Technology function
Functions specific to pumps, fans and compressors are already integrated, e.g.:
Automatic restart Application restart after a power failure or fault occurrence
Flying restart Connection of the inverter when the motor is running
Flux reduction Automatic adaptation of the motor current to the prevailing load conditions in U/f control mode (ECO mode) as well as in sensorless vector control mode
Cascade connection Load-dependent connection and disconnection of a maximum of three additional motors by the inverter in order to provide a largely constant output power (implemented by means of an additional external circuit)
Sleep mode Startup or shutdown of the drive when the relevant value drops below an external setpoint or the internal PID controller setpoint
4 integrated PID controllers One PID controller for controlling the drive speed as a function of pressure, temperature, flowrate, fill level, air quality and other process variables, and a further three PID controllers with freely configurable outputs, e.g. for controlling valves (heating, cooling) or flaps
Emergency mode Special inverter operating mode that enhances the availability of the drive system in the event of a fire
Multi-zone controller
Closed-loop control of a zone with up to 3 sensors for pressure or temperature, or
Closed-loop control of two independent zones, each with one sensor
Bypass mode When the setpoint is reached or a fault occurs, the system changes over to line operation (implemented by means of an additional external circuit)
Programmable time switches
Real-time clock For time-dependent process controls, e.g. to reduce the temperature of a heating control at night and with automatic daylight saving/standard time switchover
Freely programmable logical function blocks For simulating simple PLC functions