Article?No.
|
6EP1?332-4BA00
|
6EP1?333-4BA00
|
Product
|
S7-1500?PM1507
|
S7-1500?PM1507
|
Power?supply,?type
|
24?V/3?A
|
24?V/8?A
|
Input
|
|
|
Input
|
1-phase?AC
|
1-phase?AC
|
Rated?voltage?value?Vin?rated?min.
|
|
|
Supply?voltage
|
|
|
- 1?with?AC?minimum?rated?value
|
|
|
- 2?with?AC?minimum?rated?value
|
|
|
Rated?voltage?value?Vin?rated?max.
|
|
|
Supply?voltage
|
|
|
- 1?with?AC?maximum?rated?value
|
|
|
- 2?at?AC?maximum?nominal?value
|
|
|
|
120 V
|
120 V
|
|
230 V
|
230 V
|
|
…
|
…
|
|
Automatic?range?selection
|
Automatic?range?selection
|
Voltage?range
|
…
|
…
|
Input?voltage
|
|
|
|
85 … 132 V
|
85 … 132 V
|
|
170 … 264 V
|
170 … 264 V
|
|
…
|
…
|
Overvoltage?resistance
|
2.3???Vin?rated,?1.3?ms
|
2.3???Vin?rated,?1.3?ms
|
Mains?buffering?at?Iout?rated,?min.
|
20 ms
|
20 ms
|
Mains?buffering
|
at?Vin?=?93/187?V
|
at?Vin?=?93/187?V
|
Rated?line?frequency
|
|
|
|
50 Hz
|
50 Hz
|
|
60 Hz
|
60 Hz
|
Rated?line?range
|
45 … 65 Hz
|
45 … 65 Hz
|
Input?current
|
|
|
- at?nominal?level?of?the?input?voltage?120?V?nominal?value
|
1.4 A
|
3.7 A
|
- at?nominal?level?of?the?input?voltage?230?V?nominal?value
|
0.8 A
|
1.7 A
|
- at?nominal?level?of?the?input?voltage?400?V?nominal?value
|
|
|
- at?nominal?level?of?the?input?voltage?500?V?nominal?value
|
|
|
- at?DC?at?nominal?level?of?the?input?voltage?600?V?nominal?value
|
|
|
Switch-on?current?limiting?(+25?°C),?max.
|
23 A
|
62 A
|
I?t,?max.
|
1.3 A?·s
|
12 A?·s
|
Built-in?incoming?fuse
|
T?3,15?A/250?V?(not?accessible)
|
T?6.3?A/250?V?(not?accessible)
|
Protection?in?the?mains?power?input?(IEC?898)
|
Recommended?miniature?circuit?breaker:?10?A?characteristic?B?or?6?A?characteristic?C
|
Recommended?miniature?circuit?breaker:?16?A?characteristic?B?or?10?A?characteristic?C
|
Output
|
|
|
Output
|
Controlled,?isolated?DC?voltage
|
Controlled,?isolated?DC?voltage
|
Rated?voltage?Vout?DC
|
24 V
|
24 V
|
Total?tolerance,?static?±
|
1 %
|
1 %
|
Static?mains?compensation,?approx.
|
0.1 %
|
0.1 %
|
Static?load?balancing,?approx.
|
0.1 %
|
0.1 %
|
Residual?ripple?peak-peak,?max.
|
50 mV
|
50 mV
|
Residual?ripple?peak-peak,?typ.
|
|
|
Spikes?peak-peak,?max.?(bandwidth:?20?MHz)
|
150 mV
|
150 mV
|
Spikes?peak-peak,?typ.?(bandwidth:?20?MHz)
|
|
|
Adjustment?range
|
…
|
…
|
Product?feature?output?voltage?adjustable
|
No
|
No
|
Output?voltage?setting
|
|
|
Note
|
|
|
Status?display
|
LED?green?for?24?V?OK;?LED?red?for?error;?LED?yellow?for?stand-by
|
LED?green?for?24?V?OK;?LED?red?for?error;?LED?yellow?for?stand-by
|
Signaling
|
|
|
On/off?behavior
|
No?overshoot?of?Vout?(soft?start)
|
No?overshoot?of?Vout?(soft?start)
|
Startup?delay,?max.
|
1.5 s
|
1.5 s
|
Note
|
|
|
Voltage?rise,?typ.
|
10 ms
|
10 ms
|
Voltage?increase?time?of?the?output?voltage?maximum
|
|
|
Rated?current?value?Iout?rated
|
3 A
|
8 A
|
Current?range
|
0 … 3 A
|
0 … 8 A
|
Note
|
|
|
delivered?active?power?typ.
|
72 W
|
192 W
|
short-term?overload?current?at?short-circuit?during?run-up?typical
|
12 A
|
35 A
|
Duration?of?overloading?ability?for?excess?current?on?short-circuiting?during?the?start-up
|
70 ms
|
70 ms
|
Constant?overload?current?in?the?event?of?a?short?circuit?during?startup?/typical
|
|
|
short-term?overload?current?at?short-circuit?during?operation?typical
|
12 A
|
35 A
|
Duration?of?overloading?ability?for?excess?current?on?short-circuiting?during?the?operational?phase
|
70 ms
|
70 ms
|
constant?overload?current?at?short-circuit?during?operation?typical
|
|
|
Parallel?switching?for?enhanced?performance
|
Yes
|
Yes
|
Note
|
Parallel?switching?of?3?A?and?8?A?possible,?devices?must?be?switched?on?at?the?same?time,?max.?75%?per?device?with?I-load
|
Parallel?switching?of?3?A?and?8?A?possible,?devices?must?be?switched?on?at?the?same?time,?max.?75%?per?device?with?I-load
|
Numbers?of?parallel?switchable?units?for?enhanced?performance
|
2
|
2
|
Efficiency
|
|
|
Efficiency?at?Vout?rated,?Iout?rated,?approx.
|
87 %
|
90 %
|
Power?loss?at?Vout?rated,?Iout?rated,?approx.
|
11 W
|
21 W
|
Closed-loop?control
|
|
|
Dynamic?mains?compensation?(Vin?rated?±15?%),?max.
|
0.1 %
|
0.1 %
|
Dynamic?load?smoothing?(Iout:?50/100/50?%),?Uout?±?typ.
|
1 %
|
2 %
|
Load?step?setting?time?50?to?100%,?typ.
|
|
|
Load?step?setting?time?100?to?50%,?typ.
|
|
|
Setting?time?maximum
|
5 ms
|
5 ms
|
Protection?and?monitoring
|
|
|
?Output?overvoltage?protection
|
Additional?control?loop,?limitation?(closed?loop?control)?at?<?28.8?V
|
Additional?control?loop,?limitation?(closed?loop?control)?at?<?28.8?V
|
Pick-up?level?current?limitation
|
|
|
|
3.15 A
|
8.4 A
|
|
3.6 A
|
9.6 A
|
Current?limitation,?typ.
|
3.4 A
|
9 A
|
Characteristic?feature?of?the?output?short-circuit?protected
|
Yes
|
Yes
|
Short-circuit?protection
|
Electronic?shutdown,?automatic?restart
|
Electronic?shutdown,?automatic?restart
|
Enduring?short?circuit?current?Effective?level?typical
|
|
|
Note
|
|
|
Overload/short-circuit?indicator
|
-
|
-
|
Safety
|
|
|
Primary/secondary?isolation
|
Yes
|
Yes
|
Potential?separation
|
Safety?extra-low?output?voltage?Uout?acc.?to?EN?60950-1?and?EN?50178?and?EN?61131-2
|
Safety?extra-low?output?voltage?Uout?acc.?to?EN?60950-1?and?EN?50178?and?EN?61131-2
|
Protection?class
|
Class?I
|
Class?I
|
stray?current
|
|
|
|
3.5 mA
|
3.5 mA
|
|
0.4 mA
|
1.3 mA
|
CE?mark
|
Yes
|
Yes
|
UL/CSA?approval
|
Yes
|
Yes
|
UL/cUL?(CSA)?approval
|
cULus-Listed?(UL?508,?CSA?C22.2?No.?142),?File?E143289
|
cULus-Listed?(UL?508,?CSA?C22.2?No.?142),?File?E143289
|
Explosion?protection
|
ATEX?(EX)?II?3G?Ex?nA?nC?IIC?T4?Gc;?cULus?(ISA?12.12.01,?CSA?C22.2?No.213)??Class?I,?Div.?2,?Group?ABCD,?T4,?File?E330455
|
ATEX?(EX)?II?3G?Ex?nA?nC?IIC?T3?Gc;?cULus?(ISA?12.12.01,?CSA?C22.2?No.213)??Class?I,?Div.?2,?Group?ABCD,?T3,?File?E330455
|
FM?approval
|
Yes
|
Yes
|
FM?approval
|
Class?I,?Div.?2,?Group?ABCD,?T4
|
Class?I,?Div.?2,?Group?ABCD,?T4
|
CB?approval
|
Yes
|
Yes
|
Marine?approval
|
DNV
|
DNV
|
Degree?of?protection?(EN?60529)
|
IP20
|
IP20
|
EMC
|
|
|
Emitted?interference
|
EN?55022?Class?B
|
EN?55022?Class?B
|
Supply?harmonics?limitation
|
EN?61000-3-2
|
EN?61000-3-2
|
Noise?immunity
|
EN?61000-6-2
|
EN?61000-6-2
|
Operating?data
|
|
|
Ambient?temperature
|
|
|
|
0 … 60 °C
|
0 … 60 °C
|
|
with?natural?convection
|
with?natural?convection
|
Ambient?temperature
|
|
|
|
-40 … +85 °C
|
-40 … +85 °C
|
|
-40 … +85 °C
|
-40 … +85 °C
|
Humidity?class?according?to?EN?60721
|
Climate?class?3K3,?no?condensation
|
Climate?class?3K3,?no?condensation
|
Mechanics
|
|
|
Connection?technology
|
Screw-/spring?clamp?connection
|
Screw-/spring?clamp?connection
|
Connections
|
|
|
|
L,?N,?PE:?1?screw?terminal?each?for?0.5?...?2.5?mm?
|
L,?N,?PE:?1?screw?terminal?each?for?0.5?...?2.5?mm?
|
|
L+,?M:?2?spring-loaded?terminals?each?for?0.5?to?2.5?mm?
|
L+,?M:?2?spring-loaded?terminals?each?for?0.5?to?2.5?mm?
|
|
|
|
Width?of?the?housing
|
50 mm
|
75 mm
|
Height?of?the?housing
|
147 mm
|
147 mm
|
Depth?of?the?housing
|
129 mm
|
129 mm
|
Installation?width
|
50 mm
|
75 mm
|
Installation?height
|
205 mm
|
205 mm
|
Weight,?approx.
|
0.45 kg
|
0.74 kg
|
Product?feature?of?the?housing?housing?for?side-by-side?mounting
|
Yes
|
Yes
|
Type?of?mounting
|
|
|
|
No
|
No
|
|
No
|
No
|
|
Yes
|
Yes
|
Installation
|
Can?be?mounted?onto?S7-1500?rail
|
Can?be?mounted?onto?S7-1500?rail
|
Electrical?accessories
|
|
|
Mechanical?accessories
|
|
|