PM230 Power Modules have the following connections and interfaces:
PM?IF interface to connect the PM230 Power Module to the Control Unit. The PM230 Power Module also supplies power to the Control Unit using an integrated power supply.
Motor connection using screw terminals or screw studs
2 PE/protective conductor connections
PM230 Power Modules communicate with the Control Unit via the PM-IF interface.
Connection diagram for PM230 Power Module with or without integrated line filter class A or B
Power components that are optionally available depending on the Power Module used
The following line-side and load-side power components are optionally available in the appropriate frame sizes for the Power Modules:
Frame size
FSA
FSB
FSC
FSD
FSE
FSF
PM230 Power Module (IP54/IP55)
Available frame sizes
?
?
?
?
?
?
Line-side power components
Line filter class A
I
I
I
I
I
I
Line filter class B
I
I
I
I
I
I
Line reactor 1)
– 1)
– 1)
– 1)
– 1)
– 1)
– 1)
Load-side power components
Output reactor
S
S
S
S
S
S
Sine-wave filter
–
–
–
S
S
S
PM230 Power Module (IP20)
Available frame sizes
?
?
?
?
?
?
Line-side power components
Line filter class A
F
F
F
F
F
F
Line filter class B
U 2)
U 2)
U 2)
S
S
S
Line reactor 1)
– 1)
– 1)
– 1)
– 1)
– 1)
– 1)
Load-side power components
Output reactor
S
S
S
S
S
S
Sine-wave filter
–
–
–
S
S
S
U = Base component
S = Lateral mounting
I = Integrated
F = Power Modules available with and without integrated filter class A
– = Not possible
1) A line reactor is not required and must not be used in conjunction with a PM230 Power Module.
2) Lateral mounting is the only possible option for Push Through variants.
Maximum permissible cable lengths from the motor to the inverter when using output reactors or filters depending on the voltage range and the Power Module being used
The following load-side power components in the appropriate frame sizes are optionally available for the Power Modules and result in the following maximum cable lengths:
Maximum permissible motor cable lengths (shielded/unshielded) in m
Frame size
FSA
FSB
FSC
FSD
FSE
FSF
PM230 Power Module degree of protection IP20
Available frame sizes
?
?
?
?
?
?
Without output reactor/sine-wave filter
25/100
(82/328)
25/100
(82/328)
25/100
(82/328)
25/100
(82/328)
25/100
(82/328)
25/100
(82/328)
With optional output reactor
At 380 ... 415 V 3 AC
150/225
(492/738)
150/225
(492/738)
150/225
(492/738)
–
–
–
At 440 ... 480 V 3 AC
100/150
(328/492)
100/150
(328/492)
100/150
(328/492)
–
–
–
At 380 -10 % ... 400 V 3 AC
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
At 401 ... 480 V 3 AC +10 %
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
With optional sine-wave filter
At 380 -10 % ... 400 V 3 AC
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
At 401 ... 480 V 3 AC +10 %
–
–
–
200/300
(656/984)
200/300
(656/984)
200/300
(656/984)
With integrated line filter class A (EMC category C3)
At 380 ... 415 V 3 AC
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
At 440 ... 480 V 3 AC
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
With optional external line filter class B (EMC category C1 1), with unfiltered Power Module, maintains the limit values acc. to EN 61800?3)
At 380 ... 415 V 3 AC
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
At 440 ... 480 V 3 AC
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
50/–
(164/–)
With optional external line filter class B and output reactor (EMC category C2 1), with unfiltered Power Module, maintains the limit values acc. to EN 61800?3)