PROFIBUS DP distinguishes between two different master classes and one slave class:
Class 1 DP master
The DP master Class 1 is the central component in PROFIBUS DP. The central master station exchanges information with distributed stations (DP slaves) in a fixed, repeated message cycle.
Class 2 DP master
Devices of this type are used (programming, configuration or control devices) during start-up, for configuring the DP system, for diagnostics or controlling the plant during normal operation. A DP master Class 2 can be used, for example, to read the input, output, diagnostic and configuration data of the slaves.
DP slave
A DP slave is an I/O device which receives output information or setpoints from the DP master and sends input information, measured values or actual values to the DP master in response. A DP slave never sends data independently, it must always be prompted by the DP master.
The volume of input and output data depends on the device and can be up to 244 bytes per DP slave and transfer direction.