Current requirement (X524 at 24 V DC) without DRIVE-CLiQ supply | 0.2 A |
- Conductor cross-section, max.
| 2.5 mm2 |
| 20 A |
Max. current requirement ext. 24 V for supplying the digital outputs and 24 V sensor supply (X514 at 24 V DC) | 4 A |
- Conductor cross-section, max.
| 2.5 mm2 |
| 20 A |
I/O | |
- Number
of fail-safe digital inputs
| 10 |
- Number
of fail-safe digital outputs
| 4 |
| 3, of which 2 can be temporarily shut down using an internal test routine for dynamizing fail-safe digital inputs, current carrying capacity 0.5 A each |
| Plug-in screw-type terminals |
- Conductor cross-section, max.
| 1.5 mm2 |
Digital inputs in accordance with IEC 61131?2 Type 1, with galvanic isolation | |
| -3 ... +30 V |
- Low level
(an open digital input is interpreted as "low")
| -3 ... +5 V |
| 15 ... 30 V |
- Current consumption
at 24 V DC, typ.
| > 2 mA |
- Delay time of
digital inputs, approx. 1)
| |
| 30 ?s |
| 60 ?s |
| Low level (for inputs that can be inverted: without inversion) |
Digital outputs (continuously short-circuit proof) | |
| 24 V DC |
- Load current
per fail-safe digital output, max. 2)
| 0.5 A |
- Delay times
(resistive load) 1)
| |
| 300 ?s |
| 350 ?s |
| Output switched off |
Scanning cycle tSI for fail-safe digital inputs or fail-safe digital outputs | 4 ... 25 ms (adjustable) |
Power loss, max. At 24 V | 4.5 W |
PE connection | M4 screw |
Dimensions | |
| 50 mm (1.97 in) |
| 150 mm (5.91 in) |
| 111 mm (4.37 in) |
Weight, approx. | 0.9 kg (2 lb) |
Approvals, according to | cULus |
Safety Integrated | Acc. to IEC 61508 SIL 2 and EN ISO 13849?1 PL d and Category 3 |