Overload capabilityLoad cycle data for Single Motor Modules in chassis format The base-load current IL is based on a duty cycle of 110% for 60 s or 150% for 10 s with a duty cycle duration of 300 s. Low overload The base-load current IH is based on a duty cycle of 150% for 60 s or 160% for 10 s with a duty cycle duration of 300 s. High overload Derating factorsWhen the pulse frequency is increased, the derating factor of the output current must be taken into account. This derating factor must be applied to the currents specified in the technical data. Derating factor of the output current as a function of the pulse frequency for devices with a rated pulse frequency of 2 kHz
Current derating as a function of the ambient temperature Note: A derating factor kT > 1.0 is applicable only in conjunction with "current derating as a function of installation altitude". The rated current data may not be exceeded. For further information see System description. Current derating as a function of the installation altitude Voltage derating as a function of installation altitude |