3) The input current depends on the motor load and line impedance. The input currents apply for load at rated power for a line impedance corresponding to uK = 1 %.
Line voltage 380 ... 500 V 3 AC
PM250D Power Modules
6SL3525-0PE24-0AA1
6SL3525-0PE25-5AA1
6SL3525-0PE27-5AA1
Rated output current Irated1)
A
10.2
13.2
19
Maximum output current Imax
A
20.4
26.4
38
Rated power
kW (hp)
4
5.5
7.5
Rated pulse frequency
kHz
4
4
4
Efficiency ?
%
>95
>95
>95
Power loss 2)
At rated output current
kW
0.167
0.218
0.291
Cooling air requirement
m3/s (ft3/s)
0.012 (0.42)
0.018 (0.64)
0.025 (0.88)
Sound pressure level LpA (1 m)
dB
74.5
74.5
74.5
Rated input current 3)
A
9.5
12.2
17.7
Line supply connection U1/L1, V1/L2, W1/L3, PE
HAN Q4/2 (connector)
HAN Q4/2 (connector)
HAN Q4/2 (connector)
Conductor cross-section
mm2
2.5 ... 6
4 ... 6
4 ... 6
PE connection
(external connection)
On housing with M5 screw
On housing with M5 screw
On housing with M5 screw
Conductor cross-section (recommended)
mm2
10 ... 16
10 ... 16
10 ... 16
Motor connection U2, V2, W2, PE, motor brake, temperature sensor
HAN Q8 (socket)
HAN Q8 (socket)
HAN Q8 (socket)
Conductor cross-section
mm2
2.5 ... 4
4
4
Motor cable length, max.
Shielded
m (ft)
15 (49)
15 (49)
15 (49)
Degree of protection
IP65/UL Type 3
IP65/UL Type 3
IP65/UL Type 3
Dimensions
Width
mm (in)
445 (17.52)
445 (17.52)
445 (17.52)
Height
mm (in)
210 (8.27)
210 (8.27)
210 (8.27)
Depth
mm (in)
220 (8.66)
220 (8.66)
220 (8.66)
Frame size
FSC
FSC
FSC
Weight, approx.
kg (lb)
8.5 (18.7)
8.5 (18.7)
8.5 (18.7)
1) The rated output current Irated is based on the duty cycle for high overload (HO).
3) The input current depends on the motor load and line impedance. The input currents apply for load at rated power for a line impedance corresponding to uK = 1 %.