Ambient conditions for all SIPLUS HCS716I components
Climatic ambient conditions |
|
Operating temperature |
|
|
0 ... 55 °C |
|
95 % |
|
10 K/h |
Storage temperature |
|
|
-40 ... 70 °C |
|
95 % |
|
20 K/h |
Air pressure during operation |
|
|
860 hPa (= 1 500 m above sea level) (reduced cooling performance at lower air pressure) |
|
1 080 hPa |
Air pressure during storage |
|
|
660 hPa (= 3 500 m above sea level) |
|
1 080 hPa |
Ventilation |
Self ventilation or forced ventilation |
Mechanical ambient conditions |
|
Vibration during operation (stationary use) |
IEC 60068-2-6 Test FC (10 cycles per axis) |
|
0.075 mm amplitude |
|
9.8 m/s2 (= 1 g constant acceleration) |
Vibration during transport/storage (in delivery packaging) |
IEC 60068-2-6 Test FC (10 cycles per axis) |
|
3.5 mm amplitude |
|
9.8 m/s2 (= 1 g constant acceleration) |
Shock during operation (stationary use) |
IEC 60068-2-27 Test EA |
Shock during transport/storage (in delivery packaging) |
IEC 60068-2-29 Test EB |
Electromagnetic compatibility (Heating control is installed in control cabinet) |
|
Radio interference suppression |
EN 61000-6-4 |
Immunity to conducted interference (burst) |
EN 61000-4-4 |
|
2 kV with switching network |
|
1 kV with clamp |
Immunity to conducted interference (HF irradiation) |
EN 61000-4-6: 10 V (0.15 to 80 MHz) |
Immunity to electrostatic discharge (ESD) |
EN 61000-4-2 |
|
4 kV |
|
8 kV |
Immunity to high-frequency interference |
EN 61000-4-3 |
Immunity to high-energy pulses (surge) |
EN 61000-4-5 |
|
|
|
1 kV |
|
2 kV |
|
|
|