Active Interface ModulesLine voltage 380 … 480 V 3 AC | Active Interface Modules |
|---|
| 6SL3300-7TE32-6AA0 | 6SL3300-7TE33-8AA0 | 6SL3300-7TE35-0AA0 | Suitable for Active Line Module | | | | | | | kW | 132 | 160 | 235 | 300 | | | 6SL3330-7TE32-1AA3 | 6SL3330-7TE32-6AA3 | 6SL3330-7TE33-8AA3 | 6SL3330-7TE35-0AA3 | | | – | – | – | 6SL3335-7TE35-0AA3 | Rated current | A | 210 | 260 | 380 | 490 | Bypass contactor | | included | included | included | included | Current demand | | | | | | - 24 V DC auxiliary power supply
| A | 0.17 | 0.17 | 0.17 | 0.17 | | | | | | | | A | 1.25 | 1.25 | 2.5 | 2.5 | | A | 0.6 | 0.6 | 1.2 | 1.2 | DC link capacitance of the drive line-up, max. 1) | ?F | 41600 | 41600 | 76800 | 76800 | Power loss, max. 2) | | | | | | | kW | 2.1 | 2.2 | 3.0 | 3.9 | | kW | 2.1 | 2.2 | 3.0 | 3.9 | Cooling air requirement | m3/s | 0.24 | 0.24 | 0.47 | 0.47 | Line supply/load connection L1, L2, L3 / U2, V2, W2 | | M10 nut | M10 nut | M10 nut | M10 nut | - Conductor cross-section, max. (IEC)
| mm2 | 2 ? 185 | 2 ? 185 | 2 ? 185 | 2 ? 185 | PE/GND connection | | M10 nut | M10 nut | M10 nut | M10 nut | - Conductor cross-section, max. (IEC)
| mm2 | 2 ? 185 | 2 ? 185 | 2 ? 185 | 2 ? 185 | Degree of protection | | IP20 | IP20 | IP20 | IP20 | Dimensions | | | | | | | mm | 325 | 325 | 325 | 325 | | mm | 1400 | 1400 | 1533 | 1533 | | mm | 355 | 355 | 544 | 544 | Weight, approx. | kg | 135 | 135 | 190 | 190 | Frame size | | FI | FI | GI | GI |
1)Information on higher capacities is included in the SINAMICS Low Voltage Engineering Manual. 2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. Line voltage 380 … 480 V 3 AC | Active Interface Modules |
|---|
| 6SL3300-7TE38-4AA0 | 6SL3300-7TE41-4AA0 | Suitable for Active Line Module | | | | | | | kW | 380 | 450/500 | 630 | 800/900 | | | 6SL3330-7TE36-1AA3 | 6SL3330-7TE37-5AA3 6SL3330-7TE38-4AA3 | 6SL3330-7TE41-0AA3 | 6SL3330-7TE41-2AA3 6SL3330-7TE41-4AA3 | | | – | 6SL3335-7TE38-4AA3 | – | – | Rated current | A | 605 | 840 | 985 | 1405 | Bypass contactor | | 3RT1476-6AP36 | 3WL1110-2BB34-4AN2-Z C22 | 3WL1112-2BB34-4AN2-Z C22 | 3WL1116-2BB34-4AN2-Z C22 | Current demand | | | | | | - 24 V DC auxiliary power supply
| A | 0.17 | 0.17 | 0.17 | 0.17 | | | | | | | | A | 9.9 | 9.9 | 10.5 | 10.5 | | A | 4.6 | 4.6 | 4.9 | 4.9 | DC link capacitance of the drive line-up, max. 1) | ?F | 134400 | 134400 | 230400 | 230400 | Power loss, max. 2) | | | | | | | kW | 5.5 | 6.1 | 7.5 | 8.5 | | kW | 5.5 | 6.1 | 7.5 | 8.5 | Cooling air requirement | m3/s | 0.4 | 0.4 | 0.4 | 0.4 | Line supply/load connection L1, L2, L3 / U2, V2, W2 | | 4 ? hole for M12 | 4 ? hole for M12 | 3 ? hole for M12 | 3 ? hole for M12 | - Conductor cross-section, max. (IEC)
| mm2 | 4 ? 240 | 4 ? 240 | 6 ? 240 | 6 ? 240 | PE/GND connection | | 2 ? M12 nut | 2 ? M12 nut | 4 ? M12 nut | 4 ? M12 nut | - Conductor cross-section, max. (IEC)
| mm2 | 2 ? 240 | 2 ? 240 | 4 ? 240 | 4 ? 240 | Degree of protection | | IP00 | IP00 | IP00 | IP00 | Dimensions | | | | | | | mm | 305 | 305 | 505 | 505 | | mm | 1750 | 1750 | 1750 | 1750 | | mm | 544 | 544 | 544 | 544 | Weight, approx. | kg | 390 | 390 | 620 | 620 | Frame size | | HI | HI | JI | JI |
1)Information on higher capacities is included in the SINAMICS Low Voltage Engineering Manual. 2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions. Line voltage 500 … 690 V 3 AC | Active Interface Modules |
|---|
| 6SL3300-7TG35-8AA0 | 6SL3300-7TG37-4AA0 | 6SL3300-7TG41-3AA0 | Suitable for Active Line Module | | | | | | | kW | 560 | 800 | 1100 | 1400 | | | 6SL3330-7TG35-8AA3 | 6SL3330-7TG37-4AA3 | 6SL3330-7TG41-0AA3 | 6SL3330-7TG41-3AA3 | | | 6SL3335-7TG35-8AA3 | – | – | 6SL3335-7TG41-3AA3 | Rated current | A | 575 | 735 | 1025 | 1270 | Bypass contactor | | 3RT1476-6AP36 | 3RT1476-6AP36 (3 units) | 3WL1212-4BB34-4AN2-Z C22 | 3WL1216-4BB34-4AN2-Z C22 | Current demand | | | | | | - 24 V DC auxiliary power supply
| A | 0.17 | 0.17 | 0.17 | 0.17 | | | | | | | | A | 9.9 | 10.5 | 10.5 | 10.5 | | A | 4.6 | 4.9 | 4.9 | 4.9 | DC link capacitance of the drive line-up, max. 1) | ?F | 59200 | 153600 | 153600 | 153600 | Power loss, max. 2) | | | | | | | kW | 6.8 | 9.0 | 9.2 | 9.6 | | kW | 6.8 | 9.0 | 9.2 | 9.6 | Cooling air requirement | m3/s | 0.4 | 0.4 | 0.4 | 0.4 | Line supply/load connection L1, L2, L3 / U2, V2, W2 | | 4 ? hole for M12 | 3 ? hole for M12 | 3 ? hole for M12 | 3 ? hole for M12 | - Conductor cross-section, max. (IEC)
| mm2 | 4 ? 240 | 6 ? 240 | 6 ? 240 | 6 ? 240 | PE/GND connection | | 2 ? M12 nut | 4 ? M12 nut | 4 ? M12 nut | 4 ? M12 nut | - Conductor cross-section, max. (IEC)
| mm2 | 2 ? 240 | 4 ? 240 | 4 ? 240 | 4 ? 240 | Degree of protection | | IP00 | IP00 | IP00 | IP00 | Dimensions | | | | | | | mm | 305 | 505 | 505 | 505 | | mm | 1750 | 1750 | 1750 | 1750 | | mm | 544 | 544 | 544 | 544 | Weight, approx. | kg | 390 | 620 | 620 | 620 | Frame size | | HI | JI | JI | JI |
1)Information on higher capacities is included in the SINAMICS Low Voltage Engineering Manual. 2) The specified power loss represents the maximum value at 100 % utilization. The value is lower under normal operating conditions.
|
|