Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2012
архивный
(4872) 700-366
skenergo@mail.ru

Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/new/cat.php on line 184
SIPLUS HCS716I heater controller
Ambient conditions for all SIPLUS HCS716I components

Climatic ambient conditions

Operating temperature

  • Permissible range

0 ... 55 °C

  • Relative humidity at 25 °C

95 %

  • Temperature gradient

10 K/h

Storage temperature

  • Permissible range

-40 ... 70 °C

  • Relative humidity at 25 °C

95 %

  • Temperature gradient

20 K/h

Air pressure during operation

  • Minimum

860 hPa (= 1 500 m above sea level) (reduced cooling performance at lower air pressure)

  • Maximum

1 080 hPa

Air pressure during storage

  • Minimum

660 hPa (= 3 500 m above sea level)

  • Maximum

1 080 hPa

Ventilation

Self ventilation or forced ventilation

Mechanical ambient conditions

Vibration during operation (stationary use)

IEC 60068-2-6 Test FC (10 cycles per axis)

  • 10 ... 58 Hz

0.075 mm amplitude

  • 58 ... 150 Hz

9.8 m/s2 (= 1 g constant acceleration)

Vibration during transport/storage (in delivery packaging)

IEC 60068-2-6 Test FC (10 cycles per axis)

  • 5 ... 9 Hz

3.5 mm amplitude

  • 9 ... 500 Hz

9.8 m/s2 (= 1 g constant acceleration)

Shock during operation (stationary use)

IEC 60068-2-27 Test EA
150 m/s2 15 g, half-sine
Duration 11 ms
3 shocks per axis and direction

Shock during transport/storage (in delivery packaging)

IEC 60068-2-29 Test EB
250 m/s2 25 g, half-sine
Duration 6 ms
1 000 shocks per axis and direction

Electromagnetic compatibility

(Heating control is installed in control cabinet)

Radio interference suppression
(emitted interference)

EN 61000-6-4
Group 1, Class A

Immunity to conducted interference (burst)

EN 61000-4-4

  • AC voltage power supply lines

2 kV with switching network

  • Signal lines which exit the device

1 kV with clamp

Immunity to conducted interference (HF irradiation)

EN 61000-4-6: 10 V (0.15 to 80 MHz)

Immunity to electrostatic discharge (ESD)
(only tested on the frame)

EN 61000-4-2

  • Contact discharge

4 kV

  • Discharge via air

8 kV

Immunity to high-frequency interference

EN 61000-4-3
10 V/m (80 ... 1 000 MHz)
3 V/m (1.4  ... 2.0 GHz)
1 V/m (2.0 ... 2.7 GHz)

Immunity to high-energy pulses (surge)

EN 61000-4-5

  • Mains supply cables, signal cables
  • Symmetrical

1 kV

  • Asymmetrical

2 kV

  • PROFIBUS cable
  • Asymmetrical

1 kV

























































  © ООО "СК ЭНЕРГО" 2007-2022