Article No.
|
6EP1 961-3BA01
|
|
Input/Output
|
Stabilized, isolated DC voltage
|
|
Rated voltage Uin rated
|
24 V DC
|
|
Voltage range
|
24 ... 28.8 V
|
|
Control input
|
-
|
|
Rated output voltage Uout rated
|
U
in – approx. 1 V
|
|
Rated current Iout rated
|
40 A
|
|
Mains buffering
|
Backup time:
- With 40 A load current: 200 ms
- With 20 A load current: 400 ms
- With 10 A load current: 800 ms
- With 5 A load current: 1.6 s
Reduces the backup time by 100 ms in combination with 6EP1 437-3BA10.
|
|
Buffering time, max.
|
10 s
|
|
Protection and monitoring
|
|
|
Current limiting, static
|
Typ. 40 A
|
|
Short-circuit protection
|
Electronically
|
|
Signaling/alarm signals
|
|
|
Status display
|
Green LED for "Supply voltage > 20.5 V"
|
|
Signaling
|
-
|
|
Safety
|
|
|
Galvanic isolation
|
Yes, SELV acc. to EN 60950-1
|
|
Safety class
|
Class I
|
|
Safety test
|
Yes
|
|
CE marking
|
Yes
|
|
UL/cUL (CSA) approval
|
UL-listed (UL 508) File E197259, CSA (CSA C22.2 No. 14, CSA C22.2 No. 107.1)
|
|
Explosion protection
|
-
|
|
Degree of protection (EN 60529)
|
IP20
|
|
EMC
|
|
|
Emitted interference
|
EN 55022 Class B
|
|
Noise immunity
|
EN 61000-6-2
|
|
Operating data
|
|
|
Ambient temperature range
|
0 ... +60 °C with natural convection
|
|
Transport and storage temperature range
|
-40 ... +85°C
|
|
Humidity class
|
Climate class 3K3 according to EN 60721, no condensation
|
|
Mechanics
|
|
|
Connections
|
One screw-type terminal each for + and - for 0.5 ... 10 mm2 solid/finely stranded
|
|
Dimensions (W x H x D) in mm
|
70 x 125 x 125
|
|
Weight, approx.
|
1.2 kg
|
|
Mounting
|
Can be snapped onto standard mounting rail EN 60715 35x7.5/15
|