Suitability for use | Cable for permanent installation in cable channels and pipes, UL approval | Cable for high mechanical loading, for indoor and outdoor installation in cable carriers |
Version of the assembled FO cable | For assembly with four BFOC or SC connectors | For assembly with four BFOC or SC connectors |
Cable designation | AT-V(ZN)YY 2GK 62.5/200/230 | AT-V(ZN)Y(ZN)11Y 2GK 62.5/200/230 |
Optical data | | |
Damping ratio per length | | |
| 160 dB/km | 180 dB/km |
| 3.2 dB/km | 3.2 dB/km |
| 0.9 dB/km | 0.9 dB/km |
Bandwidth length product | | |
| 200 GHz·m | 200 GHz·m |
| 500 GHz·m | 500 GHz·m |
Mechanical data | | |
Number of fibers per FOC core | 1 | 1 |
Number of FO cores per FOC cable | 2 | 2 |
Version of the FO conductor fiber | Multi-mode gradient fiber 62.5/200/230 µm | Multi-mode gradient fiber 62.5/200/230 µm |
Design of the FOC core | Fixed core | Fixed core |
Design of the fiber-optic cable | Segmentable cable | Segmentable cable |
Outer diameter | | |
| 62.5 µm | 62.5 µm |
| 230 µm | 230 µm |
| 2.2 mm | 2.2 mm |
Symmetrical deviation of the outer diameter of the FOC core sheath | 0.1 mm | 0.1 mm |
Outer diameter of the cable | 7.2 mm | 8.8 mm |
Symmetrical deviation of the outer diameter of the line | 0.5 mm | 0.5 mm |
Material | | |
| Quartz glass | Quartz glass |
| ETFE | ETFE |
| PVC | PVC |
| PVC | PUR |
| Aramid fibers | Aramid fibers (double-ply) |
Color | | |
| Orange/black | Orange/black |
| green | green |
Bending radius | | |
| 70 mm | 88 mm |
| 105 mm | 88 mm |
| | 88 mm |
Number of bending cycles | | 5 000 000 |
Tensile load during operation | | |
| 100 N | 800 N |
Short-term shear force per length | 500 N/cm | 500 N/cm |
Continuous lateral force per length | 300 N/cm | 300 N/cm |
Weight per length | 49 kg/km | 65 kg/km |
Permitted ambient conditions | | |
Ambient temperature | | |
| -40 ... +85 °C | -25 ... +75 °C |
| -40 ... +85 °C | -30 ... +75 °C |
| -40 ... +85 °C | -30 ... +75 °C |
| -5 ... +50 °C | -5 ... +50 °C |
Burning behavior | Flame-resistant acc. to IEC 60332-1-2 and IEC 60332-3-22 (Cat. A) | Flame-resistant acc. to IEC 60332-1-2 |
Chemical resistance | | |
| Conditional resistance | resistant |
| Conditional resistance | resistant |
| Conditional resistance | Conditional resistance |
Radiological resistance to UV radiation | resistant | resistant |
Product properties, functions, components general | | |
Product property | | |
| No | No |
| Yes | Yes |
Product component Rodent protection | No | No |
Cable length | | |
| 3 000 m | 3 000 m |
| 350 m | 350 m |
| 550 m | 550 m |
| 3 000 m | 3 000 m |
Standards, specifications, approvals | | |
Certificate of suitability | UL approval: cULus OFN (NEC Article 770, UL 1651) / CSA approval: OFN 90 Cel, FT1, FT4 (CSA-Standard C22.2 No232-M1988) | |
| Yes | Yes |