General information | | |
Product type designation | IM 153-4 PN ST | IM 153-4 PN HF |
Supply voltage | | |
Rated value (DC) | 24 V | 24 V |
| Yes | Yes |
permissible range (ripple included), lower limit (DC) | 20.4 V | 18.5 V |
permissible range (ripple included), upper limit (DC) | 28.8 V | 30.2 V |
external protection for power supply lines (recommendation) | In a construction with grounded reference potential, a fuse is necessary for redundant interface modules (Recommendation: 2.5 A) | In a construction with grounded reference potential, a fuse is necessary for redundant interface modules (Recommendation: 2.5 A) |
Mains buffering | | |
| 5 ms | 5 ms |
Input current | | |
Current consumption, max. | 600 mA; with 24 V DC supply | 600 mA; with 24 V DC supply |
Inrush current, typ. | 4 A | 4 A |
I?t | 0.09 A?·s | 0.09 A?·s |
Output voltage | | |
Rated value (DC) | 5 V | 5 V |
Output current | | |
for backplane bus (5 V DC), max. | 1.5 A | 1.5 A |
Power loss | | |
Power loss, typ. | 6 W | 6 W |
Address area | | |
Addressing volume | | |
| 192 byte | 672 byte; Extended HART user data |
| 192 byte | 192 byte |
Hardware configuration | | |
Number of modules per DP slave interface, max. | 12 | 12 |
Protocols | | |
Bus protocol/transmission protocol | PROFINET IO | PROFINET IO |
Interrupts/diagnostics/status information | | |
Diagnostics indication LED | | |
| Yes | Yes |
| Yes | Yes |
Isolation | | |
Isolation tested with | 500 V DC | Between PROFINET and 24 V supply: 1 500 V AC, between functional grounding and 24 V supply: 500 V DC |
Degree and class of protection | | |
Degree of protection acc. to EN 60529 | | |
| Yes | Yes |
Ambient conditions | | |
Ambient temperature during operation | | |
| 0 °C | 0 °C |
| 60 °C | 60 °C |
Air pressure acc. to IEC 60068-2-13 | | |
| 2 000 m | 2 000 m |
Dimensions | | |
Width | 40 mm | 40 mm |
Height | 125 mm | 125 mm |
Depth | 118 mm | 118 mm |
Weights | | |
Weight, approx. | 215 g | 215 g |