The most important directives and standards are listed below. These are used as basis for the SINAMICS S150 Converter Cabinet Units drive system and they must be carefully observed to achieve an EMC-compliant configuration that is safe both functionally and in operation.
European directives
2006/95/EG
Low-voltage directive: Legal guidelines of the EU member states concerning electrical equipment for use within specified voltage limits
2004/108/EG
EMC directive: Legal guidelines of the EU member states for electromagnetic compatibility
European standards
EN 954?1 1)
Safety of machinery – safety-related parts of control systems; Part 1: General design principles
EN ISO 13849?1
Safety of machinery – safety-related parts of control systems; Part 1: General design guidelines (ISO 13849-1: 2006) (replaces EN 954-1)
EN 60146?1?1
Semiconductor converters – General requirements and line-commutated converters Part 1-1: Specification of basic requirements
EN 60204?1
Safety of machinery – Electrical equipment of machines; Part 1: General requirements
EN 60529
Degrees of protection provided by enclosures (IP code)
EN 61508?1
Functional safety of electrical/electronic/programmable electronic safety-related systems Part 1: General requirements
EN 61800?2
Variable-speed electric drives Part 2: General requirements – Rating specifications for low-voltage adjustable frequency AC power drive systems
EN 61800?3
Variable-speed electric drives Part 3: EMC requirements including specific test methods
EN 61800?5?1
Adjustable-speed electrical power drive systems Part 5: Safety requirements Main section 1: Electrical and thermal requirements
EN 61800?5?2
Adjustable speed electrical power drive systems Part 5-2: Safety requirements – Functional safety (IEC 61800-5-2: 2007)
1) Will be replaced by EN ISO 13849-1 at the end of 2011.
General technical specifications
Electrical specifications
Line voltages
80 … 480 V 3 AC , ±10 % (-15 % < 1 min)
500 … 690 V 3 AC, ±10 % (-15 % < 1 min)
Line supply types
Grounded TN/TT systems and non-grounded IT systems
Line frequency
47 ... 63 Hz
Output frequency 1)
Control type Servo
0 ... 650 Hz
Control type Vector
0 ... 600 Hz
Control type V/f
0 ... 600 Hz
Line power factor
Adjustable (factory-set to cos ? = 1)
Efficiency
> 96 %
Overvoltage category
III to EN 61800?5?1
Control method
Vector control with and without encoder or V/f control
Fixed speeds
15 fixed speeds plus 1 minimum speed, parameterizable (in the default setting, 3 fixed setpoints plus 1 minimum speed are selectable using terminal block/PROFIBUS/PROFINET)
Skipped speed ranges
4, parameterizable
Setpoint resolution
0.001 rpm digital (14 bits + sign) 12 bit analog
Braking operation
Four-quadrant operation is possible as standard (optional via a braking unit if braking is required when power fails)
Mechanical specifications
Degree of protection
IP20 (higher degrees of protection up to IP54 optional)
Protection class
I acc. to EN 61800?5?1
Touch protection
EN 50274 / BGV A3 for the intended purpose
Cabinet system
Rittal TS 8, doors with double-barb lock, three-section base plates for cable entry
Paint finish
RAL 7035 (indoor requirements)
Type of cooling
Forced air cooling AF to EN 60146
Ambient conditions
Storage 2)
Transport 2)
Operation
Ambient temperature
-25 ... +55 °C
-25 ... +70 °C
from -40 °C3) for 24 hours
03) ... +40 °C
to +50 °C, see derating data
Relative humidity
(condensation not permissible)
5 ... 95 %3)
Class 1K4 acc. to IEC 60721?3?1
5 ... 95 % at 40 °C
Class 2K3 acc. to IEC 60721?3?2
5 ... 95 %3)
Class 3K3 acc. to IEC 60721?3?3
Environmental class/harmful chemical substances
Class 1C2 acc. to IEC 60721?3?1
Class 2C2 acc. to IEC 60721?3?2
Class 3C2 acc. to IEC 60721?3?3
Organic/biological influences
Class 1B1 acc. to IEC 60721?3?1
Class 2B1 acc. to IEC 60721?3?2
Class 3B1 acc. to IEC 60721?3?3
Degree of pollution
2 acc. to EN 61800?5?1
2 acc. to EN 61800?5?1
2 acc. to EN 61800?5?1
Installation altitude
Up to 2000 m above sea level, without derating, > 2000 m, see derating data
Mechanical stability
Storage 2)
Transport 2)
Operation
Vibration load
Class 1M2 acc. to IEC 60721?3?1
Class 2M2 acc. to IEC 60721?3?2
–
Deflection
1.5 mm at 5 ... 9 Hz
3.1 mm at 5 ... 9 Hz
0.075 mm at 10 ... 58 Hz
Acceleration
5 m/s? at > 9 ... 200 Hz
10 m/s? at 9 ... 200 Hz
9.8 m/s2 at 58 ... 200 Hz
Shock load
Class 1M2 acc. to IEC 60721?3?1
Class 2M2 acc. to IEC 60721?3?2
Class 3M4 acc. to IEC 60721?3?3
Acceleration
40 m/s? at 22 ms
100 m/s? at 11 ms
100 m/s2 at 11 ms
Compliance with standards
Conformances/approvals, according to
CE (EMC Directive No. 2004/108/EC and Low-Voltage Directive No. 2006/95/EC)
Radio interference suppression
SINAMICS drive converter systems are not designed for connection to the public network (first environment). Radio interference suppression is compliant with the EMC product standard for variable-speed drives EN 61800-3, "Second environment" (industrial line supplies). The equipment can cause electromagnetic interference when it is connected to the public network. However, if supplementary measures are taken (e.g. > line filter), it can also be operated in the "first environment".
1) Please note:
- The correlation between the maximum output frequency, pulse frequency and current derating. Higher output frequencies for specific configurations are available on request.
- The correlation between the maximum output frequency and permissible output current (current derating).
Information is provided in the SINAMICS Low Voltage Engineering Manual.
2) In transport packaging.
3) Deviations with respect to the specified class are underlined.
Line voltage 380 … 480 V 3 AC
SINAMICS S150 Converter Cabinet Units
6SL3710-7LE32-1AA3
6SL3710-7LE32-6AA3
6SL3710-7LE33-1AA3
6SL3710-7LE33-8AA3
6SL3710-7LE35-0AA3
6SL3710-7LE36-1AA3
Type rating
For IL (50 Hz 400 V) 1)
kW
110
132
160
200
250
315
For IH (50 Hz 400 V) 1)
kW
90
110
132
160
200
250
For IL (60 Hz 460 V) 2)
hp
150
200
250
300
400
500
For IH (60 Hz 460 V) 2)
hp
150
200
200
250
350
350
Output current
Rated current IN A
A
210
260
310
380
490
605
Base load current IL 3)
A
205
250
302
370
477
590
Base load current IH 4)
A
178
233
277
340
438
460
Max. current Imax A
A
307
375
453
555
715
885
Infeed/regenerative feedback current
Rated input current IN E
A
197
242
286
349
447
549
Max. input current Imax E
A
315
390
570
570
735
907
Current demand, max. 5)
24 V DC auxiliary power supply
A
Internal
Internal
Internal
Internal
Internal
Internal
Pulse frequency 6)
Rated frequency
kHz
2
2
2
2
2
1.25
Pulse frequency, max.
Without current derating
kHz
2
2
2
2
2
1.25
With current derating
kHz
8
8
8
8
8
7.5
Power loss, max. 7)
At 50 Hz 400 V
kW
6.31
7.55
10.01
10.72
13.13
17.69
At 60 Hz 460 V
kW
6.49
7.85
10.45
11.15
13.65
18.55
Cooling air requirement
m3/s
0.58
0.7
1.19
1.19
1.19
1.96
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
71/73
71/73
72/74
72/74
72/74
77/79
Cable length, max.
Shielded
m
300
300
300
300
300
300
Unshielded
m
450
450
450
450
450
450
Degree of protection
IP20
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm
1400
1400
1600
1800
1800
2200
Height
mm
2000
2000
2000
2000
2000
2000
Depth
mm
600
600
600
600
600
600
Weight, approx.
kg
708
708
892
980
980
1716
Frame size
F
F
G
G
G
H
Note: The power data in hp units are based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 400 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 460 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5) If the drive closed-loop control is still to remain active when the line supply fails, then the equipment must be provided with an external 24 V DC supply.
6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
7) The specified power losses are the maximum values at 100 % utilization. The values are lower under normal operating conditions.
Line voltage 380 … 480 V 3 AC
SINAMICS S150 Converter Cabinet Units
6SL3710-7LE37-5AA3
6SL3710-7LE38-4AA3
6SL3710-7LE41-0AA3
6SL3710-7LE41-2AA3
6SL3710-7LE41-4AA3
Type rating
For IL (50 Hz 400 V) 1)
kW
400
450
560
710
800
For IH (50 Hz 400 V) 1)
kW
315
400
450
560
710
For IL (60 Hz 460 V) 2)
hp
600
700
800
900
1150
For IH (60 Hz 460 V) 2)
hp
450
600
700
900
1000
Output current
Rated current IN A
A
745
840
985
1260
1405
Base load current IL 3)
A
725
820
960
1230
1370
Base load current IH 4)
A
570
700
860
1127
1257
Max. current Imax A
A
1087
1230
1440
1845
2055
Infeed/regenerative feedback current
Rated input current IN E
A
674
759
888
1133
1262
Max. input current Imax E
A
1118
1260
1477
1891
2107
Current demand, max. 5)
24 V DC auxiliary power supply
A
Internal
Internal
Internal
Internal
Internal
Pulse frequency 6
Rated frequency
kHz
1.25
1.25
1.25
1.25
1.25
Pulse frequency, max.
Without current derating
kHz
1.25
1.25
1.25
1.25
1.25
With current derating
kHz
7.5
7.5
7.5
7.5
7.5
Power loss, max. 7)
At 50 Hz 400 V
kW
20.63
21.1
27.25
33.05
33.95
At 60 Hz 460 V
kW
21.75
22.25
28.65
34.85
35.85
Cooling air requirement
m3/s
1.96
1.96
2.6
2.6
2.6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
77/79
77/79
77/79
78/80
78/80
Cable length, max.
Shielded
m
300
300
300
300
300
Unshielded
m
450
450
450
450
450
Degree of protection
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm
2200
2200
2800
2800
2800
Height
mm
2000
2000
2000
2000
2000
Depth
mm
600
600
600
600
600
Weight, approx.
kg
1731
1778
2408
2408
2408
Frame size
H
H
J
J
J
Note: The power data in hp units are based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 400 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 460 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5) If the drive closed-loop control is still to remain active when the line supply fails, then the equipment must be provided with an external 24 V DC supply.
6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
7) The specified power losses are the maximum values at 100 % utilization. The values are lower under normal operating conditions.
Line voltage 500 … 690 V 3 AC 50 Hz
SINAMICS S150 Converter Cabinet Units
6SL3710-7LG28-5AA3
6SL3710-7LG31-0AA3
6SL3710-7LG31-2AA3
6SL3710-7LG31-5AA3
6SL3710-7LG31-8AA3
6SL3710-7LG32-2AA3
Type rating
For IL (50 Hz 690 V) 1)
kW
75
90
110
132
160
200
For IH (50 Hz 690 V) 1)
kW
55
75
90
110
132
160
For IL (50 Hz 500 V) 1)
kW
55
55
75
90
110
132
For IH (50 Hz 500 V) 1)
kW
45
55
75
90
90
110
For IL (60 Hz 575 V) 2)
hp
75
75
100
150
150
200
For IH (60 Hz 575 V) 2)
hp
75
75
100
125
150
200
Output current
Rated current IN A
A
85
100
120
150
175
215
Base load current IL 3)
A
80
95
115
142
170
208
Base load current IH 4)
A
76
89
117
134
157
192
Max. current Imax A
A
120
142
172
213
255
312
Infeed/regenerative feedback current
Rated input current IN E
A
86
99
117
144
166
202
Max. input current Imax E
A
125
144
170
210
253
308
Current demand, max. 5)
24 V DC auxiliary power supply
A
Internal
Internal
Internal
Internal
Internal
Internal
Pulse frequency 6
Rated frequency
kHz
1.25
1.25
1.25
1.25
1.25
1.25
Pulse frequency, max.
Without current derating
kHz
1.25
1.25
1.25
1.25
1.25
1.25
With current derating
kHz
7.5
7.5
7.5
7.5
7.5
7.5
Power loss, max. 7)
At 50 Hz 690 V
kW
5.12
5.38
5.84
5.75
11.02
11.44
At 60 Hz 575 V
kW
4.45
4.65
5.12
4.97
11.15
11.56
Cooling air requirement
m3/s
0.58
0.58
0.58
0.58
1.19
1.19
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
71/73
71/73
71/73
71/73
75/77
75/77
Cable length, max.
Shielded
m
300
300
300
300
300
300
Unshielded
m
450
450
450
450
450
450
Degree of protection
IP20
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm
1400
1400
1400
1400
1600
1600
Height
mm
2000
2000
2000
2000
2000
2000
Depth
mm
600
600
600
600
600
600
Weight, approx.
kg
708
708
708
708
892
892
Frame size
F
F
F
F
G
G
Note: The power data in hp units are based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 500 V or 690 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 575 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5) If the drive closed-loop control is still to remain active when the line supply fails, then the equipment must be provided with an external 24 V DC supply.
6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
7) The specified power losses are the maximum values at 100 % utilization. The values are lower under normal operating conditions.
Line voltage 500 … 690 V 3 AC 50 Hz
SINAMICS S150 Converter Cabinet Units
6SL3710-7LG32-6AA3
6SL3710-7LG33-3AA3
6SL3710-7LG34-1AA3
6SL3710-7LG34-7AA3
6SL3710-7LG35-8AA3
6SL3710-7LG37-4AA3
Type rating
For IL (50 Hz 690 V) 1)
kW
250
315
400
450
560
710
For IH (50 Hz 690 V) 1)
kW
200
250
315
400
450
630
For IL (50 Hz 500 V) 1)
kW
160
200
250
315
400
500
For IH (50 Hz 500 V) 1)
kW
132
160
200
250
315
450
For IL (60 Hz 575 V) 2)
hp
250
300
400
450
600
700
For IH (60 Hz 575 V) 2)
hp
200
250
350
450
500
700
Output current
Rated current IN A
A
260
330
410
465
575
735
Base load current IL 3)
A
250
320
400
452
560
710
Base load current IH 4)
A
233
280
367
416
514
657
Max. current Imax A
A
375
480
600
678
840
1065
Infeed/regenerative feedback current
Rated input current IN E
A
242
304
375
424
522
665
Max. input current Imax E
A
370
465
619
700
862
1102
Current demand, max. 5)
24 V DC auxiliary power supply
A
Internal
Internal
Internal
Internal
Internal
Internal
Pulse frequency 6
Rated frequency
kHz
1.25
1.25
1.25
1.25
1.25
1.25
Pulse frequency, max.
Without current derating
kHz
1.25
1.25
1.25
1.25
1.25
1.25
With current derating
kHz
7.5
7.5
7.5
7.5
7.5
7.5
Power loss, max. 7)
At 50 Hz 690 V
kW
11.97
12.69
19.98
20.55
24.05
30.25
At 60 Hz 575 V
kW
12.03
12.63
18.86
19.47
22.85
28.75
Cooling air requirement
m3/s
1.19
1.19
1.96
1.96
1.96
2.6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
75/77
75/77
77/79
77/79
77/79
77/79
Cable length, max.
Shielded
m
300
300
300
300
300
300
Unshielded
m
450
450
450
450
450
450
Degree of protection
IP20
IP20
IP20
IP20
IP20
IP20
Dimensions
Width
mm
1600
1600
2200
2200
2200
2800
Height
mm
2000
2000
2000
2000
2000
2000
Depth
mm
600
600
600
600
600
600
Weight, approx.
kg
892
892
1716
1716
1716
2300
Frame size
G
G
H
H
H
J
Note: The power data in hp units are based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 500 V or 690 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 575 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5) If the drive closed-loop control is still to remain active when the line supply fails, then the equipment must be provided with an external 24 V DC supply.
6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
7) The specified power losses are the maximum values at 100 % utilization. The values are lower under normal operating conditions.
Line voltage 500 … 690 V 3 AC 50 Hz
SINAMICS S150 Converter Cabinet Units
6SL3710-7LG38-1AA3
6SL3710-7LG38-8AA3
6SL3710-7LG41-0AA3
6SL3710-7LG41-3AA3
Type rating
For IL (50 Hz 690 V) 1)
kW
800
900
1000
1200
For IH (50 Hz 690 V) 1)
kW
710
800
900
1000
For IL (50 Hz 500 V) 1)
kW
560
630
710
900
For IH (50 Hz 500 V) 1)
kW
500
560
630
800
For IL (60 Hz 575 V) 2)
hp
800
900
1000
1250
For IH (60 Hz 575 V) 2)
hp
700
800
900
1000
Output current
Rated current IN A
A
810
910
1025
1270
Base load current IL 3)
A
790
880
1000
1230
Base load current IH 4)
A
724
814
917
1136
Max. current Imax A
A
1185
1320
1500
1845
Infeed/regenerative feedback current
Rated input current IN E
A
732
821
923
1142
Max. input current Imax E
A
1218
1367
1537
1905
Current demand, max. 5)
24 V DC auxiliary power supply
A
Internal
Internal
Internal
Internal
Pulse frequency 6
Rated frequency
kHz
1.25
1.25
1.25
1.25
Pulse frequency, max.
Without current derating
kHz
1.25
1.25
1.25
1.25
With current derating
kHz
7.5
7.5
7.5
7.5
Power loss, max. 7)
At 50 Hz 690 V
kW
34.45
34.65
36.15
42.25
At 60 Hz 575 V
kW
32.75
32.85
34.25
39.25
Cooling air requirement
m3/s
2.6
2.6
2.6
2.6
Sound pressure level LpA
(1 m) at 50/60 Hz
dB
77/79
77/79
77/79
77/79
Cable length, max.
Shielded
m
300
300
300
300
Unshielded
m
450
450
450
450
Degree of protection
IP20
IP20
IP20
IP20
Dimensions
Width
mm
2800
2800
2800
2800
Height
mm
2000
2000
2000
2000
Depth
mm
600
600
600
600
Weight, approx.
kg
2408
2408
2408
2408
Frame size
J
J
J
J
Note: The power data in hp units are based on the NEC/CEC standards for the North American market.
Information about line supply connections, motor connections and cabinet grounding can be found under Cable cross-sections and connections.
1) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 500 V or 690 V 3 AC 50 Hz.
2) Rated power of a typ. 6-pole standard induction motor based on IL or IH with 575 V 3 AC 60 Hz.
3) The base load current IL is the basis for a duty cycle of 110 % for 60 s or 150 % for 10 s with a duty cycle duration of 300 s.
4) The base load current IH is the basis for a duty cycle of 150 % for 60 s or 160 % for 10 s with a duty cycle duration of 300 s.
5) If the drive closed-loop control is still to remain active when the line supply fails, then the equipment must be provided with an external 24 V DC supply.
6)Information regarding the correlation between the pulse frequency and max. output current/output frequency is provided in the SINAMICS Low Voltage Engineering Manual.
7) The specified power losses are the maximum values at 100 % utilization. The values are lower under normal operating conditions.
skener.ru
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Установка обезжелезивания