Current requirement
(X524 at 24 V DC) without DRIVE?CLiQ supply
|
0.2 A
|
- Conductor cross-section, max.
|
2.5 mm2
|
|
|
20 A
|
|
Max. current demand ext. 24 V
For supplying the digital outputs and 24 V sensor supply (X514 at 24 V DC)
|
4 A
|
- Conductor cross-section, max.
|
2.5 mm2
|
|
|
20 A
|
|
I/O
|
|
- Number of fail-safe digital inputs
|
10
|
- Number of fail-safe digital outputs
|
4
|
|
|
3, of which 2 can be internally shut down temporarily for dynamizing fail-safe digital inputs, current carrying capacity of each is 0.5 A
|
|
|
Plug-in screw-type terminals
|
- Conductor cross-section, max.
|
1.5 mm2
|
|
Digital inputs
According to IEC 61131?2 Type 1, with isolation
|
|
|
|
-3 … +30 V
|
- Low level (an open digital input is interpreted as "low")
|
-3 … +5 V
|
|
|
15 … 30 V
|
- Current consumption at 24 V DC, typ.
|
> 2 mA
|
- Delay time of digital inputs, approx. 1)
|
|
|
|
30 ?s
|
|
|
60 ?s
|
|
|
Low level (for inputs that can be inverted: without inversion)
|
|
Digital outputs
(sustained short-circuit strength)
|
|
|
|
24 V DC
|
- Load current per fail-safe digital output, max. 2)
|
0.5 A
|
- Delay times (resistive load) 1)
|
|
|
|
300 ?s
|
|
|
350 ?s
|
|
|
Output switched off
|
|
Scanning cycle tSI
for fail-safe digital inputs or fail-safe digital outputs
|
4 ... 25 ms (adjustable)
|
|
PE connection
|
M4 screw
|
|
Dimensions
|
|
|
|
50 mm (1.97 in)
|
|
|
150 mm (5.90 in)
|
|
|
111 mm (4.37 in)
|
|
Weight, approx.
|
0.9 kg (2 lb)
|
|
Approvals, according to
|
cULus
|
|
Safety Integrated
|
Safety Integrity Level 2 (SIL2) acc. to IEC 61508, Performance Level d (PLd) acc. to ISO 13849?1 and Control Category 3 acc. to ISO 13849?1 or EN 954?1
|