The table shows the maximum buffering times for the SITOP UPS1100 battery modules for different load currents:
The SITOP Selection Tool offers detailed selection guidance according to criteria such as the required backup time, nominal current, peak current and battery connection threshold:
http://www.siemens.de/sitop-selection-tool

SITOP

UPS1100 24 V, 1.2 Ah
(6EP4131-0GB00-0AY0)

UPS1100 24 V, 3.2 Ah
(6EP4133-0GB00-0AY0)

UPS1100 24 V, 7 Ah
(6EP4134-0GB00-0AY0)

UPS1100 24 V/ 12 Ah
(6EP4135-0GB00-0AY0)

UPS1100 24V/ 2.5 Ah high-temperature
(6EP4132-GB00-0AY0)

Load current

Buffer times

       

1 A

34.5 minutes

2.6 h

5.4 h

9 h

2 h

2 A

15.5 min

1 h

2.6 h

4.6 h

1 h

3 A

9 min

39.3 min

1.6 h

2.9 h

37.5 min

4 A

6.5 min

27.1 min

1.2 h

2.2 h

27 min

6 A

3.5 min

17.5 min

41 min

1.2 h

17.6 min

8 A

2 min

12.1 min

28.6 min

53.3 min

12.5 min

10 A

1 min

9 min

21.8 min

43.5 min

8.8 min

12 A

-

7 min

17.3 min

33.3 min

6.8 min

14 A

-

5 min

15.1 min

27.5 min

5.1 min

16 A

-

4 min

12.5 min

23.8 min

4.3 min

20 A

-

1 min

9.1 min

20.1 min

-

25 A

-

-

-

12.6 min

-

30 A

-

-

-

9.1 min

-

35 A

-

-

-

17.1 min. (2 x 12 Ah)

-

40 A

-

-

-

13.5 min. (2 x 12 Ah)

-


Important information for selecting the battery capacity:

Determination of the mains buffering times is based on the discharge period of new or non-aged, completely charged battery modules at a battery temperature not below +25 °C to the shutdown of the DC UPS.

Battery aging reduces the still available battery capacity up until the end of the service life to typically around 50% of the original capacity value when new (1.2 Ah/3.2 Ah/7 Ah, etc.) and the internal resistance increases. When the message "Battery charge > 85%" appears, only around 50% x 85% = approx. 43% of the originally available capacity can be assumed at the end of the battery service life.

At battery temperatures below +25 °C, the available capacity drops approximately by another 30% at +5 °C battery temperature, to approximately 70% of the approximately remaining 43%. There is then only around 30% of the original capacity available.

A significantly larger battery capacity must therefore be selected when configuring the plant: A drop to approx. 50% is compensated for by selecting 1 / approx. 0.5 = approx. double the battery capacity (required as per the table for the relevant load current and the relevant buffering time). Available capacity of approx. 43% is compensated for by selecting 1 / approx. 0.43 = approx. 2.33 times the battery capacity. Available capacity of approx. 30% is compensated for by selecting 1 / approx. 0.3 = approx. 3.33 times the battery capacity.

Recommendation:

Instead of installing double the battery capacity, regular battery replacement halfway through the expected service life (reduction of capacity to approx. 50%) can be more advisable for the following reasons: Capacity does not drop below 100% until the halfway point of the expected battery life (or slightly beyond). With regular replacement after this point, only the single battery capacity (instead of double capacity) must be installed due to aging (-> neutral in price with regard to battery module costs, but only requires half the space).

Replacing the battery after half its service life dispenses above all with the large scatter range of the residual capacity at the end of the service life, which is not accurately defined by battery manufacturers (after the full time, many batteries are above, but many are also below the average 50% residual capacity, that is to say, even if double the capacity is installed, the influence of aging at the end of service life is not reliably compensated for, rather only typically) -> When replacing after half the expected service life, the configured buffering time is maintained with considerably greater reliability.

In the case of batteries stored in cool conditions (not above +25 °C) and for not longer than approximately 4 months, the following service life can be assumed, strongly dependent on battery temperature:

Battery temperature

Drop to approx. 50% of residual capacity

Recommendation: Replace (at 100% of residual capacity)
all

Alternative recommendation

+20 °C

4 years

2 years

 

+30 °C

2 years

1 year

 

+40 °C

1 year

0.5 years

Install double capacity and replace
(1 x per year)


In normal cases (installation in the coolest location in the control cabinet at approx. +30 °C), the battery should be replaced with single installed battery capacity in accordance with the selection table after 1 year of operation!

After a power failure, the battery module is disconnected from the loads at the end of the selected buffering time either automatically or electronically by opening the On/Off control circuit, and as soon as the 24 V input voltage is available again, it is quickly re-charged with the charge current of the relevant DC UPS module (with I-U charge characteristic: First constant current I for fast charging, and changeover to constant voltage U to maintain the charge when the battery is almost full).

DC UPS modules

SITOP UPS1600 24 V/ 10 A

SITOP UPS1600 24 V/ 20 A

SITOP UPS1600 24 V/ 40 A

Article No.

6EP4134-3AB00-0AY0
6EP4134-3AB00-1AY0 (with USB interface)
6EP4134-3AB00-2AY0 (with 2 Ethernet/PROFINET interfaces)

6EP4136-3AB00-0AY0
6EP4136-3AB00-1AY0 (with USB interface)
6EP4136-3AB00-2AY0 (with 2 Ethernet/PROFINET interfaces)

6EP4137-3AB00-0AY0
6EP4137-3AB00-1AY0 (with USB interface)
EP4137-3AB00-2AY0 (with 2 Ethernet/ PROFINET interfaces)

Input data

     

Input voltage Vin rated/ range 1)

24 V DC/ 21 ... 29 V

24 V DC/ 21 ... 29 V

24 V DC/ 21 ... 29 V

Connection threshold for buffering

22.5 V DC ± 3% (factory setting), adjustable: 21 V, 21.5 V, 22 V, 22.5 V, 23 V, 24 V, 25 V DC or via software.

22.5 V DC ± 3% (factory setting), adjustable: 21 V, 21.5 V, 22 V, 22.5 V, 23 V, 24 V, 25 V DC or via software.

22.5 V DC ± 3% (factory setting), adjustable: 21 V, 21.5 V, 22 V, 22.5 V, 23 V, 24 V, 25 V DC or via software.

Input current Iout rated

Approx. 14 A for max. charging current (3 A)

Approx. 25 A for max. charging current (4 A)

Approx. 46 A for max. charging current (5 A)

Mains buffering

   

Adjustable range using rotary coding switch

0.5 min, 1 min, 2 min, 5 min, 10 min, 20 min, max. buffering time or via software

0.5 min, 1 min, 2 min, 5 min, 10 min, 20 min, max. buffering time or via software

0.5 min, 1 min, 2 min, 5 min, 10 min, 20 min, max. buffering time or via software

Behavior on restoration of input voltage after buffering time

Interruption of Uout for 5 s for the automatic restart of PCs or optionally no interruption

Interruption of Uout for 5 s for the automatic restart of PCs or optionally no interruption

Interruption of Uout for 5 s for the automatic restart of PCs or optionally no interruption

On/off control circuit (via external isolated NO contact)

by opening the circuit the buffer mode is terminated

by opening the circuit the buffer mode is terminated

by opening the circuit the buffer mode is terminated

Starting from battery with input voltage missing (over external isolated NO contact)

by closing the circuit the buffer mode is started

by closing the circuit the buffer mode is started

by closing the circuit the buffer mode is started

Energy storage units

     

Connectable batteries

– coded Siemens types SITOP UPS1100 (max. 6 via Energy Storage Link)
– non-coded Siemens types 6EP1935-6M...
– other manufacturers

– coded Siemens types SITOP UPS1100 (max. 6 via Energy Storage Link)
– non-coded Siemens types 6EP1935-6M...
– other manufacturers

– coded Siemens types SITOP UPS1100 (max. 6 via Energy Storage Link)
– non-coded Siemens types 6EP1935-6M...
– other manufacturers

Output data

     

Output voltage in normal operation

Input voltage Uin - approx. 0.01 x I

Input voltage Uin - ca. 0.01 x I

Input voltage Uin - ca. 0.01 x I

Output voltage in buffering mode

27 V DC (no load); 24 V (50 % battery rated current); 22 V (100 % battery rated current); 18.5 V (exhaustive discharge protection)

27 V DC (no load); 24 V (50 % battery rated current); 22 V (100 % battery rated current); 18.5 V (exhaustive discharge protection)

27 V DC (no load); 24 V (50 % battery rated current); 22 V (100 % battery rated current); 18.5 V (exhaustive discharge protection)

Output +Bat/-Bat in normal operation

I-V charging characteristic (first constant charging current, then charge retention)

I-V charging characteristic (first constant charging current, then charge retention)

I-V charging characteristic (first constant charging current, then charge retention)

End-of-charge voltage

Automatic temperature-specific setting with SITOP UPS1100 battery modules

Automatic temperature-specific setting with SITOP UPS1100 battery modules

Automatic temperature-specific setting with SITOP UPS1100 battery modules

Rated output current

  • Power boost for 30 ms
  • Extra power for 5 s/min

0 ... 10 A

30 A

15 A

0 ... 20 A

60 A

30 A

0 ... 40 A

120 A

60 A

Charging current

Max. 3 A automatic adjustment with UPS1100; otherwise selectable 0.3 A, 0.8 A, 3 A

Max. 4 A automatic adjustment with UPS1100; otherwise selectable 0.8 A, 1.75 A, 4 A

Max. 5 A automatic adjustment with UPS1100; otherwise selectable 0.8 A, 1.75 A, 5 A

Efficiency for normal operation and charged battery

97.7 %

98.2 %

98.8 %

Protection and monitoring

   

Reverse polarity protection

against input voltage Uin and against batteries

against input voltage Uin and against batteries

against input voltage Uin and against batteries

Overload / short-circuit protection

Yes, restart in normal operation

Yes, restart in normal operation

Yes, restart in normal operation

Signaling

     

Normal operation/buffer mode

LED 1 (OK/BAT) green/yellow and isolated changeover switch 1

LED 1 (OK/BAT) green/yellow and isolated changeover switch 1

LED 1 (OK/BAT) green/yellow and isolated changeover switch 1

Charging status (over 85% charged)

LED 2 (BAT>85%) green and isolated changeover switch 3

LED 2 (BAT>85%) green and isolated changeover switch 3

LED 2 (BAT>85%) green and isolated changeover switch 3

Alarm (not ready for buffering)

LED 3 (Alarm) red and isolated changeover switch 2

LED 3 (Alarm) red and isolated changeover switch 2

LED 3 (Alarm) red and isolated changeover switch 2

Battery status

LED 4 (BAT.FAULT) red and isolated changeover switch 2: Battery defective, yellow: selected buffering time not assured, yellow flashing: Overtemperature

LED 4 (BAT.FAULT) red and isolated changeover switch 2: Battery defective, yellow: selected buffering time not assured, yellow flashing: Overtemperature

LED 4 (BAT.FAULT) red and isolated changeover switch 2: Battery defective, yellow: selected buffering time not assured, yellow flashing: Overtemperature.

PROFINET interface

LED 5 (SF) green and LED 6 (RUN)

LED 5 (SF) green and LED 6 (RUN)

LED 5 (SF) green and LED 6 (RUN)

Ethernet

LED 7 (P1) green/yellow and LED 8 (P2) green/yellow, link and activity

LED 7 (P1) green/yellow and LED 8 (P2) green/yellow, link and activity

LED 7 (P1) green/yellow and LED 8 (P2) green/yellow, link and activity

General data

     

Radio interference level (EN 55022) / noise immunity

Class B / Noise immunity to EN 61000-6-2

Class B / Noise immunity to EN 61000-6-2

Class B / Noise immunity to EN 61000-6-2

Safety class

Class III (ext. circuit and power supply unit: SELV in accordance with EN 60950 required)

Class III (ext. circuit and power supply unit: SELV in accordance with EN 60950 required)

Class III (ext. circuit and power supply unit: SELV in accordance with EN 60950 required)

Degree of protection (EN 60529)

IP20

IP20

IP20

Ambient temperature during operation with natural convection

-25 ... +70 °C (derating from 60 °C)

-25 ... +70 °C (derating from 60 °C)

-25 ... +70 °C (derating from 60 °C)

Transport/storage temperature

-40 ... +85 °C

-40 ... +85 °C

-40 ... +85°C

Dimensions (W x H x D) in mm

50 x 125 x 125

50 x 125 x 125

70 x 150 x 125

Weight, approx.

0.38 kg without interface,
0.4 kg with USB,
0.44 kg with Ethernet/PROFINET interfaces

0.49 kg without interface,
0.41 kg with USB,
0.45 kg with Ethernet/PROFINET interfaces

0.65 kg without interface,
0.65 kg with USB,
0.7 kg with Ethernet/PROFINET interfaces

Installation

Snaps onto DIN rail EN 50022-35x15/7.5

Snaps onto DIN rail EN 50022-35x15/7.5

Snaps onto DIN rail EN 50022-35x15/7.5

Approvals

CE, cULus, CB, ATEX available soon: cCSAus Class I Div 2, GL, ABS

CE, cULus, CB, ATEX available soon: cCSAus Class I Div 2, GL, ABS

CE, cULus available soon: CB, ATEX, cCSAus Class I Div 2, GL, ABS


1) All SITOP 24 V DC power supplies are permissible without restriction

















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Установка обезжелезивания
Каталог оборудования 2015
Каталог продуктов Siemens Industry Приводная техника Техника автоматизации Системы автоматизации Системы визуализации SIMATIC HMI Системы идентификации Промышленные коммуникации SIMATIC NET Введение Industrial Ethernet PROFINET Введение Привода Контроллеры Система управления процессами SIMATIC PCS 7 Распределенная периферия Система управления перемещениями SIMOTION Системы ЧПУ SINUMERIK Устройства отображения и контроля Активные сетевые компоненты Промышленные ПК Коммутационные и защитные приборы для распределения энергии Обзор системы Измерительные приборы SENTRON Конфигурирование, визуализация и управление с SIMATIC Конфигурирование, визуализация и управление с SENTRON Производственные датчики Пассивные сетевые компоненты Аппаратура управления Блоки питания SITOP Блоки бесперебойного питания DC-UPS SITOP UPS1600 Датчики Инжиниринговые пакеты Engineering / Network management / Diagnostics Технологические компоненты PROFINET Системный интерфейс к SIMATIC HMI PROFIBUS AS-интерфейс IO-Link Промышленная беспроводная связь SINAUT ST7 Информационная безопасность в промышленности Сетевые переходы ECOFAST Промышленные аппараты управления SIRIUS Промышленные информационные технологии Управление на базе РС Системы управления процессом Датчики Блоки питания Продукты для специальных требований Автоматизация и безопасность зданий Низковольтная коммутационная техника Технология безопасности Системные решения и продукты для отраслей Сервис ... и все, что Вам еще необходимо

  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366  skenergo@mail.ru
Яндекс.Метрика