (20)

22 (25)

30 (30)

37 (40)

45 (50)

55 (60)

  • Based on IH

kW (hp)

15 (15)

18.5 (20)

22 (25)

30 (30)

37 (40)

45 (50)

Rated pulse frequency

kHz

4

4

4

4

4

4

Efficiency ?

%

>97

>97

>97

>97

>97

>97

Power loss 3)

At rated current

kW

0.55

0.68

0.76

1.01

1.19

1.54

Cooling air requirement

m3/s (ft3/s)

0.055 (1.9)

0.055 (1.9)

0.055 (1.9)

0.055 (1.9)

0.083 (2.9)

0.083 (2.9)

Sound pressure level

LpA (1 m)

dB

45 ... 65 4)

45 ... 65 4)

45 ... 65 4)

45 ... 65 4)

44 ... 62 4)

44 ... 62 4)

24 V DC power supply

for Control Unit

A

1

1

1

1

1

1

Input current 5)

 

 

 

 

 

 

 

  • Rated current

A

36

42

57

70

86

104

  • Based on IH

A

33

38

47

62

78

94

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

  • Conductor cross-section

mm2

10 ... 35

10 ... 35

10 ... 35

10 ... 35

25 ... 70

25 ... 70

Motor connection

U2, V2, W2

 

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

  • Conductor cross-section

mm2

10 ... 35

10 ... 35

10 ... 35

10 ... 35

25 ... 70

25 ... 70

PE connection

 

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Motor cable length, max.

 

 

 

 

 

 

 

  • Shielded

m (ft)

200 (656)

200 (656)

200 (656)

200 (656)

200 (656)

200 (656)

  • Unshielded

m (ft)

300 (984)

300 (984)

300 (984)

300 (984)

300 (984)

300 (984)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

 

  • Width

mm (in)

200 (7.87)

200 (7.87)

200 (7.87)

200 (7.87)

275 (10.83)

275 (10.83)

  • Height

mm (in)

472 (18.58)

472 (18.58)

472 (18.58)

472 (18.58)

551 (21.69)

551 (21.69)

  • Depth

 

 

 

 

 

 

 

  • Without operator panel

mm (in)

237 (9.33)

237 (9.33)

237 (9.33)

237 (9.33)

237 (9.33)

237 (9.33)

  • With operator panel, max.

mm (in)

278 (10.9)

278 (10.9)

278 (10.9)

278 (10.9)

278 (10.9)

278 (10.9)

Frame size

 

FSD

FSD

FSD

FSD

FSE

FSE

Weight, approx.

 

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

16 (35.3)

16 (35.3)

17 (37.5)

17 (37.5)

26 (57.3)

26 (57.3)

  • With integrated line filter

kg (lb)

17.5 (38.6)

17.5 (38.6)

18.5 (40.8)

18.5 (40.8)

28 (61.7)

28 (61.7)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) Values dependent on ambient temperature and utilization.

5) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on Irated) for a line impedance corresponding to uK = 1%. The current values are specified on the rating plate of the Power Module.

 

Line voltage 380 ... 480 V 3 AC

PM240?2 Power Modules standard variant

Without integrated line filter

6SL3210-1PE31-5UL0

6SL3210-1PE31-8UL0

6SL3210-1PE32-1UL0

6SL3210-1PE32-5UL0

With integrated line filter class A

6SL3210-1PE31-5AL0

6SL3210-1PE31-8AL0

6SL3210-1PE32-1AL0

6SL3210-1PE32-5AL0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

  • Rated current Irated 1)

A

145

178

205

250

  • Base-load current IL1)

A

145

178

205

250

  • Base-load current IH2)

A

110

145

178

205

  • Maximum current Imax

A

220

290

356

410

Rated power

 

 

 

 

 

  • Based on IL

kW (hp)

75 (75)

90 (100)

110 (100)

132 (125)

  • Based on IH

kW (hp)

55 (60)

75 (75)

90 (100)

110 (100)

Rated pulse frequency

kHz

4

4

2

2

Efficiency ?

%

>97

>97

>97

>97

Power loss 3)

At rated current

kW

1.78

2.31

2.14

2.81

Cooling air requirement

m3/s (ft3/s)

0.153 (5.4)

0.153 (5.4)

0.153 (5.4)

0.153 (5.4)

Sound pressure level

LpA (1 m)

dB

56 ... 68 4)

56 ... 68 4)

56 ... 68 4)

56 ... 68 4)

24 V DC power supply

for Control Unit

A

1

1

1

1

Input current 5)

 

 

 

 

 

  • Rated current

A

140

172

198

242

  • Based on IH

A

117

154

189

218

Line supply connection

U1/L1, V1/L2, W1/L3

 

M10 screw stud

M10 screw stud

M10 screw stud

M10 screw stud

  • Conductor cross-section

mm2

35 ... 2 ? 120

35 ... 2 ? 120

35 ... 2 ? 120

35 ... 2 ? 120

Motor connection

U2, V2, W2

 

M10 screw stud

M10 screw stud

M10 screw stud

M10 screw stud

  • Conductor cross-section

mm2

35 ... 2 ? 120

35 ... 2 ? 120

35 ... 2 ? 120

35 ... 2 ? 120

PE connection

 

M10 screw stud

M10 screw stud

M10 screw stud

M10 screw stud

Motor cable length, max.

 

 

 

 

 

  • Shielded

m (ft)

300 (984)

300 (984)

300 (984)

300 (984)

  • Unshielded

m (ft)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

Degree of protection

 

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

  • Width

mm (in)

305 (12.01)

305 (12.01)

305 (12.01)

305 (12.01)

  • Height

mm (in)

708 (27.87)

708 (27.87)

708 (27.87)

708 (27.87)

  • Depth

 

 

 

 

 

  • Without operator panel

mm (in)

357 (14.06)

357 (14.06)

357 (14.06)

357 (14.06)

  • With operator panel, max.

mm (in)

398 (15.7)

398 (15.7)

398 (15.7)

398 (15.7)

Frame size

 

FSF

FSF

FSF

FSF

Weight, approx.

 

 

 

 

 

  • Without integrated line filter

kg (lb)

57 (126)

57 (126)

61 (135)

61 (135)

  • With integrated line filter

kg (lb)

63 (139)

63 (139)

65 (143)

65 (143)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) Values dependent on ambient temperature and utilization.

5) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on Irated) for a line impedance corresponding to uK = 1%. The current values are specified on the rating plate of the Power Module.

 

Line voltage 500 ... 690 V 3 AC

PM240?2 Power Modules standard variant

Without integrated line filter

6SL3210-1PH21-4UL0

6SL3210-1PH22-0UL0

6SL3210-1PH22-3UL0

6SL3210-1PH22-7UL0

6SL3210-1PH23-5UL0

6SL3210-1PH24-2UL0

With integrated line filter class A

6SL3210-1PH21-4AL0

6SL3210-1PH22-0AL0

6SL3210-1PH22-3AL0

6SL3210-1PH22-7AL0

6SL3210-1PH23-5AL0

6SL3210-1PH24-2AL0

Output current

at 50 Hz 690 V 3 AC

 

 

 

 

 

 

 

  • Rated current Irated 1)

A

14

19

23

27

35

42

  • Base-load current IL1)

A

14

19

23

27

35

42

  • Base-load current IH2)

A

11

14

19

23

27

35

  • Maximum current Imax

A

22

29

38

46

54

70

Rated power

 

 

 

 

 

 

 

  • Based on IL

kW (hp)

11 (10)

15 (15)

18.5 (20)

22 (25)

30 (30)

37 (40)

  • Based on IH

kW (hp)

7.5 (10)

11 (10)

15 (15)

18.5 (20)

22 (25)

30 (30)

Rated pulse frequency

kHz

4

4

4

4

4

4

Efficiency ?

%

>98

>98

>98

>98

>98

>98

Power loss 3)

At rated current

kW

0.32

0.41

0.48

0.56

0.72

0.88

Cooling air requirement

m3/s (ft3/s)

0.055 (1.9)

0.055 (1.9)

0.055 (1.9)

0.055 (1.9)

0.055 (1.9)

0.055 (1.9)

Sound pressure level

LpA (1 m)

dB

45 ... 65 4)

45 ... 65 4)

45 ... 65 4)

45 ... 65 4)

45 ... 65 4)

45 ... 65 4)

24 V DC power supply

for Control Unit

A

1

1

1

1

1

1

Input current 5)

 

 

 

 

 

 

 

  • Rated current

A

14

18

22

25

33

40

  • Based on IH

A

11

14

20

24

28

36

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

  • Conductor cross-section

mm2

10 ... 35

10 ... 35

10 ... 35

10 ... 35

10 ... 35

10 ... 35

Motor connection

U2, V2, W2

 

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

  • Conductor cross-section

mm2

10 ... 35

10 ... 35

10 ... 35

10 ... 35

10 ... 35

10 ... 35

PE connection

 

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Screw-type terminals

Motor cable length, max.

 

 

 

 

 

 

 

  • Shielded

m (ft)

200 (656)

200 (656)

200 (656)

200 (656)

200 (656)

200 (656)

  • Unshielded

m (ft)

300 (984)

300 (984)

300 (984)

300 (984)

300 (984)

300 (984)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

 

  • Width

mm (in)

200 (7.87)

200 (7.87)

200 (7.87)

200 (7.87)

200 (7.87)

200 (7.87)

  • Height

mm (in)

472 (18.58)

472 (18.58)

472 (18.58)

472 (18.58)

472 (18.58)

472 (18.58)

  • Depth

 

 

 

 

 

 

 

  • Without operator panel

mm (in)

237 (9.33)

237 (9.33)

237 (9.33)

237 (9.33)

237 (9.33)

237 (9.33)

  • With operator panel, max.

mm (in)

278 (10.9)

278 (10.9)

278 (10.9)

278 (10.9)

278 (10.9)

278 (10.9)

Frame size

 

FSD

FSD

FSD

FSD

FSD

FSD

Weight, approx.

 

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

17 (37.5)

17 (37.5)

17 (37.5)

17 (37.5)

17 (37.5)

17 (37.5)

  • With integrated line filter

kg (lb)

18.5 (40.8)

18.5 (40.8)

18.5 (40.8)

18.5 (40.8)

18.5 (40.8)

18.5 (40.8)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) Values dependent on ambient temperature and utilization.

5) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on Irated) for a line impedance corresponding to uK = 1 %. The current values are specified on the rating plate of the Power Module.

 

Line voltage 500 ... 690 V 3 AC

PM240?2 Power Modules standard variant

Without integrated line filter

6SL3210-1PH25-2UL0

6SL3210-1PH26-2UL0

6SL3210-1PH28-0UL0

6SL3210-1PH31-0UL0

6SL3210-1PH31-2UL0

6SL3210-1PH31-4UL0

With integrated line filter class A

6SL3210-1PH25-2AL0

6SL3210-1PH26-2AL0

6SL3210-1PH28-0AL0

6SL3210-1PH31-0AL0

6SL3210-1PH31-2AL0

6SL3210-1PH31-4AL0

Output current

at 50 Hz 690 V 3 AC

 

 

 

 

 

 

 

  • Rated current Irated 1)

A

52

62

80

100

115

142

  • Base-load current IL1)

A

52

62

80

100

115

142

  • Base-load current IH2)

A

42

52

62

80

100

115

  • Maximum current Imax

A

84

104

124

160

200

230

Rated power

 

 

 

 

 

 

 

  • Based on IL

kW (hp)

45 (50)

55 (60)

75 (75)

90 (100)

110 (100)

132 (125)

  • Based on IH

kW (hp)

37 (40)

45 (50)

55 (60)

75 (75)

90 (100)

110 (100)

Rated pulse frequency

kHz

4

4

4

4

2

2

Efficiency ?

%

>98

>98

>98

>98

>98

>98

Power loss 3)

At rated current

kW

1

1.21

1.22

1.55

1.82

2.33

Cooling air requirement

m3/s (ft3/s)

0.083 (2.9)

0.083 (2.9)

0.153 (5.4)

0.153 (5.4)

0.153 (5.4)

0.153 (5.4)

Sound pressure level

LpA (1 m)

dB

44 ... 62 4)

44 ... 62 4)

56 ... 68 4)

56 ... 68 4)

56 ... 68 4)

56 ... 68 4)

24 V DC power supply

for Control Unit

A

1

1

1

1

1

1

Input current 5)

 

 

 

 

 

 

 

  • Rated current

A

50

59

78

97

111

137

  • Based on IH

A

44

54

66

85

106

122

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals

Screw-type terminals

M10 screw stud

M10 screw stud

M10 screw stud

M10 screw stud

  • Conductor cross-section

mm2

25 ... 70

25 ... 70

35 ... 2 ? 120

35 ... 2 ? 120

35 ... 2 ? 120

35 ... 2 ? 120

Motor connection

U2, V2, W2

 

Screw-type terminals

Screw-type terminals

M10 screw stud

M10 screw stud

M10 screw stud

M10 screw stud

  • Conductor cross-section

mm2

25 ... 70

25 ... 70

35 ... 2 ? 120

35 ... 2 ? 120

35 ... 2 ? 120

35 ... 2 ? 120

PE connection

 

Screw-type terminals

Screw-type terminals

M10 screw stud

M10 screw stud

M10 screw stud

M10 screw stud

Motor cable length, max.

 

 

 

 

 

 

 

  • Shielded

m (ft)

200 (656)

200 (656)

300 (984)

300 (984)

300 (984)

300 (984)

  • Unshielded

m (ft)

300 (984)

300 (984)

450 (1476)

450 (1476)

450 (1476)

450 (1476)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

 

  • Width

mm (in)

275 (10.83)

275 (10.83)

305 (12.01)

305 (12.01)

305 (12.01)

305 (12.01)

  • Height

mm (in)

551 (21.69)

551 (21.69)

708 (27.87)

708 (27.87)

708 (27.87)

708 (27.87)

  • Depth

 

 

 

 

 

 

 

  • Without operator panel

mm (in)

237 (9.33)

237 (9.33)

357 (14.06)

357 (14.06)

357 (14.06)

357 (14.06)

  • With operator panel, max.

mm (in)

278 (10.9)

278 (10.9)

398 (15.7)

398 (15.7)

398 (15.7)

398 (15.7)

Frame size

 

FSE

FSE

FSF

FSF

FSF

FSF

Weight, approx.

 

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

26 (57.3)

26 (57.3)

60 (132.3)

60 (132.3)

60 (132.3)

60 (132.3)

  • With integrated line filter

kg (lb)

28 (61.7)

28 (61.7)

64 (141)

64 (141)

64 (141)

64 (141)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) Values dependent on ambient temperature and utilization.

5) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on Irated) for a line impedance corresponding to uK = 1 %. The current values are specified on the rating plate of the Power Module.

 

PM240?2 Power Modules push-through variant

Line voltage 200 ... 240 V 1 AC/3 AC

PM240?2 Power Modules push-through variant

Without integrated line filter

6SL3211-1PB13-8UL0

6SL3211-1PB21-0UL0

6SL3211-1PB21-8UL0

With integrated line filter class A

6SL3211-1PB13-8AL0

6SL3211-1PB21-0AL0

6SL3211-1PB21-8AL0

Output current

At 50 Hz 230 V 1 AC/3 AC

 

 

 

 

  • Rated current Irated 1)

A

4.2

10.4

17.5

  • Base-load current IL1)

A

4.2

10.4

17.5

  • Base-load current IH2)

A

3.2

7.4

13.6

  • Maximum current Imax

A

6.4

15.6

27.2

Rated power

 

 

 

 

  • Based on IL

kW (hp)

0.75 (1)

2.2 (3)

4 (5)

  • Based on IH

kW (hp)

0.55 (0.75)

1.5 (2)

3 (4)

Rated pulse frequency

kHz

4

4

4

Efficiency ?

%

>96

>96

>96

Power loss 3)

At rated current

kW

0.04

0.12

0.18

Cooling air requirement

m3/s (ft3/s)

0.005 (0.18)

0.0092 (0.325)

0.0185 (0.65)

Sound pressure level

LpA (1 m)

dB

<56

<62

<65

24 V DC power supply

for Control Unit

A

1

1

1

Input current 4)

 

 

 

 

  • Rated current 1 AC/3 AC

A

9.6/5.5

24/13.9

43/24.8

  • Based on IH 1 AC/3 AC

A

8.4/4.8

20.9/12.1

37.5/21.7

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 6

6 ... 16

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 6

6 ... 16

Motor cable length, max.

 

 

 

 

  • Shielded

m (ft)

150 (492)

150 (492)

150 (492)

  • Unshielded

m (ft)

150 (492)

150 (492)

150 (492)

Degree of protection

 

IP20

IP20

IP20

Dimensions

 

 

 

 

  • Width

mm (in)

126 (4.96)

154 (6.06)

200 (7.87)

  • Height

mm (in)

238 (9.37)

345 (13.58)

411 (16.18)

  • Depth

 

 

 

 

  • Without operator panel

mm (in)

171 (6.73)

171 (6.73)

171 (6.73)

  • With operator panel, max.

mm (in)

254 (10.00)

254 (10.00)

254 (10.00)

Frame size

 

FSA

FSB

FSC

Weight, approx.

With integrated line filter

 

 

 

 

  • Without integrated line filter

kg (lb)

1.8 (3.97)

3.4 (7.50)

5.8 (12.8)

  • With integrated line filter

kg (lb)

2 (4.41)

3.7 (8.16)

6.3 (13.9)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

 

Line voltage 380 ... 480 V 3 AC

PM240?2 Power Modules push-through variant

Without integrated line filter

6SL3211-1PE18-0UL1

6SL3211-1PE21-8UL0

6SL3211-1PE23-3UL0

With integrated line filter class A

6SL3211-1PE18-0AL1

6SL3211-1PE21-8AL0

6SL3211-1PE23-3AL0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

  • Rated current Irated 1)

A

7.7

18

32

  • Base-load current IL1)

A

7.7

18

32

  • Base-load current IH2)

A

5.9

13.2

26

  • Maximum current Imax

A

11.8

27

52

Rated power

 

 

 

 

  • Based on IL

kW (hp)

3 (4)

7.5 (10)

15 (15)

  • Based on IH

kW

2.2 (3)

5.5 (7.5)

11 (10)

Rated pulse frequency

kHz

4

4

4

Efficiency ?

%

>96

>97

>97

Power loss 3)

At rated current

kW

0.113

0.239

0.385

Cooling air requirement

m3/s (ft3/s)

0.007 (0.2)

0.0092 (0.325)

0.0185 (0.65)

Sound pressure level

LpA (1 m)

dB

<56

<62

<65

24 V DC power supply

for Control Unit

A

1

1

1

Input current 4)

 

 

 

 

  • Rated current

A

10.1

22.2

39.9

  • Based on IH

A

8.8

19.8

36

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 6

6 ... 16

Motor connection

U2, V2, W2

 

Screw-type terminals, plug-in

Screw-type terminals, plug-in

Screw-type terminals, plug-in

  • Conductor cross-section

mm2

1.5 ... 2.5

1.5 ... 6

6 ... 16

Motor cable length, max.

 

 

 

 

  • Without filter, shielded/unshielded

m (ft)

150/150 (492/492)

150/150 (492/492)

150/150 (492/492)

  • With integrated filter class A, shielded/unshielded

m (ft)

50/100 (164/328)

100/100 (328/328) 5)

150/150 (492/492) 5)

Degree of protection

 

IP20

IP20

IP20

Dimensions

 

 

 

 

  • Width

mm (in)

126 (4.96)

154 (6.06)

200 (7.87)

  • Height

mm (in)

238 (9.37)

345 (13.58)

411 (16.18)

  • Depth

 

 

 

 

  • Without operator panel

mm (in)

171 (6.73)

171 (6.73)

171 (6.73)

  • With operator panel, max.

mm (in)

254 (10.00)

254 (10.00)

254 (10.00)

Frame size

 

FSA

FSB

FSC

Weight, approx.

With integrated line filter

 

 

 

 

  • Without integrated line filter

kg (lb)

1.7 (3.75)

3.6 (7.94)

5.8 (12.8)

  • With integrated line filter

kg (lb)

1.8 (3.97)

3.9 (8.60)

6.3 (13.9)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1%. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) The values apply with low-capacitance CY cables - the max. permissible motor cable length is 50 m (164 ft) (shielded) as standard.

 

PM240 Power Modules

Line voltage 380 ... 480 V 3 AC

PM240 Power Modules

Without integrated line filter

6SL3224-0XE41-3UA0

6SL3224-0XE41-6UA0

6SL3224-0XE42-0UA0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

  • Rated current Irated 1)

A

302

370

477

  • Base-load current IL1)

A

302

370

477

  • Base-load current IH2)

A

250

302

370

  • Maximum current Imax

A

400

483

592

Rated power

 

 

 

 

  • Based on IL

kW (hp)

160 (250)

200 (300)

250 (400)

  • Based on IH

kW (hp)

132 (125)

160 (250)

200 (300)

Rated pulse frequency

kHz

2

2

2

Efficiency ?

%

>98

>98

>98

Power loss 3)

At rated current

kW

4.163

4.783

5.911

Cooling air requirement

m3/s (ft3/s)

0.36 (12.7)

0.36 (12.7)

0.36 (12.7)

Sound pressure level

LpA (1 m)

dB

<69

<69

<69

24 V DC power supply

for Control Unit

A

1

1

1

Rated input current 4)

 

 

 

 

  • With line reactor

A

245

297

354

  • Without line reactor

A

297

354

442

Length of cable to braking resistor, max.

m (ft)

50 (164)

50 (164)

50 (164)

Line supply connection

U1/L1, V1/L2, W1/L3

 

M10 screw stud

M10 screw stud

M10 screw stud

  • Conductor cross-section

mm2

2 ? 240

2 ? 240

2 ? 240

Motor connection

U2, V2, W2

 

M10 screw stud

M10 screw stud

M10 screw stud

  • Conductor cross-section

mm2

2 ? 240

2 ? 240

2 ? 240

PE connection

 

On housing with M10 screw

On housing with M10 screw

On housing with M10 screw

Motor cable length 5), max.

 

 

 

 

  • Shielded

m (ft)

200 (656)

200 (656)

200 (656)

  • Unshielded

m (ft)

300 (984)

300 (984)

300 (984)

Degree of protection

 

IP20

IP20

IP20

Dimensions

 

 

 

 

  • Width

mm (in)

326 (12.83)

326 (12.83)

326 (12.83)

  • Height

mm (in)

1533 (60.35)

1533 (60.35)

1533 (60.35)

  • Depth

mm (in)

547 (21.54)

547 (21.54)

547 (21.54)

Frame size

 

FSGX

FSGX

FSGX

Weight, approx.

kg (lb)

174 (384)

174 (384)

174 (384)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance. The input currents apply for a load at rated power (based on Irated) for a line impedance corresponding to uK = 1 %. These current values without line reactor are specified on the rating plate of the Power Module.

5) Max. motor cable length 25 m (82.03 ft) (shielded) for PM240 Power Modules with integrated line filter to maintain the limit values acc.to EN 61800-3 Category C2.

 

PM250 Power Modules

Line voltage 380 ... 480 V 3 AC

PM250 Power Modules

With integrated line filter

6SL3225-0BE25-5AA1

6SL3225-0BE27-5AA1

6SL3225-0BE31-1AA1

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

  • Rated current Irated 1)

A

18

25

32

  • Base-load current IL1)

A

18

25

32

  • Base-load current IH2)

A

13.2

19

26

  • Maximum current Imax

A

26.4

38

52

Rated power

 

 

 

 

  • Based on IL

kW (hp)

7.5 (10)

11 (10)

15 (15)

  • Based on IH

kW (hp)

5.5 (7.5)

7.5 (10)

11 (10)

Rated pulse frequency

kHz

4

4

4

Efficiency ?

%

95

95

95

Power loss 3)

At rated current

kW

0.298

0.488

0.472

Cooling air requirement

m3/s (ft3/s)

0.038 (1.3)

0.038 (1.3)

0.038 (1.3)

Sound pressure level

LpA (1 m)

dB

<60

<60

<60

24 V DC power supply

for Control Unit

A

1

1

1

Input current 4)

 

 

 

 

  • Rated current

A

18

25

32

  • Based on IH

A

13.2

19

26

Line supply connection

U1/L1, V1/L2, W1/L3

 

Screw-type terminals

Screw-type terminals

Screw-type terminals

  • Conductor cross-section

mm2

2.5 ... 10

2.5 ... 10

2.5 ... 10

Motor connection

U2, V2, W2

 

Screw-type terminals

Screw-type terminals

Screw-type terminals

  • Conductor cross-section

mm2

2.5 ... 10

2.5 ... 10

2.5 ... 10

PE connection

 

On housing with M5 screw

On housing with M5 screw

On housing with M5 screw

Motor cable length, max.

 

 

 

 

  • Shielded

m (ft)

25 (82)

25 (82)

25 (82)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

Dimensions

 

 

 

 

  • Width

mm (in)

189 (7.44)

189 (7.44)

189 (7.44)

  • Height

mm (in)

334 (13.15)

334 (13.15)

334 (13.15)

  • Depth

 

 

 

 

  • Without operator panel

mm (in)

185 (7.28)

185 (7.28)

185 (7.28)

  • With operator panel, max.

mm (in)

268 (10.55)

268 (10.55)

268 (10.55)

Frame size

 

FSC

FSC

FSC

Weight, approx.

kg (lb)

7.5 (10)

7.5 (10)

7.5 (10)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

 

Line voltage 380 ... 480 V 3 AC

PM250 Power Modules

Without integrated line filter

6SL3225-0BE31-5UA0

6SL3225-0BE31-8UA0

6SL3225-0BE32-2UA0

With integrated line filter

6SL3225-0BE31-5AA0

6SL3225-0BE31-8AA0

6SL3225-0BE32-2AA0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

  • Rated current Irated 1)

A

38

45

60

  • Base-load current IL1)

A

38

45

60

  • Base-load current IH2)

A

32

38

45

  • Maximum current Imax

A

64

76

90

Rated power

 

 

 

 

  • Based on IL

kW (hp)

18.5 (20)

22 (25)

30 (30)

  • Based on IH

kW (hp)

15 (15)

18.5 (20)

22 (25)

Rated pulse frequency

kHz

4

4

4

Efficiency ?

%

>97

>97

>97

Power loss 3)

At rated current

kW

0.576

0.693

0.918

Cooling air requirement

m3/s (ft3/s)

0.022 (0.8)

0.022 (0.8)

0.039 (1.4)

Sound pressure level

LpA (1 m)

dB

<60

<60

<61

24 V DC power supply

for Control Unit

A

1

1

1

Input current 4)

 

 

 

 

  • Rated current

A

36

42

56

  • Based on IH

A

30

36

42

Line supply connection

U1/L1, V1/L2, W1/L3

 

M6 screw studs

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

10 ... 35

10 ... 35

10 ... 35

Motor connection

U2, V2, W2

 

M6 screw studs

M6 screw studs

M6 screw studs

  • Conductor cross-section

mm2

10 ... 35

10 ... 35

10 ... 35

PE connection

 

On housing with M6 screw

On housing with M6 screw

On housing with M6 screw

Motor cable length 5), max.

 

 

 

 

  • Shielded

m (ft)

50 (164)

50 (164)

50 (164)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

Dimensions

 

 

 

 

  • Width

mm (in)

275 (10.83)

275 (10.83)

275 (10.83)

  • Height

 

 

 

 

  • Without integrated line filter

mm (in)

419 (16.50)

419 (16.50)

419 (16.50)

  • With integrated line filter

mm (in)

512 (20.16)

512 (20.16)

512 (20.16)

  • Depth

 

 

 

 

  • Without operator panel

mm (in)

204 (8.03)

204 (8.03)

204 (8.03)

  • With operator panel, max.

mm (in)

278 (10.94)

278 (10.94)

278 (10.94)

Frame size

 

FSD

FSD

FSD

Weight, approx.

 

 

 

 

  • Without integrated line filter

kg (lb)

13 (28.7)

13 (28.7)

13 (28.7)

  • With integrated line filter

kg (lb)

15 (33.1)

15 (33.1)

16 (35.3)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82.03 ft) (shielded) for PM250 Power Modules with integrated line filter to maintain the limit values of EN 61800-3 Category C2.

 

Line voltage 380 ... 480 V 3 AC

PM250 Power Modules

Without integrated line filter

6SL3225-0BE33-0UA0

6SL3225-0BE33-7UA0

6SL3225-0BE34-5UA0

6SL3225-0BE35-5UA0

6SL3225-0BE37-5UA0

With integrated line filter

6SL3225-0BE33-0AA0

6SL3225-0BE33-7AA0

6SL3225-0BE34-5AA0

6SL3225-0BE35-5AA0

6SL3225-0BE37-5AA0

Output current

at 50 Hz 400 V 3 AC

 

 

 

 

 

 

  • Rated current Irated 1)

A

75

90

110

145

178

  • Base-load current IL1)

A

75

90

110

145

178

  • Base-load current IH2)

A

60

75

90

110

145

  • Maximum current Imax

A

120

150 (492.15)

180

220

290

Rated power

 

 

 

 

 

 

  • Based on IL

kW (hp)

37 (40)

45 (50)

55 (60)

75 (75)

90 (100)

  • Based on IH

kW (hp)

30 (30)

37 (40)

45 (50)

55 (60)

75 (75)

Rated pulse frequency

kHz

4

4

4

4

4

Efficiency ?

%

>97

>97

>97

>97

>97

Power loss 3)

At rated current

kW

1.01

1.217

1.605

2.234

2.638

Cooling air requirement

m3/s (ft3/s)

0.022 (0.8)

0.039 (1.4)

0.094 (3.3)

0.094 (3.3)

0.117 (4.1)

Sound pressure level

LpA (1 m)

dB

<60

<62

<60

<60

<65

24 V DC power supply

for Control Unit

A

1

1

1

1

1

Input current 4)

 

 

 

 

 

 

  • Rated current

A

70

84

102

135

166

  • Based on IH

A

56

70

84

102

135

Line supply connection

U1/L1, V1/L2, W1/L3

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section, max.

mm2

10 ... 50

10 ... 50

25 ... 120

25 ... 120

25 ... 120

Motor connection

U2, V2, W2

 

M6 screw studs

M6 screw studs

M8 screw studs

M8 screw studs

M8 screw studs

  • Conductor cross-section, max.

mm2

10 ... 50

10 ... 50

25 ... 120

25 ... 120

25 ... 120

PE connection

 

On housing with M6 screw

On housing with M6 screw

On housing with M8 screw

On housing with M8 screw

On housing with M8 screw

Motor cable length 5), max.

 

 

 

 

 

 

  • Shielded

m (ft)

50 (164)

50 (164)

50 (164)

50 (164)

50 (164)

  • Unshielded

m (ft)

100 (328)

100 (328)

100 (328)

100 (328)

100 (328)

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

 

 

 

 

 

 

  • Width

mm (in)

275 (10.83)

275 (10.83)

350 (13.78)

350 (13.78)

350 (13.78)

  • Height

 

 

 

 

 

 

  • Without integrated line filter

mm (in)

499 (19.65)

499 (19.65)

634 (24.96)

634 (24.96)

634 (24.96)

  • With integrated line filter

mm (in)

635 (25.0)

635 (25.0)

934 (36.77)

934 (36.77)

934 (36.77)

  • Depth

 

 

 

 

 

 

  • Without operator panel

mm (in)

204 (8.03)

204 (8.03)

316 (12.44)

316 (12.44)

316 (12.44)

  • With operator panel, max.

mm (in)

278 (10.94)

278 (10.94)

390 (15.35)

390 (15.35)

390 (15.35)

Frame size

 

FSE

FSE

FSF

FSF

FSF

Weight, approx.

 

 

 

 

 

 

  • Without integrated line filter

kg (lb)

14 (30.9)

14 (30.9)

35 (77.2)

35 (77.2)

35 (77.2)

  • With integrated line filter

kg (lb)

21 (46.3)

21 (46.3)

51 (112.5)

51 (112.5)

51 (112.5)



1) The rated output current Irated and the base-load current IL are based on the duty cycle for low overload (LO).

2) The base-load current IH is based on the duty cycle for high overload (HO).

3) Typical values. You can find additional information on the Internet at https://support.industry.siemens.com/cs/document/94059311

4) The input current depends on the motor load and line impedance and applies for a line impedance corresponding to uK = 1 %. The rated input currents apply for a load at rated power (based on Irated) – these current values are specified on the rating plate.

5) Max. motor cable length 25 m (82.03 ft) (shielded) for PM250 Power Modules with integrated line filter to maintain the limit values of EN 61800-3 Category C2.

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ

  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà