The UPS500S can be extended to 20 kW using UPS501S expansion modules to extend the buffering time. The table shows the maximum buffering time for the possible configurations and the two UPS500P units for different load currents.

The load current can be set to 1 A or 2 A with the UPS500S.

Selection table SITOP UPS500 (optional with SITOP UPS501S expansion module) and mains buffering times

Buffering and charging times

SITOP UPS500S/501S configurations

UPS500P

Basic unit

2.5 kW

5 kW

2.5 kW

5 kW

2.5 kW

5 kW

2.5 kW

5 kW

5 kW

10 kW

Expansion modules

-

-

1 ? 5 kW

1 ? 5 kW

2 ? 5 kW

2 ? 5 kW

3 ? 5 kW

3 ? 5 kW

-

-

Total energy

2.5 kW

5 kW

7.5 kW

10 kW

12.5 kW

15 kW

17.5 kW

20 kW

5 kW

10 kW

Load current

Buffer times

0.5 A

134 s

236 s

390 s

478 s

632 s

748 s

851 s

1007 s

284 s

647 s

0.8 A

90 s

167 s

266 s

346 s

440 s

527 s

580 s

706 s

190 s

435 s

1 A

75 s

138 s

219 s

296 s

365 s

414 s

490 s

572 s

153 s

351 s

2 A

38 s

76 s

122 s

156 s

203 s

230 s

265 s

306 s

80 s

152 s

3 A

26 s

52 s

82 s

106 s

136 s

159 s

186 s

213 s

53 s

108 s

4 A

19 s

39 s

61 s

81 s

101 s

120 s

139 s

160 s

40 s

84 s

5 A

15 s

31 s

49 s

65 s

81 s

95 s

111 s

130 s

30 s

68 s

6 A

12 s

26 s

40 s

55 s

67 s

80 s

94 s

106 s

25 s

57 s

7 A

10 s

21 s

34 s

47 s

58 s

69 s

81 s

82 s

21 s

49 s

8 A

8 s

18 s

29 s

40 s

50 s

59 s

69 s

79 s

-

-

10 A

6 s

15 s

23 s

32 s

39 s

47 s

54 s

62 s

-

-

12 A

4 s

12 s

19 s

26 s

32 s

38 s

44 s

52 s

-

-

15 A

3 s

9 s

14 s

20 s

25 s

30 s

35 s

40 s

-

-

Charing current

Charging times

2 A

54 s

120 s

158 s

223 s

263 s

318 s

355 s

417 s

130 s

360 s

1 A

110 s

205 s

311 s

425 s

503 s

625 s

695 s

816 s

-

-


Important information for selecting the energy storage units:

When the mains buffering times were determined, the discharge period of new or non-aged, completely charged capacitors was used as a basis. At a continuous ambient temperature of +50 °C, a loss of capacity of approx. 20% must be considered after a service life of 8 years.

Product

SITOP UPS500S 15 A

SITOP UPS500P 7 A

Power supply, type

Basic unit 15 A

Basic unit 7 A, IP65

Article No.

6EP1933-2EC41: (with USB port and 2.5 kWs)
6EP1933-2EC51: (with USB port and 5 kWs)

6EP1933-2NC01: (with USB port and 5 kWs)
6EP1933-2NC11: (with USB port and 10 kWs)

Input L+/M in normal operation

Controlled DC voltage

Controlled DC voltage

Rated voltage Uinrated1)

24 V DC

24 V DC

Voltage range

22 ... 29 V

22.5 ... 29 V

Connection threshold for buffering

22.5 V DC ± 0.1 V (factory setting), adjustable in the range 22 ... 25.5 V DC (in 0.5 V increments)

22.5 V DC ±0.1 V

Rated current Iin rated

15.2 A + approx. 2.3 A with empty energy storage (capacitor)

7 A + approx. 2 A with empty energy storage (capacitor)

Mains buffering

   

Mains buffering or buffering times without add-on modules

6EP1933-2EC41: 15 A for 3 s or 10 A for 6 s or 5 A for 15 s or 2 A for 38 s
6EP1933-2EC51: 15 A for 9 s or 10 A for 15 s or 5 A for 31 s or 2 A for 76 s

7 A for 49 s or 5 A for 68 s or 3 A for 108 s or 1 A for 351 s

Mains buffering or buffering times with expansion modules

For longer buffering times, see table

Not applicable

On/off control circuit

External isolated NO contact (loading max. 15 V DC/max. 10 mA) is required; opening the control circuit terminates buffer mode.

Not applicable

Methods of setting the buffering time

Adjustable using DIP switches to a maximum buffering time up to forced shutdown at approx. 7 V internal capacitor voltage (output remains constant at 24 V up to that point) or to a time limit of 5 ... 315 s (in 10 s increments) if the energy content is sufficient for the required current

Not applicable

Interruption

Adjustable with DIP switch, either:

  • Interruption of the output voltage despite returning input voltage for 5 s following expiry of set buffering time to support automatic restarting of Industrial PCs

or

  • No forced interruption on expiry of the set buffer time

Not applicable

Output L+/M in normal operation

   

Rated voltage Uoutrated

24 V DC

24 V DC

Voltage range

23.3 ... 24.7 V DC or 24 V DC ± 3%

23.3 ... 24.7 V DC or 24 V DC ± 3%

Startup delay

approx. 600 ms

approx. 600 ms

Voltage rise

ca. 25 ms

ca. 25 ms

Output current Iout

0 ... 15 A

0 ... 7 A

Dynamic current with overload

Electronic current limitation to typically 25 A for approx. 200 ms, then electronic shutdown of the output with automatic restart attempts (approx. 20 s intervals between restart attempts)

Electronic shutdown at typ. 30 A, automatic restart after 20 s

Dynamic current with short-circuit

Electronic current limitation to typically 25 A for approx. 110 ms, then electronic shutdown of the output with automatic restart attempts (approx. 20 s intervals between restart attempts)

Electronic shutdown at typ. 30 A, automatic restart after 20 s

Output L+/M with buffer mode

   

Rated voltage Uoutrated

24 V DC

24 V DC

Approximate voltage range

23.3 ... 24.7 V DC or 24 V DC ± 3%

23.3 ... 24.7 V DC or 24 V DC ± 3%

Output current Iout

0 ... 15 A

0 ... 7 A

Dynamic current with overload

Electronic current limitation to typically. 25 A for approx. 200 ms, then electronic shutdown of the output (restart following return to normal operation)

Electronic shutdown at typ. 30 A, automatic restart after 20 s

Dynamic current with short-circuit

Electronic current limitation to typically. 25 A for approx. 110 ms, then electronic shutdown of the output (restart following return to normal operation)

Electronic shutdown at typ. 30 A, automatic restart after 20 s

Charging current

Approx. 1 A (factory setting), adjustable to 1 A or 2 A (charging is carried out with closed and open on/off circuit)

2 A permanently set

Charging time after a discharge

6EP1933-2EC41: 110 s with 1 A, 54 s with 2 A
6EP1933-2EC51: 205 s with 1 A, 120 s with 2 A

Approx. 300 s

Charging time with add-on modules

For longer charging times, see table

Not applicable

Efficiency / heat loss

 

 

At Uout rated, Iout rated approx.

97.5 % / 9 W

96.5 % / 5.2 W

Protection and monitoring

   

Reverse polarity protection

against polarity reversal on input voltage

against polarity reversal on input voltage

Overload protection

Electronic shutdown of the output in accordance with "dynamic current with overload" in normal operation (automatic restart attempts) or in buffer mode (restart following return to normal operation)

Electronic shutdown of the output in accordance with "dynamic current with overload" in normal operation (automatic restart attempts) or in buffer mode (restart following return to normal operation)

Thermal overload protection

Short-circuit protection

Electronic shutdown of the output in accordance with "dynamic current with short-circuit" in normal operation (automatic restart attempts) or in buffer mode (restart following return to normal operation), built-in (inaccessible) 20 A fuse.

Electronic shutdown of the output in accordance with "dynamic current with overload" in normal operation (automatic restart attempts) or in buffer mode (restart following return to normal operation)

Thermal overload protection

Signaling

 

 

Normal operation

Green LED (OK) and isolated relay contact (changeover contact)2)

Green LED (OK )

Buffer mode (capacitor supplies load alone or in addition to the PS in the case of overload)

Green LED (Bat) and isolated relay contact (changeover contact) 2)

Yellow LED (Bat)

Alarm (buffer not ready, or prewarning from < 12 V capacitor voltage)

Red LED (alarm) and isolated relay contact (changeover contact)2)

Red LED (Alarm)

"Capacitor charge > 85 %" 3)

Second green LED (Bat > 85 %) and isolated NO contact closed (off position = open)

Second green LED (Bat > 85 %)

USB port

Output of all alarm signals and receipt of the "Remote Timerstart" signal.

Technical design: Specification 2.0 with full speed, i.e. 2 Mbps Supplied with +5 V ("self powered").

Required connection to the PC: Commercially available 4-core shielded cable, 90 ohms, max. 5 m, USB series "A" connector to PC and USB series "B" connector to DC UPS

Output of all alarm signals and receipt of the "Remote Timerstart" signal.

Technical design: Specification 2.0 with full speed, i.e. 2 Mbps Supplied with +5 V ("self powered").

Required connection to the PC: see connector set

Software

A software tool for reading out and processing the signals (can run under Windows 2000, Windows XP, Windows Vista and Windows 7) is available for downloading from the Internet at
http://www.siemens.com/sitop-ups
. This site also provides more information on the interface.

A software tool for reading out and processing the signals (can run under Windows 2000, Windows XP, Windows Vista and Windows 7) is available for downloading from the Internet at
http://www.siemens.com/sitop-ups
. This site also provides more information on the interface.

Control signals

   

On/off control signal

Buffering is terminated by opening the control circuit or by means of DIP switches on the device (DIP switch must be in "Off" position). All other functions are retained.

Not applicable

"Remote Timerstart" via USB port

Starts mains buffering for the set buffering time

Starts mains buffering for the set buffering time

Safety

   

Primary/secondary isolation

No

No

Protection class

Class III (ext. circuit and power supply unit: SELV in accordance with EN 60950 required)

Class III (ext. circuit and power supply unit: SELV in accordance with EN 60950 required)

EMC

   

Emitted interference

Radio interference suppression according to EN 55022, limit-value curve B

Radio interference suppression according to EN 55022, limit-value curve B

Interference immunity

Interference immunity according to EN 61000-6-2

Interference immunity according to EN 61000-6-2

Ambient conditions

   

Ambient temperature in operation

0 ... +60 °C with natural convection

0 ... +55 °C with natural convection

Transport/storage temperature

-40 ... +70 °C

-40 ... +70 °C

Degree of protection (EN 60529)

IP20

IP65

Humidity class

Rated conditions in accordance with EN 60721, climate class 3K3 (relative humidity 5% ... 85% and absolute humidity 1 g/m3 ... 25 g/m3; no condensation)

Rated conditions in accordance with EN 60721, climate class 3K3 (relative humidity 5% ... 85% and absolute humidity 1 g/m3 ... 25 g/m3; no condensation)

Approvals

   

CE

Yes

Yes

UL/cUL (CSA) approval

cULus-listed (UL 508, CSA C22.2 No. 107.1) File E197259

-

Mechanics

   

Input connections 24 V DC

2 screw terminals for 1 ... 4 mm2/17 ... 11 AWG

See connector set4)

Output connections 24 V DC

4 screw terminals for 1 ... 4 mm2/17 ... 11 AWG

See connector set4)

Connections for control circuit and alarm signals

10 screw terminals for 0.5 ... 2.5 mm2/20 ... 13 AWG

Not applicable

USB port

Yes

Yes

Dimensions (W x H x D) in mm

120 x 125 x approx. 125

400 (without connector) x 80 x 80
470 (without connector) x 80 x 80

Required clearances

50 mm above and 50 mm below the device

50 mm above and 50 mm below the device

Weight

Approx. 1.0 kg

Approx. 1.9 kg
Approx. 2.2 kg

Installation

Can be snapped onto standard mounting rail EN 60715 35x7.5/15

Screw mounting


1) All SITOP 24 V DC power supplies are permissible without restriction

2) Permissible contact rating: 60 V DC/1 A or 30 V AC/1 A.

3) 85% with regard to residual capacity still available depending on aging. The original capacity (= capacity when new) reduces by only approx. 20 % within 8 years of operation even at a high ambient temperature of the device of +50 °C, for example, so that 80 % residual capacity still remains. The backup times also reduce by approximately 20 % in 8 years (at +50 °C) with small currents (up to approximately 5 A), and by approximately 30 % with high load currents (over 10 A).

Note: The lower the ambient temperature, the smaller the capacity reduction (approximately one half per 10 °C lower ambient temperature, that is at +40 °C, for example, only 10 % capacity reduction in 8 years)

4) “The connector set contains connection plugs for input and output and pre-assembled USB cables 2 m long (connector set not included in the scope of delivery of SITOP UPS500P); MLFB: 6EP1975-2ES00

Product

SITOP UPS501S

Power supply, type

Expansion module

Article No.

6EP1935-5PG01

Mechanics

 

Connections

Can be easily connected to SITOP UPS500S via a user-friendly plug-in system

Dimensions (W x H x D) in mm

Approx. 70 x 125 x 125

Weight

Approx. 0.7 kg

Installation

Can be snapped onto standard mounting rail EN 60715 35x7.5/15


















skener.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Арматура DENDOR

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Датчики и измерители

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Регуляторы и регистраторы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Пневматическое оборудование

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Краны и Клапаны

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Измерительные приборы

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Системы беспроводного управления «умный дом»

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Бесконтактные выключатели Конечные выключатели Оптические датчики Энкодеры

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Установка умягчения

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30


Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Установка обезжелезивания
Каталог оборудования 2015
Каталог продуктов Siemens Industry Приводная техника Техника автоматизации Системы автоматизации Системы визуализации SIMATIC HMI Системы идентификации Промышленные коммуникации SIMATIC NET Промышленные аппараты управления SIRIUS Промышленные информационные технологии Управление на базе РС Промышленные компьютеры SIMATIC PC-based Control Встраиваемые системы автоматизации Встраиваемые системы на базе SIMATIC PC Комплекты с SIMATIC IPC227D Комплекты с SIMATIC IPC427D Комплекты с SIMATIC IPC427C Комплекты с SIMATIC HMI IPC277D Комплекты с SIMATIC IPC477D SIMATIC HMI IPC477C embedded Встраиваемые системы на базе Box PC Встраиваемые системы на базе Panel PC Обзор Компоненты для расширения Системы на флэш-дисках SIMATIC PC USB FlashDrive Модули ввода/вывода PC IO Промышленный USB Hub4 Комплект дистанционного управления для SIMATIC Panel PC SIMATIC IPC Image & Partition Creator SIMATIC PC DiagMonitor SIMATIC IPC Remote Manager SIMATIC PC BIOS-Manager SIMATIC ADDM Блоки бесперебойного питания DC-UPS Модули DC-UPS с модулями батарей Модули DC-UPS со встроенными конденсаторами SITOP UPS500 Принтеры/устройства ввода/аксессуары Блоки бесперебойного питания Masterguard Системы управления процессом Датчики Блоки питания Продукты для специальных требований Автоматизация и безопасность зданий Низковольтная коммутационная техника Технология безопасности Системные решения и продукты для отраслей Сервис ... и все, что Вам еще необходимо

  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366  skenergo@mail.ru
Яндекс.Метрика