Converter cabinet units

The most important directives and standards are listed below. These are used as basis for the SINAMICS S150 converter cabinet units and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation.

European directives

2006/95/EC

Low Voltage Directive:
Directive of the European Parliament and Council of December 12, 2006, on the approximation of the laws of the member states relating to electrical equipment designed for use within certain voltage limits

2004/108/EC

EMC Directive:
Directive of the European Parliament and Council of December 15, 2004, which repeals directive 89/336/EEC, on the approximation of laws of the member states relating to electromagnetic compatibility

2006/42/EC

Machinery Directive:
Directive of the European Parliament and Council of May 17, 2006, on machinery and amending Directive 95/16/EC (recast).

European standards

EN ISO 3744

Acoustics – Determination of the sound power level and sound energy level for noise sources that result from sound pressure measurements – envelope surface procedure of the accuracy class 2 for a largely free sound field over a reflecting plane

EN ISO 13849?1

Safety of machinery – safety-related parts of control systems;
Part 1: General design guidelines (ISO 13849-1: 2006)

EN 60146?1?1

Semiconductor converters – General requirements and line-commutated converters
Part 1?1: Specification of basic requirements

EN 60204?1

Safety of machinery – Electrical equipment of machines;
Part 1: General requirements

EN 60529

Degrees of protection provided by enclosures (IP code)

EN 61508?1

Functional safety of electrical/electronic/programmable electronic safety-related systems
Part 1: General requirements

EN 61800?2

Adjustable speed electrical power drive systems
Part 2: General requirements; rating specifications for low voltage adjustable frequency AC power drive systems

EN 61800?3

Adjustable speed electrical power drive systems
Part 3: EMC requirements and specific test methods

EN 61800?5?1

Adjustable speed electrical power drive systems
Part 5: Safety requirements
Main section 1: Electrical and thermal requirements

EN 61800?5?2

Adjustable speed electrical power drive systems
Part 5-2: Safety requirements – Functional safety (IEC 61800?5?2: 2007)



General technical specifications

Electrical specifications

Line voltages

380 … 480 V 3 AC, ±10 % (-15 % <1 min)

500 … 690 V 3 AC, ±10 % (-15 % <1 min)

Line supply types

Grounded TN/TT systems and non-grounded IT systems

Line frequency

47 ... 63 Hz

Output frequency 1)

0 ... 550 Hz

Line power factor

Adjustable (factory-set to cos ? = 1)

Efficiency

>96 %

Overvoltage category

III to EN 61800?5?1

Control method

Vector control with and without encoder or V/f control

Fixed speeds

15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/PROFIBUS/PROFINET)

Skippable speed ranges

4, parameterizable

Setpoint resolution

0.001 rpm digital (14 bits + sign)
12 bits analog

Braking operation

Four-quadrant operation is possible as standard
(optional via a braking unit if braking is required when power fails)

Mechanical specifications

Degree of protection

IP20 (higher degrees of protection up to IP54 optional)

Protection class

I acc. to EN 61800?5?1

Touch protection

EN 50274 / BGV A3 when used for the intended purpose

Cabinet system

Rittal TS8, doors with double-bit key, three-section base plates for cable entry

Paint finish

RAL 7035 (indoor requirements)

Cooling method

Forced air cooling AF according to EN 60146

Ambient conditions

Storage 2)

Transport 2)

Operation

Ambient temperature

-25 ... +55 °C

-25 ... +70 °C

from -40 °C for 24 hours

0 ... 40 °C

to +50 °C, see derating data

Relative humidity

(condensation not permissible)

5 ... 95%

Class 1K4 acc. to IEC 60721?3?1

5 ... 95 % at 40 °C

Class 2K3 acc. to IEC 60721?3?2

5 ... 95%

Class 3K3 acc. to IEC 60721?3?3

Environmental class/harmful chemical substances

Class 1C2 acc. to IEC 60721?3?1

Class 2C2 acc. to IEC 60721?3?2

Class 3C2 acc. to IEC 60721?3?3

Organic/biological influences

Class 1B1 acc. to IEC 60721?3?1

Class 2B1 acc. to IEC 60721?3?2

Class 3B1 acc. to IEC 60721?3?3

Degree of pollution

2 acc. to EN 61800?5?1

Installation altitude

Up to 2000 m above sea level without derating;
> 2000 m see derating data

Mechanical stability

Storage 2)

Transport 2)

Operation

Vibratory load

Class 1M2 acc. to IEC 60721?3?1

Class 2M2 acc. to IEC 60721?3?2

  • Deflection

1.5 mm at 5 ... 9 Hz 3)

3.1 mm at 5 ... 9 Hz 3)

0.075 mm at 10 ... 58 Hz

  • Acceleration

5 m/s? at >9 ... 200 Hz

10 m/s? at 9 ... 200 Hz

9.8 m/s2 at 58 ... 200 Hz

Shock load

Class 1M2 acc. to IEC 60721?3?1

Class 2M2 acc. to IEC 60721?3?2

Class 3M4 acc. to IEC 60721?3?3

  • Acceleration

40 m/s? at 22 ms

100 m/s? at 11 ms

100 m/s2 at 11 ms

Compliance with standards

Conformances/approvals, according to

CE (EMC Directive No. 2004/108/EC and Low Voltage Directive No. 2006/95/EC and Machinery Directive No. 2006/42/EC for functional safety)

Radio interference suppression

SINAMICS drive converter systems are not designed for connection to the public grid (first environment). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800?3, "Second environment" (industrial networks). EMC disturbances can occur when connected to the public power networks. However, if additional measures are taken (e.g. line filter), it can also be operated in the "first environment".



1)Please note:

- The correlation between the maximum output frequency, pulse frequency and current derating. Higher output frequencies on request.

- The correlation between the maximum output frequency and permissible output current (current derating).

Information is provided in the SINAMICS Low Voltage Configuration Manual.

2) In transport packaging.

Deviations from the specified classes are underlined.

Line voltage 380 ... 480 V 3 AC

SINAMICS S150 Converter Cabinet Units

 

 

6SL3710-7LE32-1AA3

6SL3710-7LE32-6AA3

6SL3710-7LE33-1AA3

6SL3710-7LE33-8AA3

6SL3710-7LE35-0AA3

6SL3710-7LE36-1AA3

Type rating

       
  • At IL (50 Hz 400 V) 1)

kW

110

132

160

200

250

315

  • At IH (50 Hz 400 V) 1)

kW

90

110

132

160

200

250

  • At IL (60 Hz 460 V) 2)

hp

150

200

250

300

400

500

  • At IH (60 Hz 460 V) 2)

hp

150

200

200

250

350

350

Output current

       
  • Rated current Irated O

A

210

260

310

380

490

605

  • Base-load current I3)

A

205

250

302

370

477

590

  • Base-load current I4)

A

178

233

277

340

438

460

  • Maximum current Imax O

A

307

375

453

555

715

885

Infeed/regenerative feedback current

       
  • Rated input current Irated I

A

197

242

286

349

447

549

  • Maximum input current Imax I

A

315

390

570

570

735

907

Current demand, max. 5)

       
  • 24 V DC aux. power supply 

A

Internal

Internal

Internal

Internal

Internal

Internal

Pulse frequency 6)

       
  • Rated frequency

kHz

2

2

2

2

2

1.25

  • Pulse frequency, max.
       
  • Without current derating

kHz

2

2

2

2

2

1.25

  • With current derating

kHz

8

8

8

8

8

7.5

Power loss, max. 7)

       
  • At 50 Hz 400 V

kW

6.31

7.55

10.01

10.72

13.13

17.69

  • At 60 Hz 460 V

kW

6.49

7.85

10.45

11.15

13.65

18.55

Cooling air requirement

m3/s

0.58

0.7

1.19

1.19

1.19

1.96

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

71/73

71/73

72/74

72/74

72/74

77/79

Cable length, max.

       
  • Shielded

m

300

300

300

300

300

300

  • Unshielded

m

450

450

450

450

450

450

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

IP20

Dimensions

       
  • Width

mm

1400

1400

1600

1800

1800

2200

  • Height

mm

2000

2000

2000

2000

2000

2000

  • Depth

mm

600

600

600

600

600

600

Weight (without options), approx.

kg

708

708

892

980

980

1716

Short-circuit current rating according to IEC 8)

kA

65

65

65

65

65

65

Minimum short-circuit current 9)

A

3000

3000

4500

4500

8000

12000

Frame sizes

 

      
  • Active Interface Module

 

FI

FI

GI

GI

GI

HI

  • Active Line Module

 

FX

FX

GX

GX

GX

HX

  • Motor Module

 

FX

FX

GX

GX

GX

HX



1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.

2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.

3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5) If the drive closed-loop control is still to remain active when the line supply fails, the equipment must be provided with an external 24 V DC supply.

6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Configuration Manual.

7) The specified power losses are the maximum values at 100% utilization. The values are lower under normal operating conditions.

8) In conjunction with the specified fuses or circuit breakers.

9) Current required for reliably triggering protective devices.

Note:

The power data in hp units is based on the NEC/CEC standards for the North American market.

Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.

Line voltage 380 ... 480 V 3 AC

SINAMICS S150 Converter Cabinet Units

 

 

6SL3710-7LE37-5AA3

6SL3710-7LE38-4AA3

6SL3710-7LE41-0AA3

6SL3710-7LE41-2AA3

6SL3710-7LE41-4AA3

Type rating

      
  • At IL (50 Hz 400 V) 1)

kW

400

450

560

710

800

  • At IH (50 Hz 400 V) 1)

kW

315

400

450

560

710

  • At IL (60 Hz 460 V) 2)

hp

600

700

800

900

1150

  • At IH (60 Hz 460 V) 2)

hp

450

600

700

900

1000

Output current

      
  • Rated current Irated O

A

745

840

985

1260

1405

  • Base-load current I3)

A

725

820

960

1230

1370

  • Base-load current I4)

A

570

700

860

1127

1257

  • Maximum current Imax O

A

1087

1230

1440

1845

2055

Infeed/regenerative feedback current

      
  • Rated input current Irated I

A

674

759

888

1133

1262

  • Maximum input current Imax I

A

1118

1260

1477

1891

2107

Current demand, max. 5)

      
  • 24 V DC aux. power supply

A

Internal

Internal

Internal

Internal

Internal

Pulse frequency 6)

      
  • Rated frequency

kHz

1.25

1.25

1.25

1.25

1.25

  • Pulse frequency, max.
      
  • Without current derating

kHz

1.25

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

7.5

Power loss, max. 7)

      
  • At 50 Hz 400 V

kW

20.63

21.1

27.25

33.05

33.95

  • At 60 Hz 460 V

kW

21.75

22.25

28.65

34.85

35.85

Cooling air requirement

m3/s

1.96

1.96

2.6

2.6

2.6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

77/79

77/79

77/79

78/80

78/80

Cable length, max.

      
  • Shielded

m

300

300

300

300

300

  • Unshielded

m

450

450

450

450

450

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

Dimensions

      
  • Width

mm

2200

2200

2800

2800

2800

  • Height

mm

2000

2000

2000

2000

2000

  • Depth

mm

600

600

600

600

600

Weight (without options), approx.

kg

1731

1778

2408

2408

2408

Short-circuit current rating according to IEC 8)

kA

65

65

84

100

100

Minimum short-circuit current 9)

A

15000

2000

2500

3200

3200

Frame sizes

 

     
  • Active Interface Module

 

HI

HI

JI

JI

JI

  • Active Line Module

 

HX

HX

JX

JX

JX

  • Motor Module

 

HX

HX

JX

JX

JX



1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 400 V 3 AC 50 Hz.

2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 460 V 3 AC 60 Hz.

3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5) If the drive closed-loop control is still to remain active when the line supply fails, the equipment must be provided with an external 24 V DC supply.

6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Configuration Manual.

7) The specified power losses are the maximum values at 100% utilization. The values are lower under normal operating conditions.

8) In conjunction with the specified fuses or circuit breakers.

9) Current required for reliably triggering protective devices.

Note:

The power data in hp units is based on the NEC/CEC standards for the North American market.

Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.

Line voltage 500 ... 690 V 3 AC

SINAMICS S150 Converter Cabinet Units

 

 

6SL3710-7LG28-5AA3

6SL3710-7LG31-0AA3

6SL3710-7LG31-2AA3

6SL3710-7LG31-5AA3

6SL3710-7LG31-8AA3

6SL3710-7LG32-2AA3

Type rating

       
  • At IL (50 Hz 690 V) 1)

kW

75

90

110

132

160

200

  • At IH (50 Hz 690 V) 1)

kW

55

75

90

110

132

160

  • At IL (50 Hz 500 V) 1)

kW

55

55

75

90

110

132

  • At IH (50 Hz 500 V) 1)

kW

45

55

75

90

90

110

  • At IL (60 Hz 575 V) 2)

hp

75

75

100

150

150

200

  • At IH (60 Hz 575 V) 2)

hp

75

75

100

125

150

200

Output current

       
  • Rated current Irated O

A

85

100

120

150

175

215

  • Base-load current IL 3)

A

80

95

115

142

170

208

  • Base-load current IH 4)

A

76

89

117

134

157

192

  • Maximum current Imax O

A

120

142

172

213

255

312

Infeed/regenerative feedback current

       
  • Rated current Irated I

A

86

99

117

144

166

202

  • Maximum current Imax I

A

125

144

170

210

253

308

Current demand, max. 5)

       
  • 24 V DC aux. power supply

A

Internal

Internal

Internal

Internal

Internal

Internal

Pulse frequency 6)

       
  • Rated frequency

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • Pulse frequency, max.
       
  • Without current derating

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

7.5

7.5

Power loss, max. 7)

       
  • At 50 Hz 690 V

kW

5.12

5.38

5.84

5.75

11.02

11.44

  • At 60 Hz 575 V

kW

4.45

4.65

5.12

4.97

11.15

11.56

Cooling air requirement

m3/s

0.58

0.58

0.58

0.58

1.19

1.19

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

71/73

71/73

71/73

71/73

75/77

75/77

Cable length, max.

       
  • Shielded

m

300

300

300

300

300

300

  • Unshielded

m

450

450

450

450

450

450

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

IP20

Dimensions

       
  • Width

mm

1400

1400

1400

1400

1600

1600

  • Height

mm

2000

2000

2000

2000

2000

2000

  • Depth

mm

600

600

600

600

600

600

Weight (without options), approx.

kg

708

708

708

708

892

892

Short-circuit current rating according to IEC 8)

kA

65

65

65

65

65

65

Minimum short-circuit current 9)

A

1000

1000

1300

1800

2500

3000

Frame size

 

      
  • Active Interface Module

 

FI

FI

FI

FI

GI

GI

  • Active Line Module

 

FX

FX

FX

FX

GX

GX

  • Motor Module

 

FX

FX

FX

FX

GX

GX



1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 690 V 3 AC 50 Hz.

2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5) If the drive closed-loop control is still to remain active when the line supply fails, the equipment must be provided with an external 24 V DC supply.

6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Configuration Manual.

7) The specified power losses are the maximum values at 100% utilization. The values are lower under normal operating conditions.

8) In conjunction with the specified fuses or circuit breakers.

9) Current required for reliably triggering protective devices.

Note:

The power data in hp units is based on the NEC/CEC standards for the North American market.

Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.

Line voltage 500 … 690 V 3 AC

SINAMICS S150 Converter Cabinet Units

 

 

6SL3710-7LG32-6AA3

6SL3710-7LG33-3AA3

6SL3710-7LG34-1AA3

6SL3710-7LG34-7AA3

6SL3710-7LG35-8AA3

6SL3710-7LG37-4AA3

Type rating

       
  • At IL (50 Hz 690 V) 1)

kW

250

315

400

450

560

710

  • At IH (50 Hz 690 V) 1)

kW

200

250

315

400

450

630

  • At IL (50 Hz 500 V) 1)

kW

160

200

250

315

400

500

  • At IH (50 Hz 500 V) 1)

kW

132

160

200

250

315

450

  • At IL (60 Hz 575 V) 2)

hp

250

300

400

450

600

700

  • At IH (60 Hz 575 V) 2)

hp

200

250

350

450

500

700

Output current

       
  • Rated current Irated O

A

260

330

410

465

575

735

  • Base-load current IL 3)

A

250

320

400

452

560

710

  • Base-load current IH 4)

A

233

280

367

416

514

657

  • Maximum current Imax O

A

375

480

600

678

840

1065

Infeed/regenerative feedback current

       
  • Rated current Irated I

A

242

304

375

424

522

665

  • Maximum current Imax I

A

370

465

619

700

862

1102

Current demand, max. 5)

       
  • 24 V DC aux. power supply

A

Internal

Internal

Internal

Internal

Internal

Internal

Pulse frequency 6)

       
  • Rated frequency

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • Pulse frequency, max.
       
  • Without current derating

kHz

1.25

1.25

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

7.5

7.5

Power loss, max. 7)

       
  • At 50 Hz 690 V

kW

11.97

12.69

19.98

20.55

24.05

30.25

  • At 60 Hz 575 V

kW

12.03

12.63

18.86

19.47

22.85

28.75

Cooling air requirement

m3/s

1.19

1.19

1.96

1.96

1.96

2.6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

75/77

75/77

77/79

77/79

77/79

77/79

Cable length, max.

       
  • Shielded

m

300

300

300

300

300

300

  • Unshielded

m

450

450

450

450

450

450

Degree of protection

 

IP20

IP20

IP20

IP20

IP20

IP20

Dimensions

       
  • Width

mm

1600

1600

2200

2200

2200

2800

  • Height

mm

2000

2000

2000

2000

2000

2000

  • Depth

mm

600

600

600

600

600

600

Weight (without options), approx.

kg

892

892

1716

1716

1716

2300

Short-circuit current rating according to IEC 8)

kA

65

65

65

65

84

85

Minimum short-circuit current 9)

A

3000

4500

4500

7000

9000

15000

Frame size

 

      
  • Active Interface Module

 

GI

GI

HI

HI

HI

JI

  • Active Line Module

 

GX

GX

HX

HX

HX

JX

  • Motor Module

 

GX

GX

HX

HX

HX

JX



1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 690 V 3 AC 50 Hz.

2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5) If the drive closed-loop control is still to remain active when the line supply fails, the equipment must be provided with an external 24 V DC supply.

6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Configuration Manual.

7) The specified power losses are the maximum values at 100% utilization. The values are lower under normal operating conditions.

8) In conjunction with the specified fuses or circuit breakers.

9) Current required for reliably triggering protective devices.

Note:

The power data in hp units is based on the NEC/CEC standards for the North American market.

Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.

Line voltage 500 … 690 V 3 AC

SINAMICS S150 Converter Cabinet Units

 

 

6SL3710-7LG38-1AA3

6SL3710-7LG38-8AA3

6SL3710-7LG41-0AA3

6SL3710-7LG41-3AA3

Type rating

     
  • At IL (50 Hz 690 V) 1)

kW

800

900

1000

1200

  • At IH (50 Hz 690 V) 1)

kW

710

800

900

1000

  • At IL (50 Hz 500 V) 1)

kW

560

630

710

900

  • At IH (50 Hz 500 V) 1)

kW

500

560

630

800

  • At IL (60 Hz 575 V) 2)

hp

800

900

1000

1250

  • At IH (60 Hz 575 V) 2)

hp

700

800

900

1000

Output current

     
  • Rated current Irated O

A

810

910

1025

1270

  • Base-load current IL 3)

A

790

880

1000

1230

  • Base-load current IH 4)

A

724

814

917

1136

  • Maximum current Imax O

A

1185

1320

1500

1845

Infeed/regenerative feedback current

     
  • Rated current Irated I

A

732

821

923

1142

  • Maximum current Imax I

A

1218

1367

1537

1905

Current demand, max. 5)

     
  • 24 V DC aux. power supply

A

Internal

Internal

Internal

Internal

Pulse frequency 6)

     
  • Rated frequency

kHz

1.25

1.25

1.25

1.25

  • Pulse frequency, max.
     
  • Without current derating

kHz

1.25

1.25

1.25

1.25

  • With current derating

kHz

7.5

7.5

7.5

7.5

Power loss, max. 7)

     
  • At 50 Hz 690 V

kW

34.45

34.65

36.15

42.25

  • At 60 Hz 575 V

kW

32.75

32.85

34.25

39.25

Cooling air requirement

m3/s

2.6

2.6

2.6

2.6

Sound pressure level LpA

(1 m) at 50/60 Hz

dB

77/79

77/79

77/79

77/79

Cable length, max.

     
  • Shielded

m

300

300

300

300

  • Unshielded

m

450

450

450

450

Degree of protection

 

IP20

IP20

IP20

IP20

Dimensions

     
  • Width

mm

2800

2800

2800

2800

  • Height

mm

2000

2000

2000

2000

  • Depth

mm

600

600

600

600

Weight (without options), approx.

kg

2408

2408

2408

2408

Short-circuit current rating according to IEC 8)

kA

85

85

85

85

Minimum short-circuit current 9)

A

2000

2000

2500

3200

Frame size

 

    
  • Active Interface Module

 

JI

JI

JI

JI

  • Active Line Module

 

JX

JX

JX

JX

  • Motor Module

 

JX

JX

JX

JX



1) Rated output of a typical 6-pole standard induction motor based on IL or IH for 690 V 3 AC 50 Hz.

2) Rated output of a typical 6-pole standard induction motor based on IL or IH for 575 V 3 AC 60 Hz.

3) The base-load current IL is based on a load cycle of 110 % for 60 s or 150 % for 10 s with a load cycle duration of 300 s.

4) The base-load current IH is based on a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.

5) If the drive closed-loop control is still to remain active when the line supply fails, the equipment must be provided with an external 24 V DC supply.

6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Configuration Manual.

7) The specified power losses are the maximum values at 100% utilization. The values are lower under normal operating conditions.

8) In conjunction with the specified fuses or circuit breakers.

9) Current required for reliably triggering protective devices.

Note:

The power data in hp units is based on the NEC/CEC standards for the North American market.

Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ

  © ÎÎÎ "ÑÊ ÝÍÅÐÃÎ" 2007-2022
  (4872) 700-366  skenergo@mail.ru
ßíäåêñ.Ìåòðèêà