Input
|
|
|
Point-to-point connection to a HART field device or Point-to-point connection to a 4 ... 20 mA field device or Up to eight HART field devices with an external voltage supply integrated using multidrop
|
Communication
|
- HART communication with multidrop, as primary or secondary HART master (can be specified)
- 4 ... 20 mA current signal with a point-to-point connection scaling in user-defined measuring range in SITRANS AW210
- Linear
- User-defined scaling with up to 32 points
|
Protocol
|
HART V7 (compatible with previous HART versions)
|
Output
|
|
Communication
|
WirelessHART V7
|
Transmission frequency band
|
2.4 … 2.4835 GHz (ISM band), 16-channel frequency hopping spread spectrum
|
Range (under reference conditions)
|
Outside up to 235 m (771.00 ft)
|
RF signal strength
|
10 dBm
|
Output signals
|
|
|
- HART Cmd 3
Measured current and up to 4 other dynamic variables (measured values, derived values) or device variables
- HART Cmd 9
Up to 8 dynamic variables with status
- HART Cmd 48
Additional status information
|
|
Scaled or linearized process values
|
|
- HART Cmd 3
Measured current and up to 4 other dynamic variables (measured values, derived values) or device variables
- HART Cmd 9
Up to 8 dynamic variables with status
- HART Cmd 48
Additional status information
|
Update time for output signals
|
You can set the update times separately for the adapter and the connected devices.
The possible settings are:
- 1, 2, 4, 8, 16, 32 s
- 1, 2, 5, 10, 30, 60 min (times also depend on the gateway)
|
Measuring accuracy
|
|
Max. measuring error (4 ... 20 mA circuit)
|
1 % of measuring range, 40 … 85 °C (104 … 185 °F)
|
Rated conditions
|
|
Location
|
Outside/inside
|
Ambient conditions
|
|
|
-40 ... +85 °C (-40 ... +185 °F)
In hazardous areas up to 75 °C (167 °F)
|
|
-40 ... +85 °C (-40 ... +185 °F)
|
Electromagnetic compatibility
|
To EN 301 489-17 and EN 300 328-1
|
Design
|
|
Weight
|
0.46 kg (1.01 lb)
|
Enclosure
|
|
|
Enclosure: Aluminum alloy, RoHS-compliant polyurethane corrosion-resistant coating Cap: Resin
|
|
?" NPT female thread
|
Degree of protection
|
IP68
|
Aerial
|
Potted in enclosure
|
Auxiliary power
|
|
Power supply
|
Loop power 1 … DC 2.5 V, can be set by user in 0.5 V DC increments
|
Loop-powered, operating current
|
DC 3.2 … 25 mA operating current; overvoltage, surge and reverse polarity protection
|
Certificates and approvals
|
|
Wireless communication approvals
|
- CE (R&TTE, EMC)
- FCC Part 15.247 for wireless applications in the 2.4 GHz transmission frequency band
- IC
|
Explosion protection
|
|
Intrinsic safe "i" gases and vapors
|
II 1G Ex ia IIC T*; IP68 T* = T5 for Ta = -40 ... +85 °C T* = T6 for Ta = -40 ... +75 °C
|
Intrinsic safe dust
|
II 1 D Ex iaD 20 IP68 T95C; Ta = -40 ... +85 °C
|
Non-sparking (zone 2)
|
II 3 G Ex nA nC IIC T* Gc; IP68 T* = T5 for Ta = -40 ... +85 °C T* = T6 for Ta = -40 ... +75 °C
|
Explosion protection to FM for US Intrinsic safe, Non-sparking
|
IS/I,II,III/1/ABCDEFG/ T5 Ta = -40 ... +85 °C, T6 Ta = -40 ... +75 °C
NI/I/2/ABCD/ T5 Ta = -40 ... +85 °C, T6 Ta = -40 ... +75 °C
S/II,III/2/EFG/ T5 Ta = -40 ... +85 °C, T6 Ta = -40 ... +75 °C
I/0/AEx ia/IIC/ T5 Ta = -40 ... +85 °C T6 Ta = -40 ... +75 °C;
20/AEx iaD/T95°C; Ta = -40 ... 85°C
I/2/AEx nA nC/IIC/ T5 Ta = -40 ... +85 °C, T6 Ta = -40 ... +75 °C; IP68
|
Explosion protection to FM for CA Intrinsic safe, Non-sparking
|
IS/I,II,III/1/ABCDEFG/ T5 Ta = -40 ... +85 °C T6 Ta = -40 ... +75 °C;
NI/I/2/ABCD/ T5 Ta = -40 ... +85 °C T6 Ta = -40 ... +75 °C;
S/II,III/2/EFG/ T5 Ta = -40 ... +85 °C T6 Ta = -40 ... +75 °C;
I/0/Ex ia/IIC/ T5 Ta = -40 ... +85 °C T6 Ta = -40 ... +75 °C;
I/2/Ex nA nC/IIC/ T5 Ta = -40 ... +85 °C T6 Ta = -40 ... +75 °C
II/1/EFG Ta = -40 ... +85°C; IP68
|
Flameproof gases and vapors
|
II 2 G Ex d IIC T* Gb; IP68 T* = T5 for Ta = -40 ... +85 °C T* = T6 for Ta = -40 ... +75 °C
|
Protection by enclosure dust
|
II 2 D Ex tb IIIC T95°C Ta = -40 ... +85°C; IP68
|
Explosion protection to FM for US Explosionproof, flameproof, gas, dust
|
XP/I/1/ABCD I/1 AEx d IIC T5, T6 Gb DIP/II,III/1/EFG
21/AEx tb IIIC T95°C T5 Ta = -40 ... +85°C, T6 Ta = -40 ... +75°C Type 6P, IP68
|
Explosion protection to FM for CA Explosionproof, flameproof, gas, dust
|
XP/I/1/ABCD I/1 Ex d IIC T5, T6 Gb DIP/II,III/1/EFG T5 Ta = -40 ... +85°C, T6 Ta = -40 ... +75°C
|