General information | |
Product type designation | CPU414-3 PN/DP |
Engineering with | |
| STEP7 V5.5 or higher/iMap V3.0 + iMap STEP7 Add-on V3.0 SP5 or higher |
Supply voltage | |
Rated value (DC) | |
| No; Power supply via system power supply |
Power loss | |
Power loss, typ. | 6.5 W |
Memory | |
Work memory | |
| 4 Mbyte |
| 2 Mbyte |
| 2 Mbyte |
Load memory | |
| 64 Mbyte |
| 512 kbyte |
| 64 Mbyte |
CPU processing times | |
for bit operations, typ. | 45 ns |
for word operations, typ. | 45 ns |
for fixed point arithmetic, typ. | 45 ns |
for floating point arithmetic, typ. | 135 ns |
Counters, timers and their retentivity | |
S7 counter | |
| 2 048 |
IEC counter | |
| Yes |
S7 times | |
| 2 048 |
IEC timer | |
| Yes |
Data areas and their retentivity | |
Flag | |
| 8 kbyte; Size of bit memory address area |
Address area | |
I/O address area | |
| 8 kbyte |
| 8 kbyte |
Process image | |
| 8 kbyte |
| 8 kbyte |
Hardware configuration | |
Slots | |
| 2 |
Time of day | |
Clock | |
| Yes |
Operating hours counter | |
| 16 |
Interfaces | |
Interfaces/bus type | 1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable) |
Number of RS 485 interfaces | 0 |
Number of other interfaces | 0 |
1. Interface | |
Interface type | Integrated |
Physics | RS 485 / PROFIBUS + MPI |
Functionality | |
| Yes |
| Yes |
| Yes |
DP master | |
| 32 |
2. Interface | |
Interface type | PROFINET |
Physics | Ethernet RJ45 |
Number of ports | 2 |
Functionality | |
| No |
| No |
| Yes |
| Yes |
| Yes |
PROFINET IO Controller | |
| 256 |
| 256 |
| 64 |
3. Interface | |
Interface type | Pluggable interface module (IF) |
Plug-in interface modules | IF 964-DP (MLFB: 6ES7964-2AA04-0AB0) |
Physics | RS 485 / PROFIBUS |
Functionality | |
| No |
| Yes |
| Yes |
DP master | |
| 96 |
Isochronous mode | |
Isochronous operation (application synchronized up to terminal) | Yes; Via PROFIBUS DP or PROFINET interface |
Communication functions | |
PG/OP communication | Yes |
Data record routing | Yes |
Global data communication | |
| Yes |
S7 basic communication | |
| Yes |
S7 communication | |
| Yes |
S5 compatible communication | |
| Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 |
Standard communication (FMS) | |
| Yes; Via CP and loadable FB |
Open IE communication | |
| Yes; via integrated PROFINET interface and loadable FBs |
| 62 |
| Yes; Via integrated PROFINET interface or CP 443-1 Adv. and loadable FBs |
| 62 |
| Yes; via integrated PROFINET interface and loadable FBs |
| 62 |
Web server | |
| Yes |
Number of connections | |
| 64 |
Ambient conditions | |
Ambient temperature during operation | |
| -25 °C; = Tmin |
| 70 °C; = Tmax; @ 60°C for UL/ATEX/FM use |
Extended ambient conditions | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
Resistance | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! |
| Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Configuration | |
Programming | |
Programming language | |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
Know-how protection | |
| Yes |
| Yes; With S7 block Privacy |
Dimensions | |
Width | 50 mm |
Height | 290 mm |
Depth | 219 mm |
Weights | |
Weight, approx. | 900 g |