Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/new/cat.php on line 184
For general technical data, see section "DC Converters"
Type |
||
---|---|---|
6RA8000-0MV62-0AA0 |
||
Rated armature supply voltage that can be sensed |
V |
50/125/250/575/1 000 |
Rated supply voltage, electronics power supply |
V |
24 DC (18 … 30 V DC);In = 5 A |
Rated field supply voltage1) |
V |
480 V 2 AC (+10/-20 %) |
Rated frequency |
Hz |
45 … 65 |
Rated DC field voltage 1) |
V |
Max. 390 |
Rated DC field current |
A |
40 |
Normal ambient temperature in operation |
°C |
0 … +55 |
Dimensions |
||
|
mm |
271 |
|
mm |
388 |
|
mm |
253 |
Weight, approx. |
kg |
12 |
1) The field supply voltage can lie below the rated field voltage (set using a parameter, input voltages of up to 85 V are permissible). The output voltage decreases accordingly. The specified DC output voltage can be reliably provided up to a 5 % undervoltage of the line supply voltage (rated field supply voltage).