Transmitter TRANSMAG 2 | |
Mode of operation and design | |
Measuring principle | Electromagnetic with pulsed alternating field (PAC) |
Magnetic field excitation | Automatic power supply synchronization |
| Bipolar (16.7 Hz) Bipolar with prepulse (10 Hz) Unipolar (8.33 Hz) |
| Bipolar (20 Hz) Bipolar with prepulse (12 Hz) Unipolar (10 Hz) |
Accuracy under reference conditions | |
Measuring tolerance of pulse output | |
- With v > 0.25 m/s (0.82 ft/s)
| ? ± 0.5 % of measured value ± 1.2 mm/s (0.05 inch/s) |
- With v < 0.25 m/s (0.82 ft/s)
| ± 2.5 mm/s (0.1 inch/s) |
Measuring tolerance of analog output | As pulse output plus ± 0.1 % conversion error ± 20 µA |
Repeatability | 0.2 % of measured value |
Reference conditions | |
| 25 °C ± 5 °C (77 °F ± 9 °F) |
| 25 °C ± 5 °C (77 °F ± 9 °F) |
| Min. 30 min |
| Inlet pipe section ? 10 x DN |
Outlet pipe section ? 5 x DN |
Installed centered in pipe |
| Water without gaseous or solid components |
Calibration | |
Standard production calibration, calibration report shipped with sensor | Zero-point, 2 x 25 % and 2 x 90 % |
Outputs | |
Electrical isolation | Outputs electrically isolated from one another and from the power supply, max. 60 V permissible against PE/equipotential bonding |
Current output | 0/4 … 20 mA (7ME5034-0…. or 7ME5034-2….) |
| |
| 0/4 … 20 mA, selectable |
| 20 … 22.5 mA, optional 3.6; 20 or 24 mA |
| |
| max. 600 ?, max. load voltage 15 V DC |
| ? 250 ? |
Communication | Via analog output with PC coupling module or HART communicator |
| HART, version 5.1 |
Digital output | |
Signal | |
| Configurable as active or passive signals |
| 24 V DC, ? 24 mA, Ri = 170 ? |
| Open collector, max. 30 V DC, 200 mA |
Output configuration | |
| |
| ? 5000 pulses/s |
| ? 0.1 ms |
| ? 10000 Hz |
| Limits for flow and quantity, flow direction, alarm |
Digital output 2 (relay) | |
(only 7ME5034-0…) | |
Relay | NC or NO function |
| Max. 5 W, max. 50 V AC/DC, max. 200 mA |
| Limits for flow and quantity, flow direction, alarm |
Digital input (optional to digital output 2) | Non-intrinsically-safe |
(only 7ME5034-2…) | |
- Input function configurable as high-active or low-active
| Set measured value to zero or reset totalizer |
| Max. 30 V DC, Ri = 3 k?: High level: +11 … +30 V DC Low level: -30 … +5 V DC |
For PROFIBUS devices | |
PROFIBUS PA (for PROFIBUS?devices 7ME5034-1…) | |
| Layer 1 and 2 according to PROFIBUS PA |
Transmission according to IEC 1158-2 |
Layer 7 (protocol layer) according to PROFIBUS PA and DP V1 (EN 50170) |
Device Class B, device profile 2.0 |
Max. 4 simultaneous C2 connections |
| 9 … 32 V DC permissible |
- Current consumption from bus
| 10 mA; limited to ? 15 mA in event of fault by electrical current limitation |
Rated operating conditions | |
Installation conditions | See also sensors |
Ambient temperature | |
| -20 … +60 °C (-4 … +140 °F) |
| 0 … 50 °C (32 … 122 °F) |
Storage | -25 … +80 °C (-13 … +176 °F) |
Degree of protection | IP67/NEMA 4X |
Electromagnetic compatibility (EMC) | |
| To IEC/EN 61326 for use in industrial areas |
| To IEC/EN 61326 for use in industrial areas |
Medium conditions | |
| -20 … +150 °C (-4 … 302 °F) depending on her liner |
Minimum conductivity of medium | |
- With SITRANS F M 911/E sensors
| ? 1 µS/cm (0.1 ?S/cm depending on medium) |
Design | |
Weight of transmitter | 4.4 kg (9.7 lb) |
Remote version | Transmitter must be connected to sensor using shielded cable |
Maximum cable length | 100 m (328 ft) |
Housing | Die-cast aluminum, painted |
Displays and keypad | |
General display | LCD, backlid, two lines with 16 characters each |
Multi-display for | Flow, totalizer, flow velocity |
Keypad | 4 keys for entering parameters |
Power supply | |
corresponding to rating plate | |
| 100 … 250 V AC ± 15 %, 47 … 63 Hz |
| Approx. 120 … 630 VA, depending on sensor |
Line fuse | 100 … 230 V AC: T1.6A |
Magnet current fuse | F5A/250 V |