At 24 V DC via the CU320-2 Control Unit without taking into account the digital outputs
0.05 A
Conductor cross-section, max.
2.5 mm2
Fuse protection, max.
20 A
Digital inputs
In accordance with IEC 61131-2 Type 1
Voltage
-3 … +30 V
Low level (an open digital input is interpreted as "low")
-3 … +5 V
High level
15 … 30 V
Current consumption at 24 V DC, typ.
10 mA
Delay time of digital inputs 1), approx.
L > H
50 ?s
H > L
100 ?s
Conductor cross-section, max.
0.5 mm2
Digital outputs
Continuously short-circuit proof
Voltage
24 V DC
Load current per digital output, max.
500 mA
Delay time of digital outputs 1), approx.
150 ?s
Conductor cross-section, max.
0.5 mm2
Analog inputs
Difference
Voltage range (an open analog input is interpreted as 0 V)
-10 … +10 V
Internal resistance Ri
65 k?
Resolution 2)
13 bit + sign
Conductor cross-section, max.
0.5 mm2
Analog outputs
Continuously short-circuit proof
Voltage range
-10 … +10 V
Load current, max.
-3 … +3 mA
Resolution
11 bit + sign
Settling time, approx.
200 ?s
Conductor cross-section, max.
0.5 mm2
Power loss
< 3 W
Weight, approx.
0.1 kg
Conformity
CE
Approvals, according to
cULus
1) The specified delay times refer to the hardware. The actual reaction time depends on the time slot in which the digital input or output is processed.
2) If the analog input is to be operated in the signal processing sense with continuously variable input voltage, the sampling frequency fa = 1/ttime slice must be at least twice the value of the highest signal frequency fmax.