Product
|
SITOP UPS500S 15 A
|
SITOP UPS500P 7 A
|
Power supply, type
|
Basic unit 15 A
|
Basic unit 7 A, IP65
|
Article No.
|
6EP1933-2EC41: (with USB port and 2.5 kWs) 6EP1933-2EC51: (with USB port and 5 kWs)
|
6EP1933-2NC01: (with USB port and 5 kWs) 6EP1933-2NC11: (with USB port and 10 kWs)
|
Input L+/M in normal operation
|
Controlled DC voltage
|
Controlled DC voltage
|
Rated voltage Uinrated1)
|
24 V DC
|
24 V DC
|
Voltage range
|
22 ... 29 V
|
22.5 ... 29 V
|
Connection threshold for buffering
|
22.5 V DC ± 0.1 V (factory setting), adjustable in the range 22 ... 25.5 V DC (in 0.5 V increments)
|
22.5 V DC ±0.1 V
|
Rated current Iin rated
|
15.2 A + approx. 2.3 A with empty energy storage (capacitor)
|
7 A + approx. 2 A with empty energy storage (capacitor)
|
Mains buffering
|
|
|
Mains buffering or buffering times without add-on modules
|
6EP1933-2EC41: 15 A for 3 s or 10 A for 6 s or 5 A for 15 s or 2 A for 38 s 6EP1933-2EC51: 15 A for 9 s or 10 A for 15 s or 5 A for 31 s or 2 A for 76 s
|
7 A for 49 s or 5 A for 68 s or 3 A for 108 s or 1 A for 351 s
|
Mains buffering or buffering times with expansion modules
|
For longer buffering times, see table
|
Not applicable
|
On/off control circuit
|
External isolated NO contact (loading max. 15 V DC/max. 10 mA) is required; opening the control circuit terminates buffer mode.
|
Not applicable
|
Methods of setting the buffering time
|
Adjustable using DIP switches to a maximum buffering time up to forced shutdown at approx. 7 V internal capacitor voltage (output remains constant at 24 V up to that point) or to a time limit of 5 ... 315 s (in 10 s increments) if the energy content is sufficient for the required current
|
Not applicable
|
Interruption
|
Adjustable with DIP switch, either:
- Interruption of the output voltage despite returning input voltage for 5 s following expiry of set buffering time to support automatic restarting of Industrial PCs
or
- No forced interruption on expiry of the set buffer time
|
Not applicable
|
Output L+/M in normal operation
|
|
|
Rated voltage Uoutrated
|
24 V DC
|
24 V DC
|
Voltage range
|
23.3 ... 24.7 V DC or 24 V DC ± 3%
|
23.3 ... 24.7 V DC or 24 V DC ± 3%
|
Startup delay
|
approx. 600 ms
|
approx. 600 ms
|
Voltage rise
|
ca. 25 ms
|
ca. 25 ms
|
Output current Iout
|
0 ... 15 A
|
0 ... 7 A
|
Dynamic current with overload
|
Electronic current limitation to typically 25 A for approx. 200 ms, then electronic shutdown of the output with automatic restart attempts (approx. 20 s intervals between restart attempts)
|
Electronic shutdown at typ. 30 A, automatic restart after 20 s
|
Dynamic current with short-circuit
|
Electronic current limitation to typically 25 A for approx. 110 ms, then electronic shutdown of the output with automatic restart attempts (approx. 20 s intervals between restart attempts)
|
Electronic shutdown at typ. 30 A, automatic restart after 20 s
|
Output L+/M with buffer mode
|
|
|
Rated voltage Uoutrated
|
24 V DC
|
24 V DC
|
Approximate voltage range
|
23.3 ... 24.7 V DC or 24 V DC ± 3%
|
23.3 ... 24.7 V DC or 24 V DC ± 3%
|
Output current Iout
|
0 ... 15 A
|
0 ... 7 A
|
Dynamic current with overload
|
Electronic current limitation to typically. 25 A for approx. 200 ms, then electronic shutdown of the output (restart following return to normal operation)
|
Electronic shutdown at typ. 30 A, automatic restart after 20 s
|
Dynamic current with short-circuit
|
Electronic current limitation to typically. 25 A for approx. 110 ms, then electronic shutdown of the output (restart following return to normal operation)
|
Electronic shutdown at typ. 30 A, automatic restart after 20 s
|
Charging current
|
Approx. 1 A (factory setting), adjustable to 1 A or 2 A (charging is carried out with closed and open on/off circuit)
|
2 A permanently set
|
Charging time after a discharge
|
6EP1933-2EC41: 110 s with 1 A, 54 s with 2 A 6EP1933-2EC51: 205 s with 1 A, 120 s with 2 A
|
Approx. 300 s
|
Charging time with add-on modules
|
For longer charging times, see table
|
Not applicable
|
Efficiency / heat loss
|
|
|
At Uout rated, Iout rated approx.
|
97.5 % / 9 W
|
96.5 % / 5.2 W
|
Protection and monitoring
|
|
|
Reverse polarity protection
|
against polarity reversal on input voltage
|
against polarity reversal on input voltage
|
Overload protection
|
Electronic shutdown of the output in accordance with "dynamic current with overload" in normal operation (automatic restart attempts) or in buffer mode (restart following return to normal operation)
|
Electronic shutdown of the output in accordance with "dynamic current with overload" in normal operation (automatic restart attempts) or in buffer mode (restart following return to normal operation)
Thermal overload protection
|
Short-circuit protection
|
Electronic shutdown of the output in accordance with "dynamic current with short-circuit" in normal operation (automatic restart attempts) or in buffer mode (restart following return to normal operation), built-in (inaccessible) 20 A fuse.
|
Electronic shutdown of the output in accordance with "dynamic current with overload" in normal operation (automatic restart attempts) or in buffer mode (restart following return to normal operation)
Thermal overload protection
|
Signaling
|
|
|
Normal operation
|
Green LED (OK) and isolated relay contact (changeover contact)2)
|
Green LED (OK )
|
Buffer mode (capacitor supplies load alone or in addition to the PS in the case of overload)
|
Green LED (Bat) and isolated relay contact (changeover contact) 2)
|
Yellow LED (Bat)
|
Alarm (buffer not ready, or prewarning from < 12 V capacitor voltage)
|
Red LED (alarm) and isolated relay contact (changeover contact)2)
|
Red LED (Alarm)
|
"Capacitor charge > 85 %" 3)
|
Second green LED (Bat > 85 %) and isolated NO contact closed (off position = open)
|
Second green LED (Bat > 85 %)
|
USB port
|
Output of all alarm signals and receipt of the "Remote Timerstart" signal.
Technical design: Specification 2.0 with full speed, i.e. 2 Mbps Supplied with +5 V ("self powered").
Required connection to the PC: Commercially available 4-core shielded cable, 90 ohms, max. 5 m, USB series "A" connector to PC and USB series "B" connector to DC UPS
|
Output of all alarm signals and receipt of the "Remote Timerstart" signal.
Technical design: Specification 2.0 with full speed, i.e. 2 Mbps Supplied with +5 V ("self powered").
Required connection to the PC: see connector set
|
Software
|
A software tool for reading out and processing the signals (can run under Windows 2000, Windows XP, Windows Vista and Windows 7) is available for downloading from the Internet at http://www.siemens.com/sitop-ups . This site also provides more information on the interface.
|
A software tool for reading out and processing the signals (can run under Windows 2000, Windows XP, Windows Vista and Windows 7) is available for downloading from the Internet at http://www.siemens.com/sitop-ups . This site also provides more information on the interface.
|
Control signals
|
|
|
On/off control signal
|
Buffering is terminated by opening the control circuit or by means of DIP switches on the device (DIP switch must be in "Off" position). All other functions are retained.
|
Not applicable
|
"Remote Timerstart" via USB port
|
Starts mains buffering for the set buffering time
|
Starts mains buffering for the set buffering time
|
Safety
|
|
|
Primary/secondary isolation
|
No
|
No
|
Protection class
|
Class III (ext. circuit and power supply unit: SELV in accordance with EN 60950 required)
|
Class III (ext. circuit and power supply unit: SELV in accordance with EN 60950 required)
|
EMC
|
|
|
Emitted interference
|
Radio interference suppression according to EN 55022, limit-value curve B
|
Radio interference suppression according to EN 55022, limit-value curve B
|
Interference immunity
|
Interference immunity according to EN 61000-6-2
|
Interference immunity according to EN 61000-6-2
|
Ambient conditions
|
|
|
Ambient temperature in operation
|
0 ... +60 °C with natural convection
|
0 ... +55 °C with natural convection
|
Transport/storage temperature
|
-40 ... +70 °C
|
-40 ... +70 °C
|
Degree of protection (EN 60529)
|
IP20
|
IP65
|
Humidity class
|
Rated conditions in accordance with EN 60721, climate class 3K3 (relative humidity 5% ... 85% and absolute humidity 1 g/m3 ... 25 g/m3; no condensation)
|
Rated conditions in accordance with EN 60721, climate class 3K3 (relative humidity 5% ... 85% and absolute humidity 1 g/m3 ... 25 g/m3; no condensation)
|
Approvals
|
|
|
CE
|
Yes
|
Yes
|
UL/cUL (CSA) approval
|
cULus-listed (UL 508, CSA C22.2 No. 107.1) File E197259
|
-
|
Mechanics
|
|
|
Input connections 24 V DC
|
2 screw terminals for 1 ... 4 mm2/17 ... 11 AWG
|
See connector set4)
|
Output connections 24 V DC
|
4 screw terminals for 1 ... 4 mm2/17 ... 11 AWG
|
See connector set4)
|
Connections for control circuit and alarm signals
|
10 screw terminals for 0.5 ... 2.5 mm2/20 ... 13 AWG
|
Not applicable
|
USB port
|
Yes
|
Yes
|
Dimensions (W x H x D) in mm
|
120 x 125 x approx. 125
|
400 (without connector) x 80 x 80 470 (without connector) x 80 x 80
|
Required clearances
|
50 mm above and 50 mm below the device
|
50 mm above and 50 mm below the device
|
Weight
|
Approx. 1.0 kg
|
Approx. 1.9 kg Approx. 2.2 kg
|
Installation
|
Can be snapped onto standard mounting rail EN 60715 35x7.5/15
|
Screw mounting
|